Reading: Identify the Pressure Gauge Error
Share
Notification Show More
Font ResizerAa
Inst ToolsInst Tools
Font ResizerAa
  • Courses
  • PLC
  • Control Systems
Search
  • Courses
  • Automation
    • PLC
    • Control System
    • Safety System
    • Communication
    • Fire & Gas System
  • Instrumentation
    • Design
    • Pressure
    • Temperature
    • Flow
    • Level
    • Vibration
    • Analyzer
    • Control Valve
    • Switch
    • Calibration
    • Standards
    • Basics
    • Formula
    • Erection & Commissioning
    • Process Fundamentals
    • Root Cause Analysis
  • Interview
    • Instrumentation
    • Electrical
    • Electronics
    • Practical
  • Q&A
    • Instrumentation
    • Control System
    • Electrical
    • Electronics
    • Analog Electronics
    • Digital Electronics
    • Power Electronics
    • Microprocessor
Follow US
All rights reserved. Reproduction in whole or in part without written permission is prohibited.
Inst Tools > Blog > Practical Questions > Identify the Pressure Gauge Error

Identify the Pressure Gauge Error

An operator claims pressure gauge is defective and needs to be replaced. The pressure controller and gauge readings are different.

Last updated: September 7, 2020 5:05 pm
Editorial Staff
Practical Questions Pressure Measurement
No Comments
Share
3 Min Read
SHARE

An operator claims pressure gauge PG-108 is defective and needs to be replaced. This pressure gauge registers 50 PSI, while pressure controller PIC-33 and pressure recorder PR-33 both register the pressure as being equal to setpoint: 43 PSI.

Before replacing this pressure gauge, however, you decide to do some diagnostic thinking to see if there might be other causes for the abnormally high reading at PG-108.

The first thing you check is the position of control valve PV-33a, and you find its stem position to be at 35% open.

Identify the Pressure Gauge Error

Identify the Pressure Gauge Error

Identify the likelihood of each specified fault in this process. Consider each fault one at a time (i.e. no coincidental faults), determining whether or not each fault could independently account for all measurements and symptoms in this process.

Identify the below faults are possible or impossible?

  • PG-108 calibration error
  • PT-33 calibration error
  • PIC-33 left in manual mode
  • PY-33a calibration error
  • PY-33b calibration error

Finally, identify the next diagnostic test or measurement you would make on this system. Explain how the result(s) of this next test or measurement help further identify the location and/or nature of the fault.

Answer:

The fact that the gauge disagrees with both the recorder and the controller tells us the problem is either with the gauge or with the transmitter. Nothing else (controller mode, valve signal path, PY-33a) could cause this to happen.

Therefore, valid tests include anything to help us discern whether there is a problem in the gauge, in the transmitter, in the resistor, or in the controller’s PV input.

  • PG-108 calibration error – Possible
  • PT-33 calibration error – Possible
  • PIC-33 left in manual mode – Impossible
  • PY-33a calibration error – Impossible
  • PY-33b calibration error – Impossible

More Questions:

  1. Based on the information you have at this point, can you tell whether any suspected calibration error is due to a misadjustment of zero or of span? Explain why or why not.
  2. Is controller PIC-33 direct-acting or reverse-acting? How can you tell?
  3. Does control valve PV-33a throttle gas or liquid? How can you tell?
  4. Identify a typographical error in this P&ID.
  5. A useful diagnostic technique for identifying which instrument is miscalibrated is to compare the readings of multiple instruments (all sensing the same process variable) to see which one of them disagrees most with the others. May we apply this technique to the problem at hand? If so, which instrument readings should we compare? If not, explain why not.

Share your answers with us through the below comments section.

Read Next:

  • Loop Diagram Questions
  • Faults in a Transformer
  • Control Loop Questions
  • Pressure Control Loop
  • Problem with Pirani Gauge

Credits: Tony R. Kuphaldt

Don't Miss Our Updates
Be the first to get exclusive content straight to your email.
We promise not to spam you. You can unsubscribe at any time.
Invalid email address
You've successfully subscribed !

Continue Reading

Example PLC Program
Draw the appropriate Pressure Switch Symbol ?
What is the Purpose of Chemical Seals Pressure Transmitter?
Identify Faults in PID Control Loop
How much Pressure is applied to Inclined Water Manometer?
Galileo Thermometer
Share This Article
Facebook Whatsapp Whatsapp LinkedIn Copy Link
Share
Leave a Comment

Leave a Reply Cancel reply

Your email address will not be published. Required fields are marked *

Stay Connected

128.3kFollowersLike
69.1kFollowersFollow
208kSubscribersSubscribe
38kFollowersFollow

Categories

Explore More

Displacer Level Transmitter Question & Answer
Type E thermocouple Calculations
Determine the Problems with Level Transmitter and Gauge
Solenoid Valves Practical Problems
Question on Analytical Controller
Calculate LRV and URV for 4-20 mA Loop-powered DP Transmitter
Purge Type Level Transmitter Questions
Scaling Sensor Output to Engineering Units

Keep Learning

Calculation of Hydrostatic Pressure

Calculation of Hydrostatic Pressure

Programmable Logic Controller (PLC) Questions and Answers

Programmable Logic Controller (PLC) Questions and Answers – 1

pressure transmitter calibration setup

Questions on Pressure Transmitter Calibration Setup

Direct Mounting of Diaphragm Seals Level Transmitter

What are the Mounting Techniques of Diaphragm Seals?

Which instrument is at fault in this system

Which Instrument is at Fault in this System?

Types of Pressure Measuring Scales

Types of Pressure Measuring Scales

Pressure Transmitter Calibration Procedure

Pressure Transmitter Calibration Procedure

Explain What these Spool Valve Represent

Explain What these Spool Valve Symbols Represent?

Learn More

Top 100 Instrumentation Engineering Questions & Answers

Top 100 Instrumentation Engineering Questions & Answers

Various Types of Sensors Used in Water Treatment Plant

Various Types of Sensors used in Water Treatment Plant

Types of Industrial Level Sensors

Types of Industrial Level Sensors

What is a Magnetic Contactor

What is a Magnetic Contactor? – Principle, Types, Advantages

Design Basis for Fire Detection and Alarm System

Design Basis for Fire Detection and Alarm System

Power Systems Questions & Answers

Power Systems MCQ Series 14

Difference between Globe Valve and Gate Valve

Difference between Globe Valve and Gate Valve ?

On Delay Timer TON in Tia Portal

Timers in PLC Programming – Siemens Tia Portal Tutorials

Follow US
All rights reserved. Reproduction in whole or in part without written permission is prohibited.
Welcome Back!

Sign in to your account

Username or Email Address
Password

Lost your password?