Vibration Measurement

AND Logic in Bently Nevada Vibration System

One of the most important and confusing concepts in Bently Nevada is Normal AND vs True AND.

This is used in logic building.

Suppose there is one heavy rating machine in your plant and obviously it is expensive. We use special safety systems for these machines like vibration and temperature monitoring and protection systems so whenever there is an abnormality in vibration/temperature observed, then the machine should trip accordingly.

Bently Nevada Vibration System

AND Logic in Bently Nevada Vibration System

Now assume the following logic:

High vibration in two vibration probes is used for machine trips. (The two probes must detect High vibration then only the machine will be tripped)

In the above case, what if 1 vibration probe goes to NOT OK? (NOT OK means the sensor probe failed or it is damaged). In this case, say only 1 probe detected it and as per logic, the machine should trip on high vibration of both probes, but the machine won’t trip because only 1 probe detected and the other probe is in a faulty state.

Now again think of another example where the process is more important and machines should not trip on spurious vibrations. Now here what if one vibration probe goes to NOT OK and the other detects high vibration?

Yes, it’s confusing!

Now here we have to understand the role of Normal AND and True AND.

Normal AND Logic

In Normal AND whenever a probe goes into the NOT OK state, it is taken out of logic, and logic is degraded.

Consider 2 out of 2 logic.

In the 2oo2 logic, if the Probe 1 detects high vibration and Probe 2 is NOT OK

Then logic becomes 1 out of 1 considering Probe 1 as input.

This type of configuration is used when the machine is more important than the process.

True AND Logic

In True AND whenever a probe goes into the NOT OK state, the logic remains the same.

Consider 2oo2 logic again.

In two-out-two logic, if Probe 1 detects high vibration and Probe 2 is NOT OK.

Then machine won’t trip even if Probe 1 detects high vibration.

This type of configuration is used when the process is more important than the machine.

This logic is driven through a relay which is normally de-energized (can be changed to normally energized also).

Normal AND Truth table

The below table shows the different possible scenarios using Normal AND logic in the Bently Nevada condition monitoring system.

Vibration Probe 1Vibration Probe 2Relay Status
Normal VibrationNormal VibrationDe-energized
Normal VibrationNOT OKDe-energized
NOT OKNormal VibrationDe-energized
High VibrationNOT OKEnergized
NOT OKHigh VibrationEnergized
NOT OKNOT OKDe-energized
High VibrationHigh VibrationEnergized

True AND Truth table

The below table shows the different possible scenarios using True AND logic in the Bently Nevada condition monitoring system.

Vibration Probe 1Vibration Probe 2Relay Status
Normal VibrationNormal VibrationDe-energized
Normal VibrationNOT OKDe-energized
NOT OKNormal VibrationDe-energized
High VibrationNOT OKDe-energized
NOT OKHigh VibrationDe-energized
NOT OKNOT OKDe-energized
High VibrationHigh VibrationEnergized

If you liked this article, then please subscribe to our YouTube Channel for Instrumentation, Electrical, PLC, and SCADA video tutorials.

You can also follow us on Facebook and Twitter to receive daily updates.

Read Next:

You've successfully subscribed !

View Comments

Share

Recent Articles

  • PLC Tutorials

VFD Simulator Download – Free Yaskawa V1000 Software

VFD simulator download: Master the online tool from the Yaskawa V1000 & programming software for…

2 days ago
  • PLC Tutorials

Conveyor Sorting Machine PLC Program with Calculation Function

The conveyor sorting machine is widely used in the packing industries using the PLC program…

5 days ago
  • PLC Tutorials

Example of Flip-Flop PLC Program for Lamps Application

Learn the example of flip-flop PLC program for lamps application using the ladder logic to…

5 days ago
  • PLC Tutorials

STAR DELTA Programming using PLC Controller

In this article, you will learn the STAR DELTA programming using PLC controller to start…

6 days ago
  • Instrumentation Design

Single and Three Phase Immersion Electrical Heaters Wiring Circuits

Lube oil consoles of rotary equipment packages in industrial process plants are usually equipped with…

3 days ago
  • Instrumentation Design

Immersion Heaters in Lube Oil Consoles

Rotating equipment packages such as pumps, compressors, turbines need the lube oil consoles for their…

5 days ago