Inst ToolsInst ToolsInst Tools
  • Ask
  • Courses
  • Videos
  • Q & A
    • Interview
      • Instrumentation
      • Electronics
      • Electrical
      • Practical Questions
    • MCQ
      • Instrumentation MCQ
      • Electrical MCQ
      • Electronics MCQ
      • Control Systems MCQ
      • Analog Electronics MCQ
      • Digital Electronics MCQ
      • Power Electronics MCQ
      • Microprocessor MCQ
      • Multiple Choice Questions
  • EE
    • Electronics
      • Electronics Q & A
      • Electronic Basics
      • Electronic Devices & Circuits
      • Electronics Animation
      • Digital Electronics
    • Electrical
      • Electrical Basics
      • Electrical Q & A
      • Power Electronics
      • Electrical Machines
      • Electrical Animation
      • Power Systems
      • Switchgear & Protection
      • Transmission & Distribution
  • Measure
    • Control Valves
    • Calibration
    • Temperature
    • Pressure
    • Flow
    • Level
    • Analyzers
    • Switches
    • Vibration
    • Solenoid Valve
  • Control
    • PLC Tutorials
    • Control Systems
    • Safety Instrumented System (SIS)
    • Communication
    • Fire & Gas System
  • More
    • Design
    • Tools
    • Animation
    • Basics
    • Formulas
    • Standards
    • TextBooks
    • Common
    • Software
    • Excel Tools
    • Erection & Commissioning
    • Process Fundamentals
    • Videos
    • Books
Search
All rights reserved. Reproduction in whole or in part without written permission is prohibited.
Reading: Erratic Stroking Control Valves Delaying the Shutdown Plant Restart
Share
Notification Show More
Font ResizerAa
Inst ToolsInst Tools
Font ResizerAa
  • Courses
  • PLC Tutorials
  • Control Systems
Search
  • Ask
  • Courses
  • Videos
  • Q & A
    • Interview
    • MCQ
  • EE
    • Electronics
    • Electrical
  • Measure
    • Control Valves
    • Calibration
    • Temperature
    • Pressure
    • Flow
    • Level
    • Analyzers
    • Switches
    • Vibration
    • Solenoid Valve
  • Control
    • PLC Tutorials
    • Control Systems
    • Safety Instrumented System (SIS)
    • Communication
    • Fire & Gas System
  • More
    • Design
    • Tools
    • Animation
    • Basics
    • Formulas
    • Standards
    • TextBooks
    • Common
    • Software
    • Excel Tools
    • Erection & Commissioning
    • Process Fundamentals
    • Videos
    • Books
Follow US
All rights reserved. Reproduction in whole or in part without written permission is prohibited.
Inst Tools > Blog > Root Cause Analysis (RCA) > Erratic Stroking Control Valves Delaying the Shutdown Plant Restart

Erratic Stroking Control Valves Delaying the Shutdown Plant Restart

Root Cause Analysis (RCA): Erratic Stroking Control Valves threaten delaying the 4-months shutdown plants restart.

Last updated: September 28, 2022 3:22 pm
S Raghava Chari
Root Cause Analysis (RCA) Control Valves
No Comments
Share
5 Min Read
SHARE

Root Cause Analysis (RCA): Erratic Stroking Control Valves threaten delaying the 4-months shutdown plants restart.

Contents
Control Valve ProblemAuthor SolutionSuccessEpilogue

Note: This root cause analysis (RCA) is from real-time scenarios that happened in industries during the tenure of one or two decades ago. These articles will help you to improve your troubleshooting skills and knowledge.

Control Valve Problem

Severe drought forced a 4‑months plant shutdown, as all available water did not meet the citizen’s drinking water needs even.

Operators checked the equipment two weeks before the plant water supply promised resumption. They found around 75 erratically stroking control valves (CV).

Even smart instrument engineers and crews’ inability to set the CVs’ valve positioners (VP) right resulted in the author – then instrument chief – intervention.

Erratic Stroking Control Valves
Control Valve

Note: The above image is not related to this root cause analysis of the control valves article.

Author Solution

The Difficult to Diagnose, Unusual, and Despairing Problem (DDUDP) baffled the author too. His guess of the VPs’ damaged input, output bellows, or both seemed ridiculous as the minus 40 deg C dew point moisture and oil-free instrument air-wetted VPs parts shined as new.

In the absence of other causes, he dissembled a calibration defying valve positioner (VP) input bellow reluctantly. Lo & Behold! The spring inside was so rusted that finger pressing crumbled it.

How the absolutely dry air wetted springs rusted is still a mystery! Random 3 more bellows springs too crumbled easily.

An unusual step solves the unusual problem! The USA valve vendor refusal to airfreight springs only, his exorbitant prices for the entire bellows assemblies and 3 months deliveries despaired all, eager to start the 4 months long shutdown plant soonest. The managers urged the author to find a quick and lasting solution hook or crook!

After an hour thought, the author gave a spring removed from a good valve positioner (VP) to a local spring maker and asked him to supply 25 Nos. identical springs by the evening! He dispelled the aghast all persons particularly instrument engineers and technicians objections thus:

  • Springs made out equal dia same spring steel wire copying the original will have the original spring’s load vs. deflection characteristics, subject to minor individual variations because of making tolerances
  • Calibrating each positioner strokes the control valve correctly despite the springs’ springs load vs. deflection characteristics minor variations. This is the reason for calibrating each valve positioner with even VP vendor provided springs.
  • Still all were doubtful and sure the author’s attempt would fail and awaited the imported high cost input bellows assemblies arrival.

Success

The vendor delivered 25 Nos. springs the next morning. Since none found the spring rusting cause, the author got the springs dipped in anti-corrosive black paint and sun-dried to avoid likely corrosion.

Instrument technicians fitted one each to randomly selected six different travels control valves and their valve positioners. The six control valve’s easy and repeatable calibrations pleasantly surprised all.

The skeptics who predicted doom also grudgingly admired the author! The vendor delivered 60 more springs the next day and fulfilled the order.

The bold step benefits:

The bold step benefits are:

  1. Crew fitted a painted spring to each of the erratic stroking control valves (CVs) and readied all CVs within 3-days. The valve positioners (VPs) calibrations were easy, repeatable and hysteresis free.
  2. Randomly checked two days before water supply resumption 10 CVs fine stroking doubly assured the new springs’ quality.
  3. The valve positioners repair costs were negligible
  4. The US valve vendor accepted the bellows assemblies order cancellation free of charge
  5. Above all the three months re-start delay threat eliminated.

Epilogue

A year later inspected 3 Nos. random springs were sound and not corroded. The local springs fitted all valve positioners performed as problems-free as other valve positioners during the author’s 15 years-long service in the plant.

Author: S. Raghava Chari

Do you face any issues with control valves? Share with us through the below comments section.

If you liked this article, then please subscribe to our YouTube Channel for Instrumentation, Electrical, PLC, and SCADA video tutorials.

You can also follow us on Facebook and Twitter to receive daily updates.

Read Next:

  • Sliding Stem Control Valve
  • Types of Pneumatic Valves
  • Protect Pumps from Cavitation
  • Pressure Relief Valve Principle
  • Valve Multiple Choice Questions
Don't Miss Our Updates
Be the first to get exclusive content straight to your email.
We promise not to spam you. You can unsubscribe at any time.
Invalid email address
You've successfully subscribed !
Valve Actuator Bench Set
Control Valve Passing Problem after Overhauling Job
Basic Requirements of Control Valves Sizing
Safety Liquid Ammonia Disconnect threatens NH3 Vapor Spill
Fire burnt Ammonia Converter Thermocouples Problem
Share This Article
Facebook Whatsapp Whatsapp LinkedIn Copy Link
Share
Leave a Comment

Leave a Reply Cancel reply

Your email address will not be published. Required fields are marked *

Stay Connected

128.3kFollowersLike
69.1kFollowersFollow
208kSubscribersSubscribe
38kFollowersFollow

Categories

Recent Comments

  • Kamli on Top Free PLC Software
  • Guifty Shimica on Top Non-PLC Certification Courses for Automation Professionals
  • Guifty Shimica on Top Non-PLC Certification Courses for Automation Professionals
  • MIHARITSOA Aina Sitraka on Top Non-PLC Certification Courses for Automation Professionals

Related Articles

Safety Relief Valve

Safety Relief Valve Quiz: Test Your Knowledge

Top 80+ Valve Questions and Answers

Top 80+ Valve Questions and Answers

Difference Between Solenoid Valve and Motorized Valve

Difference Between Solenoid Valve and Motorized Valve

butt weld end Plug Valves Leaks Stopped

PTFE lined 6” 300# butt weld end Plug Valves Leaks Stopped Forever

Difference between Butterfly Valves and Ball Valves

Difference between Butterfly Valves and Ball Valves

Types of Control Valve Trim

Types of Control Valve Trim

Butterfly Valve Failure caused Fire

Butterfly Valve Failure Caused Serious vicinity Heavy Fire

trip solenoid installed on a control valve appears

SIS Final Control Elements

More Articles

Total Organic Carbon Analyzers Questions and Answers

Total Organic Carbon Analyzers Questions and Answers

diode-clamper-circuit

Full Wave Voltage Doubler using Diodes

Electrical Systems vs. Pneumatic Systems

Electrical Systems vs. Pneumatic Systems

Impulse Tubing Leak Test Checks

Impulse Tubing Leak Test Checks

Ball Valve Material Selection

Ball Valve Material Selection

In-Situ Zirconia Oxygen Analyzer

Oxygen (O2) Measurement in Flue Gas

Air Cylinder Consumption Calculation for Control Valves

Air Cylinder Consumption Calculation for Control Valves

Digital Electronics Multiple Choice Questions

Triggering of Flip Flops Objective Questions

Follow US
All rights reserved. Reproduction in whole or in part without written permission is prohibited.
Welcome Back!

Sign in to your account

Username or Email Address
Password

Lost your password?