Configuration of Control Valve in Studio 5000

We are going to use a P-AOUT Analog output Add-on block for the configuration of a Control Valve in studio 5000 and, we will see Analog Output parameters descriptions which we are going to configure.

Configuration of Control Valve in Studio 5000

Follow the below steps for the configuration of the control valve in Studio 5000.

Step 1:

Open Logix designer and open PlantPAx Project file in which all required add-on blocks of PlantPAx library are imported.

Open Logix designer and open PlantPAx

Step 2:

Right Click on Main Program and create a new routine as Analog Output.

And in the main program, calls the routine using JSR Instruction as shown below.

Step 3:

Double click on the Analog Output routine and click on add-on and select P-AOUT instruction as shown below.

Step 4:

After adding the P_AOUT block we will bind a tag as CV_01 (Control valve 01) in the controller scope.

Step 5:

After that, click on the 3 dots tab and the parameter window will open where you can select and force the parameters you want.

Inp-tieback: It indicates tieback CV i.e raw output of CV units.
Inp-IntlkOK: If it indicates=1 then all interlocks configured for particular valves are OK.
Inp-NBIntlkOK: It indicates those interlocks which cannot be bypassed are OK or not.
Inp-Ovrd: It indicates whether the input is overridden or not i.e if value=1 then particular input I override and if it is=0 then it is healthy.
Inp-OvrdCV: Target CV can be overridden.
Out CV: It indicates the simulated raw output value of the Control valve.
Sts-Err: It indicates that the control valve is in error. It means input failure.
Sts-Maint: It indicates the control valve is in maintenance mode.
Sts-Prog: It denotes Valve is in program mode.
Sts-Oper: It indicates Valve is in Operator mode.

Step 6:

Now we are going to enter the raw count and its engineering value accordingly which the actual valve will modulate. Enter 0 to 30840 in Raw min and Raw max as shown below and 0 to 100 will be your actual valve target value in%.

Step 7:

Your valve is configured you can test as shown below, download the logic/routine file in your available controller or in the emulator as I have done.

You've successfully subscribed !

View Comments

Share

Recent Articles

  • PLC Tutorials

Conveyor Sorting Machine PLC Program with Calculation Function

The conveyor sorting machine is widely used in the packing industries using the PLC program…

5 days ago
  • PLC Tutorials

Example of Flip-Flop PLC Program for Lamps Application

Learn the example of flip-flop PLC program for lamps application using the ladder logic to…

5 days ago
  • PLC Tutorials

STAR DELTA Programming using PLC Controller

In this article, you will learn the STAR DELTA programming using PLC controller to start…

5 days ago
  • Instrumentation Design

Single and Three Phase Immersion Electrical Heaters Wiring Circuits

Lube oil consoles of rotary equipment packages in industrial process plants are usually equipped with…

3 days ago
  • Instrumentation Design

Immersion Heaters in Lube Oil Consoles

Rotating equipment packages such as pumps, compressors, turbines need the lube oil consoles for their…

5 days ago
  • PLC Tutorials

How to Blink Lights in Ladder Logic?

This article explains how to blink lights in ladder logic with a detailed explanation video…

4 weeks ago