In the present times, Smart transmitters are widely used in process industries. However, ordinary transmitters still exist in various industries, its application is confined to non-critical and applications of less importance.
This article analyses the difference between the ordinary transmitter and smart transmitter taking pressure, differential pressure transmitter, and temperature into consideration.
Key differences between ordinary transmitter and smart transmitter:
The major improvements of smart transmitter’s accuracy, static pressure effects, temperature performance, and time stability give an overall improvement in the performance.
Rangeability is increased to 400: 1 for the smart transmitter against the ordinary transmitter from 6:1.
Significantly extended rangeability helps to
A clear example of real savings through increased rangeability is in applications where two or more conventional units are applied across a single orifice plate to improve accuracy over a wide range of flows.
The increased rangeability of the smart transmitter means that only one unit is required, thereby saving not only the other units and the cost of installing and maintaining them and also preventing the inherent low reliability of two or three loops against one.
In the case of the smart transmitter, the range can be changed manually through the communicator for different plant operating conditions.
The smart transmitter range, damping, etc., can now be adjusted from up to 1500 m away by communication over the 4-20 mA signal line.
The adjustment can be done by connecting a smart field communicator (SFC) across the two signal lines at any point along their path.
Adjustments are made in any engineering units selectable from PSI, m bar, bar, k Pa.
The re-ranging of the smart transmitter without applying pressure is possible.
Calibration corrections can be made for small errors caused by mounting angle effects.
Zero checks, and corrections if necessary, can be performed from the control room at plant shut-downs or during normal maintenance.
Rearranging and remote diagnostics can now be performed back at the control room, thus taking a fraction of the previous maintenance time which usually requires two men for several hours to do any field check or change.
All of the above can be carried out by one man from the convenience of the central location.
The main aim of smart transmitters has been designed with reliable and stable operation as the dominant requirement.
A few components are used, and protection is provided against damaging influences, such as reverse polarity, over-pressure, and surge voltage.
The smart transmitters also have been designed to meet Cenelec Intrinsic Safety and Explosion-proof Standards as well as other International Safety Approval requirements.
The enclosure complies with classification IP67 which prevents moisture, dust ingress problems with the working of the transmitter.
In the smart transmitter, since they do not contain switches, links, or any type of adjustments in the electronics compartment, the integrity transmitter enclosure need not be disturbed, and the likelihood of a transmitter cap being left loose is greatly reduced.
Diagnostic aids are included in both transmitters and SFC to avoid misuse, e.g. by identifying excessive process temperature or, in the event of a component breakdown, to identify the fault, advise the SFC operator and alert the control room by giving an upscale alarm signal.
In the event of a transmitter or loop problem, the diagnosis via the SFC from the control room area will identify the problem and corrective action by the maintenance team can be carried out. Loop downtime is minimized.
Read Next:
The conveyor sorting machine is widely used in the packing industries using the PLC program…
Learn the example of flip-flop PLC program for lamps application using the ladder logic to…
In this article, you will learn the STAR DELTA programming using PLC controller to start…
Lube oil consoles of rotary equipment packages in industrial process plants are usually equipped with…
Rotating equipment packages such as pumps, compressors, turbines need the lube oil consoles for their…
This article explains how to blink lights in ladder logic with a detailed explanation video…