By using this site, you agree to the Privacy Policy and Terms of Use.
Accept
Inst ToolsInst ToolsInst Tools
  • Ask
  • Courses
  • Videos
  • Q & A
    • Interview
      • Instrumentation
      • Electronics
      • Electrical
      • Practical Questions
    • MCQ
      • Instrumentation MCQ
      • Electrical MCQ
      • Electronics MCQ
      • Control Systems MCQ
      • Analog Electronics MCQ
      • Digital Electronics MCQ
      • Power Electronics MCQ
      • Microprocessor MCQ
      • Multiple Choice Questions
  • EE
    • Electronics
      • Electronics Q & A
      • Electronic Basics
      • Electronic Devices & Circuits
      • Electronics Animation
      • Digital Electronics
    • Electrical
      • Electrical Basics
      • Electrical Q & A
      • Power Electronics
      • Electrical Machines
      • Electrical Animation
      • Power Systems
      • Switchgear & Protection
      • Transmission & Distribution
  • Measure
    • Control Valves
    • Calibration
    • Temperature
    • Pressure
    • Flow
    • Level
    • Analyzers
    • Switches
    • Vibration
    • Solenoid Valve
  • Control
    • PLC Tutorials
    • Control Systems
    • Safety Instrumented System (SIS)
    • Communication
    • Fire & Gas System
  • More
    • Design
    • Tools
    • Animation
    • Basics
    • Formulas
    • Standards
    • TextBooks
    • Common
    • Software
    • Excel Tools
    • Erection & Commissioning
    • Process Fundamentals
    • Videos
    • Books
Search
All rights reserved. Reproduction in whole or in part without written permission is prohibited.
Reading: Displacer Level Transmitter Calibration using Water & Process Liquid
Share
Notification Show More
Font ResizerAa
Inst ToolsInst Tools
Font ResizerAa
  • Ask
  • Courses
  • Videos
  • Q & A
  • EE
  • Measure
  • Control
  • More
Search
  • Ask
  • Courses
  • Videos
  • Q & A
    • Interview
    • MCQ
  • EE
    • Electronics
    • Electrical
  • Measure
    • Control Valves
    • Calibration
    • Temperature
    • Pressure
    • Flow
    • Level
    • Analyzers
    • Switches
    • Vibration
    • Solenoid Valve
  • Control
    • PLC Tutorials
    • Control Systems
    • Safety Instrumented System (SIS)
    • Communication
    • Fire & Gas System
  • More
    • Design
    • Tools
    • Animation
    • Basics
    • Formulas
    • Standards
    • TextBooks
    • Common
    • Software
    • Excel Tools
    • Erection & Commissioning
    • Process Fundamentals
    • Videos
    • Books
Follow US
All rights reserved. Reproduction in whole or in part without written permission is prohibited.
Inst Tools > Blog > Calibration > Displacer Level Transmitter Calibration using Water & Process Liquid
CalibrationLevel Measurement

Displacer Level Transmitter Calibration using Water & Process Liquid

In this article, we will learn calibration procedures of displacer level transmitter using water, process fluid, and also interface level measurement.

Last updated: October 17, 2023 1:53 pm
Editorial Staff
Share
10 Min Read
SHARE

In this article, we will learn 4 methods of calibration procedures of displacer level transmitter (DLT) using water, process fluid, and also interface level measurement.

Contents
Instrument Coupling to the Torque TubeCalibration of Displacer Level Transmitter (DLT)Calibration Procedure of Displacer Level Transmitter (DLT) for Level Measurement using WaterCalibration Procedure for Interface Level Measurement using WaterCalibration Procedure for Level Measurement using Process FluidCalibration Procedure for Interface Level Measurement using with Water and Process Fluid

Instrument Coupling to the Torque Tube

Remove the side cover of the mechanism compartments, and the plug located at the bottom of the instrument.

Required level of 70% liquid for coupling. For level measurements fill water up to 70% of DLT chamber and for interface measurements fill always HSG (High Specific Gravity) liquid up to 70% of DLT chamber.

By looking through the side cover of the mechanism compartments, verify that the screw coupling end of the beam is loose.

Through the 3/4 ” NPT hole at the bottom of the case, press the flexure with your finger to verify it is possible to move the beam from left to right. The value displayed should vary accordingly.

Displacer Level Transmitter Calibration Procedure

Calibration of Displacer Level Transmitter (DLT)

Enter in Advance Setup menu enter calibration tools to display COUPLING method

Condensate Level Transmitter Calibration

Enter in Calibration Tools

Transmitter Calibration Tools

Enter in Coupling Method to enable. After enabled RED indication shows then adjust flexure to Right or Left to get the value at -5% to +5%.

RED indication turns to GREEN at the value in the Limit.

Displacer Level Sensor Coupling Method

The value read on the LCD must be between –5% and +5%. Getting the value within the limit enter in Stop Coupling.

Transmitter Calibration with Laptop

Look at the mechanism compartments through the side cover, and index the oval hole of the flexure towards the special conical ended by bending the flexure toward the case front (see Figure).

The value read on the LCD must be between –5% and +5%. While holding the flexure in that position, slightly but firmly tighten the screw using a 2.5 mm Allen wrench.

NOTE: An undue tightening can damage the instrument.

Displacer Level Transmitter Coupling Adjustment

Calibration Procedure of Displacer Level Transmitter (DLT) for Level Measurement using Water

  • Isolation valve of upper & lower nozzle of the DLT is closed.
  • Drain & vent valve is opened to remove inventory from the DLT chamber.
  • Specific Gravity of the fluid whose level is to be measured is configured in the DLT using HART or Laptop.
  • One Flexible transparent tube is connected from drain point of the DLT and hung above upper nozzle of the DLT.
  • 100% level is calculated as follow:
  • 100% level = SG x CC (Range)
  • SG – Specific Gravity of the fluid (Refer datasheet)
  • Range/CC – Centre to centre distance between the Upper & Lower Nozzle (Refer datasheet)
  • The water is poured until calculated 100% level of the DLT as viewed from the transparent flexible tube. This point is calibrated as SPAN (i.e. 100% value) in the DLT.
  • Now the water is drained from drain port of the DLT until ZERO level as viewed from the transparent flexible tube. This point is calibrated as ZERO in the DLT.
  • Four equal divisions are marked between 0% & calculated 100% on the DLT chamber and these markings are mentioned as 25%, 50% & 75%.
  • Water is poured until 25%, 50% & 75% level of the DLT as viewed from the transparent flexible tube. These levels are verified as 25%, 50% & 75% respectively in the DLT.
  • The DLT is now calibrated and then it is taken online by closing vent & drain valve and opening isolation valve of the lower flange and then upper flange.

Calibration Procedure for Interface Level Measurement using Water

  • Isolation valve of upper & lower nozzle of the DLT is closed.
  • Drain & vent valve is opened to remove inventory from the DLT chamber.
  • One Flexible transparent tube is connected from drain point of the DLT and hung above upper nozzle of the DLT.
  • Specific Gravity of the process fluids whose interface level is to be measured is configured in the DLT using HART or Laptop.
  • 100% level is calculated as follow:
  • 100% level = HSG x CC (Range)
  • HSG – Specific Gravity of Heavier fluid
  • CC – Centre to centre distance between the Upper & Lower Nozzle.
  • 0% level is calculated as follow:
  • 0% level = LSG x CC (Range)
  • SGL – Specific Gravity of lighter fluid (Refer datasheet)
  • Range/CC – Centre to centre distance between the Upper & Lower Nozzle (Refer datasheet)
  • The water is poured until calculated 100% level of the DLT as viewed from the transparent flexible tube. This point is calibrated as SPAN (i.e. 100% value) in the DLT.
  • Now the water is drained from drain port of the DLT until calculated 0% level as viewed from the transparent flexible tube. This point is calibrated as ZERO in the DLT.
  • Four equal divisions are marked between calculated 0% & calculated 100% on the DLT chamber and these markings are mentioned as 25%, 50% & 75%.
  • Water is poured until 25%, 50% & 75% level of the DLT as viewed from the transparent flexible tube. These levels are verified as 25%, 50% & 75% respectively in the DLT.
  • The DLT is now calibrated and then it is taken online by closing vent & drain valve and opening isolation valve of the lower flange and then upper flange.

Calibration Procedure for Level Measurement using Process Fluid

  • Isolation valve of upper & lower nozzle of the DLT is closed.
  • Drain & vent valve is opened to remove inventory from the DLT chamber.
  • Specific Gravity of the process fluid whose level is to be measured is configured in the DLT using HART or Laptop.
  • One Flexible transparent tube is connected from drain point of the DLT and hung above upper nozzle of the DLT.
  • Process fluid is poured until 100% level of the DLT as viewed from the transparent flexible tube. This point is calibrated as SPAN (i.e. 100% value) in the DLT.
  • Then the process Fluid is drained from drain port of the DLT until ZERO level as viewed from the transparent flexible tube. This point is calibrated as ZERO in the DLT.
  • Four equal divisions are marked between 0% & 100% on the DLT chamber and these markings are mentioned as 25%, 50% & 75%.
  • Process fluid is poured until 25%, 50% & 75% level of the DLT as viewed from the transparent flexible tube. These levels are verified as 25%, 50% & 75% respectively in the DLT.
  • The DLT is now calibrated and then it is taken online by closing vent & drain valve and opening isolation valve of the lower flange and then upper flange.

Calibration Procedure for Interface Level Measurement using with Water and Process Fluid

  • Isolation valve of upper & lower nozzle of the DLT is closed.
  • Drain & vent valve is opened to remove inventory from the DLT chamber.
  • One Flexible transparent tube is connected from drain point of the DLT and hung above upper nozzle of the DLT.
  • Specific Gravity of the process fluids whose interface level is to be measured is configured in the DLT using HART or Laptop.
  • Lighter Process Fluid (LSG) is poured from vent port of the DLT until 100% level as viewed from the transparent flexible tube. This point is calibrated as ZERO in the DLT.
  • Heavier Process Fluid (HSG) is poured from vent port of the DLT until 100% level as viewed from the transparent flexible tube. This point is calibrated as SPAN (i.e. 100%) in the DLT.
  • Four equal divisions are marked between 0% & 100% on the DLT chamber and these markings are mentioned as 25%, 50% & 75%.
  • Process fluid (i.e. combined heavier & lighter fluid) is poured until interphase of these fluid reaches 25%, 50% & 75% level of the DLT as viewed from the transparent flexible tube. These levels are verified as 25%, 50% & 75% respectively in the DLT.
  • The DLT is now calibrated and then it is taken online by closing vent & drain valve and opening isolation valve of the lower flange and then upper flange.

Credits: PLQP Instrumentation Team

If you liked this article, then please subscribe to our YouTube Channel for Instrumentation, Electrical, PLC, and SCADA video tutorials.

You can also follow us on Facebook and Twitter to receive daily updates.

Read Next:

  • Level Indicators Working Principle
  • Transparent & Reflex Level Gauge
  • Calculate Current 4-20 mA
  • Level Gauge Design
  • Types of Level Gauges
Don't Miss Our Updates
Be the first to get exclusive content straight to your email.
We promise not to spam you. You can unsubscribe at any time.
Invalid email address
You've successfully subscribed !
All About Instrumentation Impulse Lines
Comparison of Level Meters – Level Measurement Instruments
Fieldbus Flow Transmitter Configuration
Non Contacting Radar Level Transmitter Animation
Pressure Transmitter Calibration Procedure
Share This Article
Facebook Whatsapp Whatsapp LinkedIn Copy Link
Share
2 Comments
  • Anubhav shah says:
    December 17, 2021 at 10:37 pm

    hello,
    we have installed magnetrol e3 displacer level transmitter as well as an interface transmitter.

    level transmitter is showing “loop current saturated” and system side we have Schneider DCS latest when simulation from the field is done the IO bad alarm is coming and when we increase the current from 4,8,12,16 & 20 mA in the display it’s reading correctly and system side it’s not measuring but same time raw count is increasing respectively.
    note: when calibration is done with water it’s working fine.

    in interface level transmitter it’s showing below alerts,
    initializing
    secondary fault lo
    loop current fixed
    more status available
    device malfunction.

    kindly provide the solution for the above query.

    thank you

    Reply
  • Man Mohan Tak says:
    January 10, 2022 at 10:51 pm

    Please check both isolation valves of displacer chamber are open. Drain valves closed.

    Reply

Leave a Reply Cancel reply

Your email address will not be published. Required fields are marked *

Stay Connected

128.3kFollowersLike
69.1kFollowersFollow
206kSubscribersSubscribe
38kFollowersFollow

Latest

Top Non-PLC Certification Courses for Automation Professionals
Top Non-PLC Certification Courses for Automation Professionals
Common
Things You Need to Know About DeviceNet
Things You Need to Know About DeviceNet
Communication
Why is IEC 60269 Important
Why is IEC 60269 Important? – Electrical Applications
Standards
NAMUR OPEN ARCHITECTURE
What is NAMUR OPEN ARCHITECTURE?
Control Systems

Related Articles

Functional Testing of Control Valve Positioners

Functional Testing of Control Valve Positioners

Zero Suppression in level Measurement

Zero Suppression and Zero Elevation Calculations

Laser Level Measurement

Laser Level Measurement Principle

More Articles

Top Non-PLC Certification Courses for Automation Professionals
Common

Top Non-PLC Certification Courses for Automation Professionals

June 9, 2025
Things You Need to Know About DeviceNet
Communication

Things You Need to Know About DeviceNet

June 9, 2025
Why is IEC 60269 Important
Standards

Why is IEC 60269 Important? – Electrical Applications

June 9, 2025
NAMUR OPEN ARCHITECTURE
Control Systems

What is NAMUR OPEN ARCHITECTURE?

June 6, 2025
How to Check the Continuity of Protective Conductors
Electrical Basics

How to Check the Continuity of Protective Conductors?

June 6, 2025
What is Electrical Panel Door Earth Bonding? Explained
Electrical Basics

What is Electrical Panel Door Earth Bonding? Explained

June 6, 2025
automatic changeover switch explained
Electrical Basics

Automatic Transfer Switch – Electrical Circuit, Operation, Video

June 5, 2025
PLC engineering software
PLC TutorialsSoftware

How to Download GX Works? Mitsubishi PLC Software

June 3, 2025
//

Inst Tools

Sign Up for Our Newsletter

Subscribe to our newsletter to get our newest articles instantly!

[mc4wp_form id=”847″]

Follow US
All rights reserved. Reproduction in whole or in part without written permission is prohibited.
Welcome Back!

Sign in to your account

Username or Email Address
Password

Lost your password?