Inst ToolsInst ToolsInst Tools
  • Courses
  • Videos
  • Q & A
    • Interview
      • Instrumentation
      • Electronics
      • Electrical
      • Practical Questions
    • MCQ
      • Instrumentation MCQ
      • Electrical MCQ
      • Electronics MCQ
      • Control Systems MCQ
      • Analog Electronics MCQ
      • Digital Electronics MCQ
      • Power Electronics MCQ
      • Microprocessor MCQ
      • Multiple Choice Questions
  • EE
    • Electronics
      • Electronics Q & A
      • Electronic Basics
      • Electronic Devices & Circuits
      • Electronics Animation
      • Digital Electronics
    • Electrical
      • Electrical Basics
      • Electrical Q & A
      • Power Electronics
      • Electrical Machines
      • Electrical Animation
      • Power Systems
      • Switchgear & Protection
      • Transmission & Distribution
  • Measure
    • Control Valves
    • Calibration
    • Temperature
    • Pressure
    • Flow
    • Level
    • Analyzers
    • Switches
    • Vibration
    • Solenoid Valve
  • Control
    • PLC Tutorials
    • Control Systems
    • Safety Instrumented System (SIS)
    • Communication
    • Fire & Gas System
  • More
    • Design
    • Tools
    • Animation
    • Basics
    • Formulas
    • Standards
    • TextBooks
    • Common
    • Software
    • Excel Tools
    • Erection & Commissioning
    • Process Fundamentals
    • Videos
    • Books
Search
All rights reserved. Reproduction in whole or in part without written permission is prohibited.
Reading: Radar and Ultrasonic Level Transmitter Practical Problems Troubleshooting
Share
Notification Show More
Font ResizerAa
Inst ToolsInst Tools
Font ResizerAa
  • Courses
  • PLC Tutorials
  • Control Systems
Search
  • Courses
  • Videos
  • Q & A
    • Interview
    • MCQ
  • EE
    • Electronics
    • Electrical
  • Measure
    • Control Valves
    • Calibration
    • Temperature
    • Pressure
    • Flow
    • Level
    • Analyzers
    • Switches
    • Vibration
    • Solenoid Valve
  • Control
    • PLC Tutorials
    • Control Systems
    • Safety Instrumented System (SIS)
    • Communication
    • Fire & Gas System
  • More
    • Design
    • Tools
    • Animation
    • Basics
    • Formulas
    • Standards
    • TextBooks
    • Common
    • Software
    • Excel Tools
    • Erection & Commissioning
    • Process Fundamentals
    • Videos
    • Books
Follow US
All rights reserved. Reproduction in whole or in part without written permission is prohibited.
Inst Tools > Blog > Level Measurement > Radar and Ultrasonic Level Transmitter Practical Problems Troubleshooting

Radar and Ultrasonic Level Transmitter Practical Problems Troubleshooting

In this article, we will learn the radar and ultrasonic level transmitter practical problems and Troubleshooting solutions.

Last updated: July 9, 2024 10:19 am
Editorial Staff
Level Measurement
No Comments
Share
5 Min Read
SHARE

Today we will discuss about troubleshooting steps which we can follow in case we encounter problems in radar level transmitter or ultrasonic level transmitter.

Level Transmitter Problems

Radar and Ultrasonic Level Transmitter Problems Troubleshooting
  1. Check the supply voltage to the level transmitter. If no voltage is present, then check the fuse healthiness in the marshalling cabinet.
  2. If fuse is ok, then check the barrier/isolator condition. If found faulty, then replace it. If found ok, then check all the intermediate connections.
  3. Any connections might be loose. Also check the cable healthiness by checking the resistance of the cable. Replace the cable pair with a spare cable pair if found faulty. 
  4. Replace the transmitter power card if the incoming voltage is present but the transmitter doesn’t power ON.
  5. If level sensor value remains 0% or 100%, do a power reboot of the transmitter. 
  6. After power reboot, if still value remains 0% or 100%, then in case of non-contact type radar and ultrasonic level transmitter, remove the level transmitter from the tank or vessel. Clean the transmitter’s sensor part. Many times, moisture droplets or vapors get deposited on the sensor and hence we get low or high readings. Clean the sensor with a soft cloth. Also inspect the physical condition of the sensor. In case of radar type level transmitter, check the physical healthiness of the sensor cone.
  7. Check the flange and the path of the waves. Many times, for water service, spider forms web in the path of the radar/ultrasonic waves. So, remove the spider web. Also, sometimes rusting can form bulged structures. This bulged structures also reflect the waves directly and hence we get low or high readings in the level transmitter. So, remove that rusted part. Try to make that portion straight by buffing.
  8. If guided wave radar is used with extended pipe connections, then check whether the valves for extended pipe are open or not.
  9. For guided wave radar level sensor, if power reboot doesn’t work, then first remove the transmitter from the probe part. Clean the tip of the transmitter and the probe tip. Reinstall and check whether the level transmitter works or not.
  10. If still level sensor values are not proper then removing the radar level transmitter’s probe is the step. Remove the probe and clean the probe. Some material might be sticked on the probe. Inspect the probe properly and remove the material.
  11. If above steps do not work then try replacing the respective internal cards.
  12. After installation of the radar transmitter and probe, if still the transmitter is stuck on certain level reading, then again remove the probe. Do steam jetting or hydro jetting on the probe. This will remove the material stuck on the probe’s surface.
  13. Also clean the still pipe used for guided wave radar if present.
  14. If there is value mismatch in the field and the PLC or DCS system, then check both the configured ranges in the field as well as the control system. Confirm the configured ranges with level coordination diagram or any other approved documents available at plant.
  15. If the level transmitter’s value is fluctuating, then physically check whether the level is still in the vicinity of the level transmitter or not. Too much fluctuation in level or air bubbles can also create issue in level measurement. Try changing the installation location of the level transmitter if possible.
  16. If value of level is fluctuating very fast, then try increasing the time constant (damping value) by few seconds. 

Read Next

  • Electrical Ground Loops
  • Purging of Instruments
  • Purged Impulse Lines
  • Impulse Steam Traps
  • Impulse Piping Installation
Don't Miss Our Updates
Be the first to get exclusive content straight to your email.
We promise not to spam you. You can unsubscribe at any time.
Invalid email address
You've successfully subscribed !

Recommended Articles

What is Thermal Differential Level Measurement?
Level Measurement Objective Questions
Probe Type GWR Level Transmitter Working Animation
Magnetic Level Indicators Working Animation
Magnetostrictive Level Measurement
Optical Level Switch Working Principle
Share This Article
Facebook Whatsapp Whatsapp LinkedIn Copy Link
Share
Leave a Comment

Leave a Reply Cancel reply

Your email address will not be published. Required fields are marked *

Stay Connected

128.3kFollowersLike
69.1kFollowersFollow
208kSubscribersSubscribe
38kFollowersFollow

Categories

Recent Comments

  • William Snyder on Top Non-PLC Certification Courses for Automation Professionals
  • Kamli on Top Free PLC Software
  • Guifty Shimica on Top Non-PLC Certification Courses for Automation Professionals
  • Guifty Shimica on Top Non-PLC Certification Courses for Automation Professionals

Related Articles

DP-Level-Transmitter-Diaphragm-with-capillary-tube-type

DP Level Transmitter Calibration for Diaphragm Seal with Capillary

Conductive Level Measurement Working Principle

Conductive Level Measurement Working Principle

Closed Tank Non-Zero-Based Direct Mount Application

Open and Closed Tank Level Calculations

Stilling well in liquid level measurement

Stilling Well in Interface Level Measurement System

Differential Pressure Measurement

Basics of Differential Pressure Level Transmitters

Difference between Transparent Level Gauge and Reflex Level Gauge

Difference between Transparent Level Gauge and Reflex Level Gauge

Closed Tank DP Level Transmitter

How to Find LRV and URV of Closed Tank DP Level Transmitter

Weight-based Level Instruments Principle

Weight-based Level Measurement Principle

More Articles

Radiochemical Questions and Answers

Gamma Camera Questions & Answers

Pneumatic Valves and Cylinders Sizing

Pneumatic Valves and Cylinders Sizing – Part 1

OPC Communication

OPC Solves Automation’s Data Connectivity

Differential Pressure Transmitter with 5 Way Manifold Valve

Differential Pressure Transmitter with 5 Way Manifold Valve

SIS PFD - Safety Instrumented System

SIS PFD – Safety Instrumented System

Control Valve Calibration

How-to do Control Valve Calibration?

Electric Circuits Objective Questions

Electric Circuits Objective Questions – Set 14

Digital Control Systems

Z & S Domain Relationship

Follow US
All rights reserved. Reproduction in whole or in part without written permission is prohibited.
Welcome Back!

Sign in to your account

Username or Email Address
Password

Lost your password?