Inst ToolsInst ToolsInst Tools
  • Courses
  • Automation
    • PLC
    • Control System
    • Safety System
    • Communication
    • Fire & Gas System
  • Instrumentation
    • Design
    • Pressure
    • Temperature
    • Flow
    • Level
    • Vibration
    • Analyzer
    • Control Valve
    • Switch
    • Calibration
    • Erection & Commissioning
  • Interview
    • Instrumentation
    • Electrical
    • Electronics
    • Practical
  • Q&A
    • Instrumentation
    • Control System
    • Electrical
    • Electronics
    • Analog Electronics
    • Digital Electronics
    • Power Electronics
    • Microprocessor
  • Request
Search
  • Books
  • Software
  • Projects
  • Process
  • Tools
  • Basics
  • Formula
  • Power Plant
  • Root Cause Analysis
  • Electrical Basics
  • Animation
  • Standards
  • 4-20 mA Course
  • Siemens PLC Course
Reading: Normally-open and Normally-closed Switch Contacts
Share
Notification Show More
Font ResizerAa
Inst ToolsInst Tools
Font ResizerAa
  • Courses
  • Design
  • PLC
  • Interview
  • Control System
Search
  • Courses
  • Automation
    • PLC
    • Control System
    • Safety System
    • Communication
    • Fire & Gas System
  • Instrumentation
    • Design
    • Pressure
    • Temperature
    • Flow
    • Level
    • Vibration
    • Analyzer
    • Control Valve
    • Switch
    • Calibration
    • Erection & Commissioning
  • Interview
    • Instrumentation
    • Electrical
    • Electronics
    • Practical
  • Q&A
    • Instrumentation
    • Control System
    • Electrical
    • Electronics
    • Analog Electronics
    • Digital Electronics
    • Power Electronics
    • Microprocessor
  • Request
Follow US
All rights reserved. Reproduction in whole or in part without written permission is prohibited.
Inst Tools > Blog > Animation > Normally-open and Normally-closed Switch Contacts

Normally-open and Normally-closed Switch Contacts

Last updated: March 4, 2021 4:20 pm
Editorial Staff
Animation PLC Tutorials Switches
1 Comment
Share
7 Min Read
SHARE

Perhaps the most confusing aspect of discrete sensors is the definition of a sensor’s normal status.

Contents
Normally-open and Normally-closedExample

Electrical switch contacts are typically classified as either normally-open or normally-closed, referring to the open or closed status of the contacts under “normal” conditions. But what exactly defines “normal” for a switch?

The answer is not complex, but is often misunderstood due to the ambiguous nature of the word normal.

The “normal” status for a switch is the status its electrical contacts are in during a condition of no physical stimulation. Another way to think of the “normal” status is to think in terms of the switch being at rest.

For a momentary-contact pushbutton switch, this would be the status of the switch contact when it is not being pressed. Electrical switches are always drawn in schematic diagrams in their “normal” statuses, regardless of their application.

Normally-open and Normally-closed

For instance, the following diagram shows a normally-open pushbutton switch controlling a lamp on a 120 volt AC circuit (the “hot” and “neutral” poles of the AC power source labeled L1 and L2, respectively):

Normally-open switch contacts

We can tell this switch is a normally-open (NO) switch because it is drawn in an open position.

The lamp will energize only if someone presses the switch, holding its normally-open contacts in the “closed” position. Normally-open switch contacts are sometimes referred to in the electrical industry as form-A contacts.

If we had used a normally-closed pushbutton switch instead, the behavior would be exactly opposite. The lamp would energize if the switch was left alone, but it would turn off if anyone pressed the switch.

Normally-closed switch contacts are sometimes referred to in the electrical industry as form-B contacts:

Normally-closed switch contacts

This seems rather simple, don’t you think? What could possibly be confusing about the “normal” status of a switch?

The confusion becomes evident, though, when you begin to consider process switches (i.e. switches actuated by process measurements such as pressure, flow, level, etc.).

In order to better understand this concept, we will consider a simple application of a flow switch: a switch built to actuate when a sufficient rate of fluid flows through a pipe.

A flow switch is built to detect fluid flow through a pipe. In a schematic diagram, the switch symbol appears to be a toggle switch with a “flag” hanging below.

Example

The schematic diagram, of course, only shows the circuitry and not the pipe where the switch is physically mounted:

Switch Working Animation

This particular flow switch is used to trigger an alarm light if coolant flow through the pipe ever falls to a dangerously low level, and the contacts are normally-closed as evidenced by the closed status in the diagram.

Here is where things get confusing: even though this switch is designated as “normally-closed,” it will spend most of its lifetime being held in the open status by the presence of adequate coolant flow through the pipe.

Only when the flow through the pipe slows down enough will this switch return to its “normal” status and conduct electrical power to the lamp.

In other words, the “normal” status for this switch (closed) is actually an abnormal status for the process it operates within (low flow), for the simple reason that the switch should be stimulated and not at rest while the process is operating as it should.

We often wonder why process switch contacts are labeled according to this convention of “no stimulation” instead of according to the typical status of the process in which the switch is used.

The answer to this question is that the manufacturer of the switch has no idea whatsoever as to your intended use.

A flow switch manufacturer does not know or care whether their product gets used as a low-flow detector or as a high-flow detector.

In other words, the manufacturer cannot predict what the typical status of your process will be, and so the definition of “normal” status for the switch must be founded on some common criterion unrelated to your particular application.

That common criterion is the resting status: when the sensor is exposed to the least (or no) amount of stimulation from the process it senses.

Here is a listing of “normal” definitions for various process switch types:

  • Limit switch: target not contacting the switch
  • Proximity switch: target far away
  • Pressure switch: low pressure (or even a vacuum)
  • Level switch: low level (empty)
  • Temperature switch: low temperature (cold)
  • Flow switch: low flow rate (fluid stopped)

These are the conditions represented by the switch statuses shown in a schematic diagram. These may very well not be the statuses of the switches when they are exposed to typical operating conditions in the process.

A helpful tip to remember about process switches and their respective schematic diagram symbols is that the symbols are conventionally drawn in such a way that an upward motion of the movable switch element represents increasing stimulus.

Here are some examples of this, showing various.

Process switch types and NO/NC contact configurations, comparing their states with no stimulus versus when the stimulus exceeds the each switch’s threshold or “trip” setting.

The normal status of each switch as defined by the manufacturer is labeled in green text:

Normally-open and Normally-closed Switch Contacts

It is imperative to remember that the way a switch is drawn in a schematic diagram merely represents its “normal” status as defined by the manufacturer.

This may or may not be the switch’s status during “typical” operation of the process, and it may or may not be the status of that switch at the time of concern when you are examining the schematic!

The “normal” status of a switch means just one thing: what that switch will do when subjected to minimum stimulus – that is to say, what it will do when its stimulus is less than the actuation threshold of the switch.

If you liked this article, then please subscribe to our YouTube Channel for PLC and SCADA video tutorials.

You can also follow us on Facebook and Twitter to receive daily updates.

Read Next:

Pushbutton switches and Types

Basics of Limit switches

Relays in Ladder Logic Tutorials

What is Contactor ?

Relay circuits

Don't Miss Our Updates
Be the first to get exclusive content straight to your email.
We promise not to spam you. You can unsubscribe at any time.
Invalid email address
You've successfully subscribed !

Continue Reading

Programming and Tuning PID Controller in PLC – Siemens TIA Portal
Understanding the Scan Cycle of SIEMENS PLC
Program Flow Control Instructions in PLC Programming
SCADA Hardware and Software
Electromagnetic and Conductive limit switches Principle
Getting to Know the LED Indications on GE Make PLC
Share This Article
Facebook Whatsapp Whatsapp LinkedIn Copy Link
Share
1 Comment
  • vilas k says:
    January 23, 2023 at 11:01 am

    Very good information . Thanks.

    Reply

Leave a Reply Cancel reply

Your email address will not be published. Required fields are marked *

Stay Connected

128.3kFollowersLike
69.1kFollowersFollow
210kSubscribersSubscribe
38kFollowersFollow

Categories

Explore More

Typical HMI Screen Design for Water Treatment Plant
Open Platform Communication (OPC)
DCS Commissioning Steps
Comparison Instructions in PLC Programming
How to choose between PLC and DCS Systems ?
Procedure for Siemens S7-300 Download from PC to PLC
Industrial Automation Engineers Interview Questions
Delta PLC Counter with Comparison

Keep Learning

Factory Acceptance Test of PLC Panel

Factory Acceptance Test (FAT) of a PLC Panel

PLC Demo Software

PLC Trainer Demo Download

HMI screen for operator

Auto Tiffin Box Filling Station

Oscillating Piston Flow Meters Animation

Oscillating Piston Flow Meters Working Principle

Impeller Flow Sensor

Impeller Flow Sensor Working Principle and Animation

ROTARY ABUTMENT FLOW METERS WORKING ANIMATION

Rotary Abutment Flow Meters Working Principle and Animation

Cable Float Level Switch Principle

Cable Float Level Switch Working Principle

Scintillation Counter Theory

Scintillation Counter Principle

Learn More

Pressure Gauge Problems

Pressure Gauge Problems

Single Phase Induction Motors Questions and Answers

Single Phase Induction Motors Questions and Answers

Working of Shuttle valve

What is a Shuttle Valve? Principle, Advantages, Disadvantages

Electric Circuits Objective Questions

Electric Circuits Objective Questions – Set 6

Piston Check Valve

What is Piston Check Valve ?

What is a Wet Contact in PLC

What is a Wet Contact? – Basics of PLC Wiring

desuperheater

Desuperheater Design

Air Consumption Calculation for Control Valves

Air Consumption Calculation for ON/OFF Valves

Menu

  • About
  • Privacy Policy
  • Copyright

Quick Links

  • Learn PLC
  • Helping Hand
  • Part Time Job

YouTube Subscribe

Follow US
All rights reserved. Reproduction in whole or in part without written permission is prohibited.
Welcome Back!

Sign in to your account

Username or Email Address
Password

Lost your password?