Inst ToolsInst ToolsInst Tools
  • Courses
  • Automation
    • PLC
    • Control System
    • Safety System
    • Communication
    • Fire & Gas System
  • Instrumentation
    • Design
    • Pressure
    • Temperature
    • Flow
    • Level
    • Vibration
    • Analyzer
    • Control Valve
    • Switch
    • Calibration
    • Erection & Commissioning
  • Interview
    • Instrumentation
    • Electrical
    • Electronics
    • Practical
  • Q&A
    • Instrumentation
    • Control System
    • Electrical
    • Electronics
    • Analog Electronics
    • Digital Electronics
    • Power Electronics
    • Microprocessor
  • Request
Search
  • Books
  • Software
  • Projects
  • Process
  • Tools
  • Basics
  • Formula
  • Power Plant
  • Root Cause Analysis
  • Electrical Basics
  • Animation
  • Standards
  • 4-20 mA Course
  • Siemens PLC Course
Reading: Cable Shielding – Purpose, Selection, Grounding
Share
Font ResizerAa
Inst ToolsInst Tools
Font ResizerAa
  • Courses
  • Design
  • PLC
  • Interview
  • Control System
Search
  • Courses
  • Automation
    • PLC
    • Control System
    • Safety System
    • Communication
    • Fire & Gas System
  • Instrumentation
    • Design
    • Pressure
    • Temperature
    • Flow
    • Level
    • Vibration
    • Analyzer
    • Control Valve
    • Switch
    • Calibration
    • Erection & Commissioning
  • Interview
    • Instrumentation
    • Electrical
    • Electronics
    • Practical
  • Q&A
    • Instrumentation
    • Control System
    • Electrical
    • Electronics
    • Analog Electronics
    • Digital Electronics
    • Power Electronics
    • Microprocessor
  • Request
Follow US
All rights reserved. Reproduction in whole or in part without written permission is prohibited.
Inst Tools > Blog > Common > Cable Shielding – Purpose, Selection, Grounding

Cable Shielding – Purpose, Selection, Grounding

In this article we will learn about the cable shielding, purpose, selection factors, and grounding of shields.

Last updated: March 15, 2025 6:16 pm
R Jagan Mohan Rao
Common
1 Comment
Share
6 Min Read
SHARE

Shielding

The shielding in the cables of Instrumentation and Control systems is intended to block electrical noise (interference) induced by the effects of electric fields in the environment.

Contents
ShieldingSelection of Cable ShieldingGrounding Cable ScreenGrounding in the fieldShielded Ground WiresGrounding in control area or the process interface buildings.

Electrical noise or interference are all unwanted signals of electrical origin that can alter the original signal. It is either by coupling inductive or electrostatic discharge.

Most applications of the cables for Instrumentation are the process-oriented acquisition of very low power signals, therefore it is necessary to block as much as possible interference or external noise that may distort information.

Selection of Cable Shielding

Consider the following while selecting shielding:

  • Type of signal to transmit
  • Proximity of noise sources
  • Frequency of noise signals
  • Required cable physical flexibility

Cables with a few types of screens by the manufacturers are discussed below.

Copper Tape Screen with or without Wire Copper  

The copper tape type screen consists of a tape of copper applied in a helical manner, to which has added a series of copper wires.

The purpose of this type of configuration is to make the shielding resistance very small, which is equivalent to a higher current carrying capacity in the event of a fault.

Protection against induction coupling (coupling magnetic by indentations of the screen) in high frequencies and electrostatic discharges.

Copper Tape Screen and Screen in Mesh

Screen in Mesh or Braid of Copper Threads

The screen type mesh, are copper wires twisted together, applied on the core or filling of the cable forming an electrostatic fabric.

This type of shielding provides great flexibility to the cable and protection against coupling by induction or diffusion (usually caused by screen resistance at low frequencies) where low DC resistance is required.

Grounding Cable Screen

In automation systems, proper grounding plays an important role in the health and integrity of the overall process signals.

Cable Shielding - Purpose, Selection, Grounding

Proper grounding protects automation systems from possible damage due to

  • power surges,
  • voltage fluctuations,
  • lightning strikes, and
  • short circuits.

Apart from the above, a proper grounding hierarchy helps reduce signal noise and interference.

It is by providing a low-resistance pathway for these unwanted voltages and currents that could lead to safety hazards or degradation of processing control signals. In looking into the field of problems associated with signal noise, erratic spikes, or interference problems, we find that most of these problems arise from poor grounding.

To ensure proper grounding of instrumentation systems, a clear grounding scheme must be followed.

One must carefully evaluate the whole grounding system when diagnosing a problem or when designing new plants. These areas are grounding in the field, interconnecting wiring, and grounding within the control buildings or the central process interface.

Grounding in the field

In the field, the enclosures of all instrument devices have to connect to the ground, usually the general grounding network of the plant, or a link to an electrically conductive structure that is connected to the network.

Raceways such as ducts and trays are grounded at both ends.

Shielded Ground Wires

One must properly cut the tape and shield and its ground wire in the field, near the instrument. From field instruments, all the way to sorting cabinets, shield drain wires must be treated and terminated similar to signal cables.

Once the instrument loop reaches the marshaling cabinet, the shield drain wires have to be assembled and tied together and terminate at the bus bar for the ground shield.

Exposed parts of discharge cables within junction boxes or sorting cabinets should be covered with insulation tape to protect against the possibility of multiple drain wires contacting each other.

In addition to the above measure, all spare pairs or triads that run between field junction boxes and sorting cabinets must be terminated at both ends.

In some cases, it would be helpful to ground the replacement wiring in the classification cabinets to minimize the potential noise pickup.

Grounding in control area or the process interface buildings.

In the control room or the process interface of buildings, the cabinets of the process automation system and classification cabinets must be equipped with two bars: one for bus AC & DC ground connection and another for common discharge cables and shield.

The DC bus bar and shield ground must be electrically isolated from the cabinet structure.

All shield drain cables and DC cables must be joined and connected to the insulated bus bars. It is vitally important to secure screened discharge cables to the ground at one end, usually in marshaling classification cabinets. Grounding them at both ends can result from in-ground loops, which happen to be a major cause of signal noise.

Read Next:

  • SIL Verification
  • How to Choose UPS?
  • Instrument Junction Box
  • Instruments Tapping Points
  • Instrumentation Design Engineer
Don't Miss Our Updates
Be the first to get exclusive content straight to your email.
We promise not to spam you. You can unsubscribe at any time.
Invalid email address
You've successfully subscribed !

Continue Reading

Metric Prefixes and Unit Conversions
Difference Between Skin Effect and Proximity Effect
How does the IIoT work? – Industrial Internet of Things
Best Engineering Mobile Apps on Google Play & App Store
What Type of Heating is Best for Your Home?
Flange Types and Definitions
Share This Article
Facebook Whatsapp Whatsapp LinkedIn Copy Link
Share
1 Comment
  • RAPOLU VAISHNAVI says:
    January 8, 2022 at 7:49 pm

    Made easy to understand,nice article.

    Reply

Leave a Reply Cancel reply

Your email address will not be published. Required fields are marked *

Stay Connected

128.3kFollowersLike
69.1kFollowersFollow
210kSubscribersSubscribe
38kFollowersFollow

Categories

Explore More

What is Linear Electric Motor?
How is Electricity Generated From Solar Energy?
Conveyor : Belt, Screw, Pneumatic, Hydraulic, Roller, Chain, Bucket, Vibratory
Introduction to Chemical Dosing System
Dew Point in Instrument Air
Use of Isolator in Microwaves
Web Tension Measurement and Control Technologies
Difference between HVAC Absorption Chillers and Electric Chillers

Keep Learning

Hydrogen Sulfide Accident

The Aghorn Hydrogen Sulfide Accident – H2S Gas

How to Prevent Conveyor Problems

Common Conveyor Problems and How to Prevent Them

Top 10 Podcasts about Electronics

Top 10 Podcasts about Electronics

Top 20 Service Business Opportunities in the Instrumentation Industry

Top 20 Instrumentation Service Business Opportunities in the Industry

Automation in Logistics Industry

Automation in Logistics Industry

Brass Cable Gland

How to Choose a Brass Cable Gland Manufacturer?

P&ID Legend

What is a Legend? – Piping and Instrumentation Diagram

Batch Pan Automation in the sugar industry

Batch Pan Automation in the Sugar Industry

Learn More

PLC Circuit with Switches

PLC Example with Switches

Sugar Industry Logics

Mill Interlocks in the Sugar Industry

Online Analyzers Questions & Answers

Online Analyzers Questions & Answers

Diode-positive-limiter

Positive & Negative Diode Clippers

Why Fiber Optic Cable is Spliced rather than Termination

Why Fiber Optic Cable is Spliced rather than Termination?

How to Do Maintenance of Control Valve Which is Stuck in Field?

How to Do Maintenance of Control Valve Which is Stuck in Field?

PID Loop Tuning

PID Controller Loop Tuning Questions and Answers – Part 1

Electrical Machines Questions and Answers

Transformer Losses and Efficiency

Menu

  • About
  • Privacy Policy
  • Copyright

Quick Links

  • Learn PLC
  • Helping Hand
  • Part Time Job

YouTube Subscribe

Follow US
All rights reserved. Reproduction in whole or in part without written permission is prohibited.
Welcome Back!

Sign in to your account

Username or Email Address
Password

Lost your password?