Inst ToolsInst ToolsInst Tools
  • Courses
  • Videos
  • Q & A
    • Interview
      • Instrumentation
      • Electronics
      • Electrical
      • Practical Questions
    • MCQ
      • Instrumentation MCQ
      • Electrical MCQ
      • Electronics MCQ
      • Control Systems MCQ
      • Analog Electronics MCQ
      • Digital Electronics MCQ
      • Power Electronics MCQ
      • Microprocessor MCQ
      • Multiple Choice Questions
  • EE
    • Electronics
      • Electronics Q & A
      • Electronic Basics
      • Electronic Devices & Circuits
      • Electronics Animation
      • Digital Electronics
    • Electrical
      • Electrical Basics
      • Electrical Q & A
      • Power Electronics
      • Electrical Machines
      • Electrical Animation
      • Power Systems
      • Switchgear & Protection
      • Transmission & Distribution
  • Measure
    • Control Valves
    • Calibration
    • Temperature
    • Pressure
    • Flow
    • Level
    • Analyzers
    • Switches
    • Vibration
    • Solenoid Valve
  • Control
    • PLC Tutorials
    • Control Systems
    • Safety Instrumented System (SIS)
    • Communication
    • Fire & Gas System
  • More
    • Design
    • Tools
    • Animation
    • Basics
    • Formulas
    • Standards
    • TextBooks
    • Common
    • Software
    • Excel Tools
    • Erection & Commissioning
    • Process Fundamentals
    • Videos
    • Books
Search
All rights reserved. Reproduction in whole or in part without written permission is prohibited.
Reading: Doubtful Temperature Readings threatens Soaking Pit Wrecks 
Share
Notification Show More
Font ResizerAa
Inst ToolsInst Tools
Font ResizerAa
  • Courses
  • PLC Tutorials
  • Control Systems
Search
  • Courses
  • Videos
  • Q & A
    • Interview
    • MCQ
  • EE
    • Electronics
    • Electrical
  • Measure
    • Control Valves
    • Calibration
    • Temperature
    • Pressure
    • Flow
    • Level
    • Analyzers
    • Switches
    • Vibration
    • Solenoid Valve
  • Control
    • PLC Tutorials
    • Control Systems
    • Safety Instrumented System (SIS)
    • Communication
    • Fire & Gas System
  • More
    • Design
    • Tools
    • Animation
    • Basics
    • Formulas
    • Standards
    • TextBooks
    • Common
    • Software
    • Excel Tools
    • Erection & Commissioning
    • Process Fundamentals
    • Videos
    • Books
Follow US
All rights reserved. Reproduction in whole or in part without written permission is prohibited.
Inst Tools > Blog > Root Cause Analysis (RCA) > Doubtful Temperature Readings threatens Soaking Pit Wrecks 

Doubtful Temperature Readings threatens Soaking Pit Wrecks 

Instrumentation engineering root cause analysis of doubtful temperature readings of temperature recorder that threatens soaking pit wrecks.

Last updated: September 28, 2022 2:51 pm
S Raghava Chari
Root Cause Analysis (RCA)
No Comments
Share
3 Min Read
SHARE

Instrumentation engineering root cause analysis of doubtful temperature readings of temperature recorder that threatens soaking pit wrecks.

Contents
Soaking Pit Doubtful Temperature ReadingsProblem Repeats Eliminated
Article Type:Root Cause Analysis (RCA)
Category:Instrumentation
Equipment Type:Instruments
Author:S. Raghava Chari

Note: This root cause analysis (RCA) is from real-time scenarios that happened in industries during the tenure of two or three decades ago. These articles will help you to improve your troubleshooting skills and knowledge.

Soaking Pit Doubtful Temperature Readings

The pit supervisor asserted the temperature recorder read temperatures are incorrect and stubbornly refused ingots charging, though the temperature recorder and supporting temperature indicator read the same. The instrument crew repeatedly calibrated both and assured all are OK!

The author was called upon to resolve the issue checked the pit wall temperature with an optical pyrometer and agreed with the pit supervisor.

He checked with the crew who made the thermocouples and found that they had by mistake made the TC out of Pt. Rh 10%-Pt. wire pair and not out of recorder & indicator calibrated Pt. Rh 13%-Pt. wires – the problem root cause.

He appreciated the pit supervisor for his judgment; Charged, Ingots would have melted and ruined the revamped pit. Clearing the solidified steel out of the pit and revamp would have put the pit and reduced the rolling mill output several weeks.

Doubtful Temperature Readings

Problem Repeats Eliminated

Since that plant’s most temperature measurements calibration is Pt. Rh 13% – Pt.

The author eliminated the recurrence of the problems thus:

  1. Made Pt Rh 13-Pt TC wires the plant standard
  2. Exchanged the unused Pt-Rh Pt TC wire rolls with Pt Rh 13 – Pt wire rolls
  3. Changed the measuring circuit card of all Pt Rh 10 – Pt calibrated instruments with Pt Rh 13 Pt cards and marked the scales Pt Rh 13 Pt and verified the calibration   

Author: S. Raghava Chari

Do you face any similar issues? Share with us through the below comments section.

If you liked this article, then please subscribe to our YouTube Channel for Instrumentation, Electrical, PLC, and SCADA video tutorials.

You can also follow us on Facebook and Twitter to receive daily updates.

Read Next:

  • Target Flow Transmitters Failed
  • Multistage Flash Drums Readings
  • Rotameter Caused Pipe Weld Cracks
  • Level Instruments Stopped Working
  • Differential Pressure Transmitter Problem
Don't Miss Our Updates
Be the first to get exclusive content straight to your email.
We promise not to spam you. You can unsubscribe at any time.
Invalid email address
You've successfully subscribed !

Continue Reading

Malfunctioning Inlet Check Valves caused chaos at Compressor stop/trip
An Indian Plants all turbines’ low Vacuum & Saudi Plant turbo-compressor only
Instrument Steam Pressure Taps Primary Block Valves Glands and Bonnets Leaks
Amine Pump Trip – Root Cause Analysis
Industrial Light Fittings and Street Light Poles Corrosion Problems
Control Valve Passing Problem after Overhauling Job
Share This Article
Facebook Whatsapp Whatsapp LinkedIn Copy Link
Share
Leave a Comment

Leave a Reply Cancel reply

Your email address will not be published. Required fields are marked *

Stay Connected

128.3kFollowersLike
69.1kFollowersFollow
208kSubscribersSubscribe
38kFollowersFollow

Categories

Explore More

Rotary Granulator Drive Root Cause Analysis (RCA)
CO2 Stripper Collapsed Internals Revamp
Problems with Demister Pads – Root Cause Analysis (RCA)
Supplied Screen Vibrators Perennial Problems
Target Flow Transmitters Failed the Very Midnight
[RCA] Pump Low throughput Eliminated
Gearbox within week Failing Journal Bearing upset Plant Operations
Instrumentation Engineering Problems Solved – Root Cause Analysis
Poorly Built Switchgears – Why Breaker Parts Tear apart or don’t work?
Aluminum Cable Terminations Repeat Failures

Keep Learning

Thermowell Shank to Flange Repeat Weld Leaks

Thermowell Shank to Flange Repeat Weld Leaks

Compressor IP Case Discharge Temperature Gradually Increases

Compressor IP Case Discharge Temperature Gradually Increases

Plant Shutdown Analysis: Valve Closed and SOV Coil Failure

Plant Shutdown Analysis: Valve Closed and SOV Coil Failure

High-pressure Service Level Transmitters Misunderstood Zero Drifts

High-pressure Service Level Transmitters Misunderstood Zero Drifts

Antifriction bearings (AFB) Problems

Antifriction bearings (AFB) Problems and Delays Plant Restarts

Fired Boiler Induced Draft Fan (IDF) Failures

Fired Boiler Induced Draft Fan (IDF) Failures Upset all Plants Operations

Under and Over-Capacity Control Valve

Under and Over-Capacity Control Valve Pose Poor Controllability

Steam Turbine Driven Centrifugal Compressors Leak due to Broken Instrument

Discharge Head 3‑monthly leaks of Steam Turbine Driven Centrifugal Compressors

Discover More

Damaged Magnetic Flow Meter Flow Tube

None Could Repair Slightly Damaged Magnetic Flow Meter Flow Tube

2-way solenoid valve Normally Closed

What is a 2-way Solenoid Valve ?

Radiation Pyrometer Working Principle

Radiation Pyrometer Working Principle

5-Port-2-Position-Valve-Animation

5 Port 2 Position Valve Working Principle

Squirrel Cage Induction Motor vs Slip Ring Induction Motor

Refrigeration Compressor Turbine Not-tripping when needed Trip

Refrigeration Compressor Turbine Not-tripping when needed Trip

Advanced Microcontroller Projects Using Proteus Simulation

Advanced Microcontroller Projects Using Proteus Simulation

Independent-Voltage-Source-circuit-ideal-battery

Circuit Elements and Types of Circuits

Follow US
All rights reserved. Reproduction in whole or in part without written permission is prohibited.
Welcome Back!

Sign in to your account

Username or Email Address
Password

Lost your password?