Reading: Control Modes of Air Handling Unit (AHU) – HVAC Basics
Share
Notification Show More
Font ResizerAa
Inst ToolsInst Tools
Font ResizerAa
  • Courses
  • Design
  • PLC
  • Interview
  • Control System
Search
  • Courses
  • Automation
    • PLC
    • Control System
    • Safety System
    • Communication
    • Fire & Gas System
  • Instrumentation
    • Design
    • Pressure
    • Temperature
    • Flow
    • Level
    • Vibration
    • Analyzer
    • Control Valve
    • Switch
    • Calibration
    • Erection & Commissioning
  • Interview
    • Instrumentation
    • Electrical
    • Electronics
    • Practical
  • Q&A
    • Instrumentation
    • Control System
    • Electrical
    • Electronics
    • Analog Electronics
    • Digital Electronics
    • Power Electronics
    • Microprocessor
Follow US
All rights reserved. Reproduction in whole or in part without written permission is prohibited.
Inst Tools > Blog > Control Systems > Control Modes of Air Handling Unit (AHU) – HVAC Basics

Control Modes of Air Handling Unit (AHU) – HVAC Basics

In this article, we will learn the different control modes of air handling unit (AHU). Understand the control strategies used in HVAC.

Last updated: May 23, 2023 4:24 pm
Viral Nagda
Control Systems
No Comments
Share
6 Min Read
SHARE

AHU stands for an air handling unit. AHU is a very important application in handling air flow and maintaining temperature, humidity, and differential pressure. This is because proper air is a must for human survival.

Contents
Control Modes of Air Handling UnitNight Cycle ModeOccupied Operation ModeExtended Operation ModeAHU Off Delay ModeFire ModeConstant DAT (discharge air temperature) ControlSequential Control of Output SignalsCompulsory Damper Monitoring Mode

AHU is thus controlled mostly nowadays by industrial automation. Because automation is involved, various techniques have been adapted in a single AHU to run it efficiently.

Control Modes of Air Handling Unit

Control Modes of Air Handling Unit (AHU) - HVAC Basics

A single strategy for running AHU cannot prove worthwhile, because you can overall control the efficiency of HVAC by various control modes. So, there are many control strategies used in an AHU, depending upon the application.

Different types of controls can reduce power consumption, improve the comfort of occupants by means of scheduled operation and also handle alarms more properly.

In this article, we will learn the general types of control modes used in an air handling unit (AHU).

Night Cycle Mode

AHU cools down the temperature during daytime or simply, when occupants are present in a room during working hours. But, during night time, when fewer or no occupants are present, then there is no use to run the Air Handling Unit at full efficiency.

For this, a mode called night mode is programmed in PLC. When night mode is enabled either by a manual switch or automatically (PLC will read current time), then the blower will run at a lesser speed; and the temperature set-point will be increased.

This will make the cooling elements like compressors and chillers run at a lesser frequency. Ultimately, your energy consumption will reduce due to this strategy.

Occupied Operation Mode

 This is the normal running mode of AHU. As discussed earlier, this mode is used during normal working hours with a proper number of occupants.

The blower is run at a nominal speed and the cooling elements run at a normal temperature to maintain temperature and humidity.

Extended Operation Mode

When the number of occupants rises, with the additional requirement of cooling, then this mode is activated either manually or automatically.

Temperature set-points will reduce further and blowers will run at faster speeds. This will make the AHU run more with more power consumption.

AHU Off Delay Mode

Sometimes it is required to turn off the AHU after a delay. This requirement mostly comes in the case of the usage of heaters or humidifiers. If you turn off the AHU along with them, then there are chances of the heater still being hot or moist air still present due to lack of movement of air.

So, in this mode, the heaters or humidifiers are turned off immediately, but the AHU is kept running for some time. This cools down heating coils or removes moist air.

Fire Mode

When the fire is sensed in the system, then the AHU will turn off immediately with all the respective heating and cooling elements.

This enables fire mode in the PLC and during this, fire dampers will remain open fully. When the system goes back to the normal state, then fire dampers will get closed once again.

Constant DAT (discharge air temperature) Control

In constant mode, the discharge air temperature is tried to be kept at a constant value by use of PID. PID will operate on a single set-point and this PID will be controlled by the discharge air temperature.  

Sequential Control of Output Signals

Suppose there are multiple actuators connected in series. Then, this mode is used to control these outputs. One actuator is controlled until the end of its available range before the next actuator is used.

The PID control is divided over multiple actuators. The user can define the order and percentage of the PID control signal for each actuator. This similar control can be used for multiple fans, heaters, dampers, and coolers.

Compulsory Damper Monitoring Mode

This mode makes sure that dampers are opened or closed before starting or stopping the AHU, or the modulating type dampers are run for a certain time to then make AHU functional.

This requires limit switch inputs from dampers. Damper control makes AHU safer to operate because then there will be no issue of clogged air or air not passing through ducts, or even fire not spreading in the room.

These are the general modes used everywhere in AHU systems. You can customize the program in a PLC according to your requirements, for modulating the various heating and cooling elements accordingly. In this way, we saw the different control modes of AHU.

Read Next:

  • Types of HVAC Chillers
  • HVAC Heat Transfer Loops
  • Automation used in HVAC
  • HVAC Objective Questions
  • Valves in HVAC System
Don't Miss Our Updates
Be the first to get exclusive content straight to your email.
We promise not to spam you. You can unsubscribe at any time.
Invalid email address
You've successfully subscribed !

Continue Reading

Basics of Loop Checks
Functional Design Specifications for DCS and SIS Projects – FDS Document
PID Controller Loop Tuning Questions and Answers – Part 1
How to Select the Right Type of Controller
Two Element Drum Level Control System
How to Stop Cyber Attacks on PLC or DCS?
Share This Article
Facebook Whatsapp Whatsapp LinkedIn Copy Link
Share
Leave a Comment

Leave a Reply Cancel reply

Your email address will not be published. Required fields are marked *

Stay Connected

128.3kFollowersLike
69.1kFollowersFollow
210kSubscribersSubscribe
38kFollowersFollow

Categories

Explore More

Identify Instruments in Piping and instrumentation Diagram
ON-OFF Controller Principle
Understanding a Process Control Loop
System Cabinet Health Checks – PLC and DCS Industrial Automation
PID Controller Selection
What is a Transducer ?
What is PV Tracking ?
Recognizing an Over-Tuned PID Controller by Phase Shift

Keep Learning

Analog Instruments

Explaining Various Types of Analog Instruments

Control Systems Interview Questions & Answers

Control Systems Interview Questions & Answers

Identify Process Variables in P&ID

Identify Process Variables in P&ID

What is a Network Switch?

Network Switch Requirement in SCADA and DCS Architecture

controller integral wind-up

Limit Controls : High Limit & Low Limit Functions

Sources of Static Grounding and Methods to Control

Sources of Static Grounding and Methods to Control

Troubleshooting PLC Current Loops

Troubleshooting Current Loops with Voltage Measurement

DCS Alarm Summary Dashboard using Microsoft Power BI

DCS Alarm Summary Dashboard using Microsoft Power BI

Learn More

Interface Level Measurement Selection Guide

Interface Level Measurement Selection Guide

Electric Motor Actuator Parts

Electric Motor Actuator Parts

Motor Clock Wise Operation using PLC

CW and CCW Operation of Motor from Same Push button

SCL Language in Siemens Tia Portal

FOR DO Statement in SCL Language

How to Solve Cable Tray Sagging

How to Solve Cable Tray Sagging ?

FBD Logic

Why different PLC Programming Languages were Developed?

Factors to Consider When Choosing Power Tools

Factors to Consider When Choosing Power Tools

vortex flow transmitter

What is a Vortex Flow Meter?

Menu

  • About
  • Privacy Policy
  • Copyright

Quick Links

  • Learn PLC
  • Helping Hand
  • Part Time Job

YouTube Subscribe

Follow US
All rights reserved. Reproduction in whole or in part without written permission is prohibited.
Welcome Back!

Sign in to your account

Username or Email Address
Password

Lost your password?