In Flow Control Loop, Trace the path of current in the loop diagram signal wiring, then determine voltage drops at the respective flow rates. Examine the following loop diagram:
Trace the path of current in the signal wiring, then determine the following voltage drops at the respective flow rates. Assume a power supply voltage of exactly 24 volts DC:
Voltage across FY-14 resistor = __________ ; Flow rate = 100 GPM
Voltage between terminals TB40-3 and TB40-4 = __________ ; Flow rate = 200 GPM
Voltage across FT-14 transmitter terminals = __________ ; Flow rate = 175 GPM
Voltage between terminals TB64-8 and TB27-15 = __________ ; Flow rate = 200 GPM
Voltage across FY-14 resistor = 2.6 volts ; Flow rate = 100 GPM
Voltage between terminals TB40-3 and TB40-4 = 19.8 volts ; Flow rate = 200 GPM
Share Your Answers for the remaining questions.
Credits: Tony R. Kuphaldt
The conveyor sorting machine is widely used in the packing industries using the PLC program…
Learn the example of flip-flop PLC program for lamps application using the ladder logic to…
In this article, you will learn the STAR DELTA programming using PLC controller to start…
Lube oil consoles of rotary equipment packages in industrial process plants are usually equipped with…
Rotating equipment packages such as pumps, compressors, turbines need the lube oil consoles for their…
This article explains how to blink lights in ladder logic with a detailed explanation video…
View Comments
How voltage across fy-14 is 2.6 volts at 100gpm can your ellaborate please???
My mail id engtarique451@gmail.com or whatsapp no. +96660330861
I dont know how it came please reply me
From the diagram, the flow transmitter range is 0 to 250 gpm
Now Calculate the loop current at 100 gpm, it is 10.4 mA
Calculate Voltage, V = I.R = 10.4mA x 250 = 2.6 v
You can use this online calculator: https://instrumentationtools.com/instrumentation-calculator/
Voltage across FY-14 resistor = __________ ;
Voltage between terminals TB40-3 and TB40-4 = __________ ;
Voltage across FT-14 transmitter terminals = __________ ;
Voltage between terminals TB64-8 and TB27-15 = __________ ;
if 80 GMP. thank you.
I need a sample.
Voltage across FY-14 resistor = 2.6 Volts ; Flow rate = 100 GPM
Voltage between terminals TB40-3 and TB40-4 = 24 volts ; Flow rate = 200 GPM
Voltage across FT-14 transmitter terminals = 24 volts ; Flow rate = 175 GPM
Voltage between terminals TB64-8 and TB27-15 = 24 volts ; Flow rate = 200 GPM
Why is the voltage between terminals TB40-3 and TB40-4 = 19.8 volts ; Flow rate = 200 GPM? It should be 24 volts because the analog output and inputs is 4 to 24 mA and constant voltage of 24 voltage because parallel connection from the PS to FT
Hello guys!
Correct answers:
1. 2.6V
2. 19.8V
3. 20.2 V
4. 0.0 V
If you are still confused pls connect with me I will send my solution
Alikhansadykov97@gmail.com