Inst ToolsInst ToolsInst Tools
  • Courses
  • Automation
    • PLC
    • Control System
    • Safety System
    • Communication
    • Fire & Gas System
  • Instrumentation
    • Design
    • Pressure
    • Temperature
    • Flow
    • Level
    • Vibration
    • Analyzer
    • Control Valve
    • Switch
    • Calibration
    • Erection & Commissioning
  • Interview
    • Instrumentation
    • Electrical
    • Electronics
    • Practical
  • Q&A
    • Instrumentation
    • Control System
    • Electrical
    • Electronics
    • Analog Electronics
    • Digital Electronics
    • Power Electronics
    • Microprocessor
  • Request
Search
  • Books
  • Software
  • Projects
  • Process
  • Tools
  • Basics
  • Formula
  • Power Plant
  • Root Cause Analysis
  • Electrical Basics
  • Animation
  • Standards
  • 4-20 mA Course
  • Siemens PLC Course
Reading: Process Switches and Alarms
Share
Notification Show More
Font ResizerAa
Inst ToolsInst Tools
Font ResizerAa
  • Courses
  • Design
  • PLC
  • Interview
  • Control System
Search
  • Courses
  • Automation
    • PLC
    • Control System
    • Safety System
    • Communication
    • Fire & Gas System
  • Instrumentation
    • Design
    • Pressure
    • Temperature
    • Flow
    • Level
    • Vibration
    • Analyzer
    • Control Valve
    • Switch
    • Calibration
    • Erection & Commissioning
  • Interview
    • Instrumentation
    • Electrical
    • Electronics
    • Practical
  • Q&A
    • Instrumentation
    • Control System
    • Electrical
    • Electronics
    • Analog Electronics
    • Digital Electronics
    • Power Electronics
    • Microprocessor
  • Request
Follow US
All rights reserved. Reproduction in whole or in part without written permission is prohibited.
Inst Tools > Blog > Control Systems > Process Switches and Alarms

Process Switches and Alarms

Last updated: July 29, 2019 4:56 am
Editorial Staff
Control Systems
1 Comment
Share
7 Min Read
SHARE

Another type of instrument commonly seen in measurement and control systems is the process switches. The purpose of a switch is to turn on and off a device like heaters, motors, valves etc… with varying process conditions.

Contents
Process Switch with AlarmsExample of Process Alarms and SwitchesHigh and Low Alarms

Usually, switches are used to activate alarms to alert human operators to take special action or can be used to trip or initiate interlocks.

In other situations, switches are directly used as control devices like there is level switch installed in a tank to prevent damage of a pump, pump will be automatically stopped/tripped when level reaches low in the tank.

Process Switch with Alarms

The following P&ID of a compressed air control system shows both uses of process switches:

Process Alarms and Switches

The “PSH” (pressure switch, high) activates when the air pressure inside the vessel reaches its high control point. The “PSL” (pressure switch, low) activates when the air pressure inside the vessel drops down to its low control point.

Both switches feed discrete (on/off) electrical signals to a logic control device (symbolized by the diamond) which then controls the starting and stopping of the electric motor-driven air compressor.

Another switch in this system labeled “PSHH” (pressure switch, high-high) activates only if the air pressure inside the vessel exceeds a level beyond the high shut-off point of the high pressure control switch (PSH).

If this switch activates, something has gone wrong with the compressor control system, and the high pressure alarm (PAH, or pressure alarm, high) activates to notify a human operator.

All three switches in this air compressor control system are directly actuated by the air pressure in the vessel: in other words, these are direct process-sensing switches allowing us to build on/off control systems and alarms for any type of process.

Example of Process Alarms and Switches

For example, the chlorine wastewater disinfection system shown earlier may be equipped with a couple of electronic alarm switches to alert an operator if the chlorine concentration ever exceeds pre-determined high or low limits:

Instrumentation Alarms

The labels “AAL” and “AAH” refer to analytical alarm (analytical alarm or analyzer alarm) low and analytical alarm high, respectively. Note how the diagram shows these two alarm units connected to the electronic (420 mA) signal output by the chlorine analyzer (AT).

This tells us the AAL and AAH alarm units are really just electronic circuits, alarming if the analytical transmitter’s 4-20 mA analog signal falls below (AAL) or exceeds (AAH) certain pre-set limits.

As such, the AAL and AAH alarms do not directly sense the chlorine concentration in the water, but rather indirectly sense it by monitoring the chlorine analyzer’s 4-20 milliamp output signal.

Since both alarms work off the 4 to 20 milliamp electronic signal output by the chlorine analytical transmitter (AT) rather than directly sensing the process, their construction is greatly simplified.

If these were process-sensing switches, each one would have to be equipped with the analytical capability of directly sensing chlorine concentration in water. In other words, each switch would have to be its own self-contained chlorine concentration analyzer, with all the attendant complexity.

An example of an electronic alarm module (triggered by a 4-20 mA current signal coming from a transmitter) is the Moore Industries model SPA (“Site Programmable Alarm”), shown here for reference:

Local Controller Alarms

In addition to providing alarm capability, this SPA module also provides a digital display (a small LCD screen) to show the analog signal value for operational or diagnostic purposes.

Like all current-operated alarm modules, the Moore Industries SPA may be configured to “trip” electrical contacts when the current signal reaches a variety of different programmed thresholds. Some of the alarm types provided by this unit include high process, low process, out-of-range, and high rate-of-change.

High and Low Alarms

For example, if high- and low-alarm capability were desired for the steam drum water level process, one could add a pair of level switches to the level transmitter output signal line:

Note : The level transmitter signal can be used in soft program and can assign the low and high alarms i.e. LAL & LAH.

Process Alarms Types

These two switches serve as water level alarms, because the signal comes from the level transmitter, which outputs an signal in direct proportion to water level in the boiler’s steam drum.

The alternative would be independent level sensing switches attached directly to the steam drum, each switch equipped with its own means of directly sensing water level:

Level Transmitter Alarms

It should be mentioned that the choice between using process alarm switches directly actuated by the process versus alarm switches actuated by a transmitter’s analog signal is not arbitrary.

In the system where the two alarm switches actuate from the transmitter’s output signal, the integrity of the water level control and that of the high- and low-level alarms all depend on the proper function of one transmitter. If that one transmitter were to fail, all three system functions would be compromised.

This elevates the importance of a single instrument, which is generally not desirable from the perspective of reliability and process safety. In the system where each level alarm switch independently senses steam drum water level, one device may fail without compromising either of the other two functions.

This independence is desirable because it greatly reduces the probability of “common-cause” failures, where a single fault disables multiple system functions.

The final determination should be based on a rigorous analysis of device versus system reliability, which is typically the task of a process engineer.

Articles You May Like :

Alarm and Trip Documents

Relation Control System

Safety Switches for Conveyor

Industrial Control Systems

Water Level Control Logic

Don't Miss Our Updates
Be the first to get exclusive content straight to your email.
We promise not to spam you. You can unsubscribe at any time.
Invalid email address
You've successfully subscribed !

Continue Reading

Using of MCT instead of Cable Glands on the Cabinets
Control Room Alarm Management Practices
PID Controller Theory
DCS Alarm Summary Dashboard using Microsoft Power BI
Overview of HIPPS System
Identify Level Control Loop Tuning Problems
Share This Article
Facebook Whatsapp Whatsapp LinkedIn Copy Link
Share
1 Comment
  • Malvern Jones says:
    November 23, 2018 at 4:35 pm

    Where safety of the system is important it is often preferable to use a pressure switch that is independent of the pressure transmitter. In systems where this safety needs to be certified, then pressure switches with the relevent SIL rating should be used. If you need help, tale a look at our range https://www.coulton.com/Ettore_Cella_Pressure_Switches.html

    Reply

Leave a Reply Cancel reply

Your email address will not be published. Required fields are marked *

Stay Connected

128.3kFollowersLike
69.1kFollowersFollow
210kSubscribersSubscribe
38kFollowersFollow

Categories

Explore More

Compressor Emergency Shutdown Root Cause Analysis
What is a Active Barrier ?
DeltaV System Configuration Changes and Download
Demo of a SCADA Software – Level Control System
De-energize to Safe Loop philosophy
Industrial Automation in the Mining Industry
Anti Surge Controller Working Principle
Feedback Control Principle

Keep Learning

Compare DCS, PLC, RTU

Difference between DCS, PLC, and RTU ?

Liquid Level Switch Control Pump and Lamp

Liquid Level Switch Control Pump and Lamp

Override Control Functions

What is Override Control? – Need & Applications

Standard Colors in PLC Automation Systems

Standard Colors in PLC Automation Systems

Instrumentation Engineer Interview Questions

Interview Questions on PID Controllers

Controller Output Current Loop

DCS Controllers to Output Current Loops

PID Tuning recommendations

PID Tuning Recommendations based on Process Dynamics

Industrial Automation Solution

How to Choose the Right Industrial Automation Solution?

Learn More

Starting a Synchronous Motor

Starting a Synchronous Motor

State Variable Analysis and Design

Solution of State Equations

two chemical streams are mixed together

Practical Process Control System Questions & Answers – 12

PLC Timer Application in Security Camera Recording

PLC Timer Application in Security Camera Recording

Accuracy, resolution, range, counts, digits and precision

Definition of Accuracy, Precision, Resolution, Range

Advanced PLC Programming Training Course

Advanced PLC Course with Programming and Simulation

Comparison of Absorption Chillers and Electric (Compression) Chillers

Difference between Water Cooled Chiller and Air Cooled Chiller

Transmitters 4-20mA Current Failure Alarm Limits

Transmitters 4-20mA Current Failure Alarm Limits

Menu

  • About
  • Privacy Policy
  • Copyright

Quick Links

  • Learn PLC
  • Helping Hand
  • Part Time Job

YouTube Subscribe

Follow US
All rights reserved. Reproduction in whole or in part without written permission is prohibited.
Welcome Back!

Sign in to your account

Username or Email Address
Password

Lost your password?