Closed tank DP Level Transmitter with cleaning leg Calibration

Schematic Diagram of a Closed tank DP Level Transmitter with cleaning leg Calibration
Closed tank DP Level Transmitter with cleaning leg Calibration

Formulas:

Min range = SG x h

Max range = SG x h

Example:

If the height of an X is 5 meters in which there is a liquid that has a density of 1 g / cm3, what is the range of calibration on the transmitter?

SG = 1

Min range = SG x h
= 1 x 0 m
= 0 mH 2 O

Max range = SG x h
= 1 x 5 m
= 5 mH 2 O

The transmitter Range = 0 to 5 mH 2 O