Inst ToolsInst ToolsInst Tools
  • Courses
  • Automation
    • PLC
    • Control System
    • Safety System
    • Communication
    • Fire & Gas System
  • Instrumentation
    • Design
    • Pressure
    • Temperature
    • Flow
    • Level
    • Vibration
    • Analyzer
    • Control Valve
    • Switch
    • Calibration
    • Erection & Commissioning
  • Interview
    • Instrumentation
    • Electrical
    • Electronics
    • Practical
  • Q&A
    • Instrumentation
    • Control System
    • Electrical
    • Electronics
    • Analog Electronics
    • Digital Electronics
    • Power Electronics
    • Microprocessor
  • Request
Search
  • Books
  • Software
  • Projects
  • Process
  • Tools
  • Basics
  • Formula
  • Power Plant
  • Root Cause Analysis
  • Electrical Basics
  • Animation
  • Standards
  • 4-20 mA Course
  • Siemens PLC Course
Reading: Pneumatic Piping Design and Specification
Share
Notification Show More
Font ResizerAa
Inst ToolsInst Tools
Font ResizerAa
  • Courses
  • Design
  • PLC
  • Interview
  • Control System
Search
  • Courses
  • Automation
    • PLC
    • Control System
    • Safety System
    • Communication
    • Fire & Gas System
  • Instrumentation
    • Design
    • Pressure
    • Temperature
    • Flow
    • Level
    • Vibration
    • Analyzer
    • Control Valve
    • Switch
    • Calibration
    • Erection & Commissioning
  • Interview
    • Instrumentation
    • Electrical
    • Electronics
    • Practical
  • Q&A
    • Instrumentation
    • Control System
    • Electrical
    • Electronics
    • Analog Electronics
    • Digital Electronics
    • Power Electronics
    • Microprocessor
  • Request
Follow US
All rights reserved. Reproduction in whole or in part without written permission is prohibited.
Inst Tools > Blog > Control Valves > Pneumatic Piping Design and Specification

Pneumatic Piping Design and Specification

Pneumatic piping employed in oil and gas plants is used to provide air for the operation of instruments and other devices.

Last updated: December 1, 2020 2:51 pm
Editorial Staff
Control Valves Instrumentation Design
No Comments
Share
6 Min Read
SHARE

Pneumatic piping employed in plants is used to convey air for two basic reasons:

Contents
Pneumatic PipingPressure Reducing StationSizingDesignRegulated Air Supply Header

(1) that of supplying Energy for the operation of instruments and other devices, and

(2) that of transmission of Information between instruments.

Pneumatic Piping

Pneumatic Piping Design and Specification

Integrity of the piping system is essential to avoid loss of the pneumatic supply and degradation of the transmitted signals.

Supply air is usually delivered to the control center from external sources at pressures typically between 60 and 150 psi gage (400–1000 kPa). It should be clean, dry, and suitable for the application and environment.

A sufficient flow of supply air should be available to meet the control center requirements for transient as well as steady state conditions. Displacement of oxygen in the control center or control room, resulting from the use of bleed type instruments when gases other than air are used, should be considered.

Pressure Reducing Station

A pressure reducing station (sometimes termed as “air set”) reduces and regulates the supply air pressure to a level suitable for the application. The reduced pressure is usually 20 psi gage (140kPa) for systems employing 3–15 psi gage (20–100 kPa) signal ranges and 40 psi gauge (270 kPa) for 6–30 psi gage (40–200 kPa) signal ranges.

Pressure reducing stations are normally located inside the control center but can be external if special access requirements or space limitations exist.

Sizing

The number of air users in the control center establishes the capacity requirements. It is a common practice to determine the total instantaneous air usage by adding together the maximum consumption of each pneumatic device and multiplying by safety or sizing factor of 1.3 to 2.0.

Air filters and pressure regulators are selected from manufacturers’ capacity data based on the total adjusted instantaneous usage and required regulated pressure.

Design

An installation of dual pressure regulators and dual air filters is generally employed. They are arranged in parallel with appropriate valving so that one system can be serviced while the other is in use.

When 3-way valves are used, they should not interrupt the supply to the instruments during a transfer from one leg to the other. Pressure gauges should be provided in each leg to indicate the pressure of the regulated air. A pressure gauge may also be installed to indicate the pressure of the supply air.

A pressure gauge with a blow-out back or disc and a plastic lens is recommended. Low air pressure alarms are often initiated from suitable pressure switches at the pressure reducing station. Adequate clearance is necessary to provide for service and maintenance of the system.

Regulated Air Supply Header

The regulated air is normally piped to a larger diameter plastic or non-ferrous metal pipe section acting as a manifold or header and reservoir from which each air user receives its supply.

The headers are normally installed in a horizontal or vertical plane in the lower part of the control center and have individual shut-off valves at each air supply take-off point. Each shut-off valve should be identified with a non-corrosive metal or plastic tag. It is a good practice to provide up to 15 percent spare valved connections.

The assembly is normally mounted in a rigid manner, sloping at least 1/8 inch per foot away from the supply end, down toward a drain cock. If there is the possibility that failure of the pressure reducing station could result in over pressure damage to the air users, a suitably sized safety relief valve should be installed. The safety relief valve should be sized to pass the rated flow capacity of one regulator failing full open.

The individual air users are connected to the header shut-off valves by tubing. This supply tubing is typically 1/4 inch outside diameter soft copper, plastic, or stainless steel. Some devices with larger air usage may require supply tubing of 3/8 inch or 1/2 inch outside diameter, as suggested by the specifications for that device.

It is a general practice to increase the volume of the air supply header as the number of air users increases. To minimize the pressure drop across the air supply header during large transients in air demand, it is a common practice to use larger diameters and longer sections of pipe.

Interest to add any further points? Share with us through below comments section.

Read Next:

  • Junction Box Schedule
  • Thermowell Specification
  • Temperature Gauges
  • Instrument Process Datasheet
  • All About Turbine Meters
Don't Miss Our Updates
Be the first to get exclusive content straight to your email.
We promise not to spam you. You can unsubscribe at any time.
Invalid email address
You've successfully subscribed !

Continue Reading

Control Valve Parts Questions and Answers
Valve Seat Leakage Test
Where should we Terminate the Cable Shields ?
 Control Valve Accessories – Principle, Purpose, Advantages
What is Travel Stop in Control Valve?
Control Valve Performance with Constant Pressure
Share This Article
Facebook Whatsapp Whatsapp LinkedIn Copy Link
Share
Leave a Comment

Leave a Reply Cancel reply

Your email address will not be published. Required fields are marked *

Stay Connected

128.3kFollowersLike
69.1kFollowersFollow
210kSubscribersSubscribe
38kFollowersFollow

Categories

Explore More

What are Isolation valves? – Purpose, Types, Configurations
How Sliding Stem Valves Work ?
How to Avoid Process Downtime ?
Instrument Air Quality
Solenoid Valves Selection Guidelines
Electrical and Instrumentation – Automation Pre-engineering Documents
Erratic Stroking Control Valves Delaying the Shutdown Plant Restart
Pressure Relief Valve Principle

Keep Learning

Multiple Thermowell Installations Problems

Multiple Thermowell Installations Problems

Needle Valve Schematic

How Needle Valve Works ?

pilot-operated pressure relief valve

Pilot-operated Safety and Relief Valves

Design Basis for Fire Detection and Alarm System

Design Basis for Fire Detection and Alarm System

Snap Acting Relay Working Principle

Snap Acting Relay Working Principle

Readings Mismatch between Field & Control Room

Readings Mismatch between Field & Control Room ? Why

Basic Terms used in SIL Verification

Basic Terms used in SIL Verification

Shut down valve

What is Shutdown Valve?

Learn More

Improved Sprocket Segment Bolting to body

A Plant Bucket Elevators chains too short chain lives problem eliminated

Power Electronics Objective Questions

Dual Converters Quiz

Infrared Hydrocarbon Gas Detector Calibration Procedure

Infrared Hydrocarbon Gas Detector Calibration Procedure

Lightning Arrester Basics and Terminology

Lightning Arrester Basics and Terminology

Transmitter Indicators

What is Indicator ?

Nuclear Magnetic Resonance Spectrometer Questions and Answers

Nuclear Magnetic Resonance Spectrometer Questions & Answers

What is Temperature

What is Temperature ?

Boiler Drum Level Control Systems

Boiler Drum Level Control Systems

Menu

  • About
  • Privacy Policy
  • Copyright

Quick Links

  • Learn PLC
  • Helping Hand
  • Part Time Job

YouTube Subscribe

Follow US
All rights reserved. Reproduction in whole or in part without written permission is prohibited.
Welcome Back!

Sign in to your account

Username or Email Address
Password

Lost your password?