Inst ToolsInst ToolsInst Tools
  • Ask
  • Courses
  • Videos
  • Q & A
    • Interview
      • Instrumentation
      • Electronics
      • Electrical
      • Practical Questions
    • MCQ
      • Instrumentation MCQ
      • Electrical MCQ
      • Electronics MCQ
      • Control Systems MCQ
      • Analog Electronics MCQ
      • Digital Electronics MCQ
      • Power Electronics MCQ
      • Microprocessor MCQ
      • Multiple Choice Questions
  • EE
    • Electronics
      • Electronics Q & A
      • Electronic Basics
      • Electronic Devices & Circuits
      • Electronics Animation
      • Digital Electronics
    • Electrical
      • Electrical Basics
      • Electrical Q & A
      • Power Electronics
      • Electrical Machines
      • Electrical Animation
      • Power Systems
      • Switchgear & Protection
      • Transmission & Distribution
  • Measure
    • Control Valves
    • Calibration
    • Temperature
    • Pressure
    • Flow
    • Level
    • Analyzers
    • Switches
    • Vibration
    • Solenoid Valve
  • Control
    • PLC Tutorials
    • Control Systems
    • Safety Instrumented System (SIS)
    • Communication
    • Fire & Gas System
  • More
    • Design
    • Tools
    • Animation
    • Basics
    • Formulas
    • Standards
    • TextBooks
    • Common
    • Software
    • Excel Tools
    • Erection & Commissioning
    • Process Fundamentals
    • Videos
    • Books
Search
All rights reserved. Reproduction in whole or in part without written permission is prohibited.
Reading: Orifice Sizing Guidelines and Thumb Rules with Flowchart
Share
Notification Show More
Font ResizerAa
Inst ToolsInst Tools
Font ResizerAa
  • Courses
  • PLC Tutorials
  • Control Systems
Search
  • Ask
  • Courses
  • Videos
  • Q & A
    • Interview
    • MCQ
  • EE
    • Electronics
    • Electrical
  • Measure
    • Control Valves
    • Calibration
    • Temperature
    • Pressure
    • Flow
    • Level
    • Analyzers
    • Switches
    • Vibration
    • Solenoid Valve
  • Control
    • PLC Tutorials
    • Control Systems
    • Safety Instrumented System (SIS)
    • Communication
    • Fire & Gas System
  • More
    • Design
    • Tools
    • Animation
    • Basics
    • Formulas
    • Standards
    • TextBooks
    • Common
    • Software
    • Excel Tools
    • Erection & Commissioning
    • Process Fundamentals
    • Videos
    • Books
Follow US
All rights reserved. Reproduction in whole or in part without written permission is prohibited.
Inst Tools > Blog > Flow Measurement > Orifice Sizing Guidelines and Thumb Rules with Flowchart

Orifice Sizing Guidelines and Thumb Rules with Flowchart

Here we shared the brief details of orifice sizing guidelines and a simple flowchart with basic thumb rules during the design and selection.

Last updated: February 21, 2023 3:06 pm
Jatin Katrodiya
Flow Measurement Instrumentation Design
No Comments
Share
5 Min Read
SHARE

Here we shared the brief details of orifice sizing guidelines and a simple flowchart with basic thumb rules during the design and selection.

Contents
Orifice Sizing GuidelinesThumb Rules for Orifice Sizing

Orifice Sizing Guidelines

Follow the below-mentioned summary about orifice selection and sizing.

Check Sizing Standard: ISO 5167; AGA Report No-3; MFC-14M

Orifice Flange standard: ASME B 16.36.

For 2″ lines and above: Orifice plates with flanges can be used.

Integral Orifice: For line sizes equal to / less than 1.5″

D-D/2 tapping to be used for size >14″, Flanged tapping <=14” line size

Flow rangeability: 1:4 ( for closed loops) and 1:5 (for open loops) for orifice

Example – Max flow condition is 45000 Nm/hr; Min flow condition is 10000 Nm3/hr

Then rangeability is 45000/10000 = 4.5 So the orifice can be used for rangeability 5 and below.

Where flow rangeability is between 5:1 to 10:1, Dual Differential pressure transmitters are preferred for better accuracy.

The orifice plate square-edge concentric by default choice.

Quadrant edge for services with low Reynolds e.g. <10000

Conical entrance orifice for services with low Reynolds e.g. <2000

Eccentric / Segmental type of orifice plates shall be used for specific applications

Eccentric type – where fluids carry the gases and Gases carry the liquids

Segmental type – Light slurries or fluid with a high concentration of solids

Conditional Orifice Plates with multi-holes are to be used for special cases if required.

Example – Straight length can not comply

Consider Straight Length as per Max 0.7 β case from ISO 5167 table 3

Drain/Vent hole applicable d>=25.4 mm

Bore diameter d>=12.5 mm for flow orifice

Plate thickness t <=0.05D, typically 3 mm

MOC of Orifice Flange as per PMS, MOC of Plate as SS316 or higher as per PMS

Always pay attention to Pressure and Temperature compensation for Gas flow measurement.

Thumb Rules for Orifice Sizing

Orifice Plate Sizing

Flow across the orifice is proportional to the Sqrt of differential pressure across the orifice plate.

Lower β will have a higher pressure drop across the orifice because the orifice hole is small

Higher β will have a lower pressure drop across the orifice because the orifice hole is bigger. Sometimes it is difficult to measure lower differential pressure by DP Transmitter (e.g. 30 mmH2O)

At Lower DP conditions (e.g. min flow case) the transmitter accuracy is lower. Refer to the DP Transmitter catalogs for further readings.

A higher DP range for Transmitter is preferred because it will have better accuracy, but it will have higher pressure drops across the orifice. Hence there is always a trade-off for selecting a calibration range to satisfy accuracy and PPL (permanent pressure loss).

Permanent pressure loss is proportional to calibrated DP. Higher the calibrated DP, Higher the PPL (which may not be acceptable to process sometimes). In general, the allowable permanent pressure drop across is 0.1 to 0.2 bar.

Approximate PPL at Calibrated condition = (1 – β^1.9)*differential pressure Calibrated

Approximate PPL at Actual condition = (1 – β^1.9)*differential pressure actual.

Most DP transmitter has a rangeability of 100:1 which results in a flow rangeability of 10:1 [Sqrt(100)].

Furthermore, the initial 10% of DP transmitter readings are more erroneous. So Practically DP Transmitter’s usable rangeability is 100% (Max):10% (min) which equals 10:1 so the flow rangeability comes to around 3.16:1, so in industry, the orifice is used for flow rangeability up to 5:1, this is a conservative design.

Where minimum flow condition or turndown case is not so important, the orifice can be used/selected up to 10:1 flow rangeability.

It is advised to know all your project specification requirements to kick-start the sizing of the flow orifice. The most stringent requirement has to be respected (e.g. β is allowed in the range of 0.1 to 0.7 for flow orifice as per ISO 5167 part 2. However, some client specifications will have β range of 0.2 to 0.6)

Orifice Sizing Guidelines

Read Next:

  • Flow Meter Calibration
  • Pitot Tube Problems
  • Flow Meter Verification
  • MPFM Working Principle
  • Flow Transmitter Questions
Don't Miss Our Updates
Be the first to get exclusive content straight to your email.
We promise not to spam you. You can unsubscribe at any time.
Invalid email address
You've successfully subscribed !
How do You Select a Pressure sensor?
Thermowell Problems
How to Minimize Water Vapor in Instrument Air Lines?
Hot Wire Anemometer Principle and Types
How O-Ring Failure caused NASA’s shuttle to Blast ?
Share This Article
Facebook Whatsapp Whatsapp LinkedIn Copy Link
Share
Leave a Comment

Leave a Reply Cancel reply

Your email address will not be published. Required fields are marked *

Stay Connected

128.3kFollowersLike
69.1kFollowersFollow
208kSubscribersSubscribe
38kFollowersFollow

Categories

Recent Comments

  • Guifty Shimica on Top Non-PLC Certification Courses for Automation Professionals
  • Guifty Shimica on Top Non-PLC Certification Courses for Automation Professionals
  • MIHARITSOA Aina Sitraka on Top Non-PLC Certification Courses for Automation Professionals
  • Vaishnavi on Free Instrumentation Course for Trainee Engineers

Related Articles

Design Basis for Fire Detection and Alarm System

Design Basis for Fire Detection and Alarm System

Flow Transmitter Output Current Calculation

Calculate Flow Transmitter Output Current

Difference between Orifice & Restriction Orifice

Instrumentation Deliverables Generated from 3D Modeling

Instrumentation Deliverables Generated from 3D Modeling

Advantages and Disadvantages of Flow Measurement Techniques

Advantages & Disadvantages of Different Flow Meters

Transit Time flow meter Theory

Transit Time Flow Meter Principle

Basic Terms used in SIL Verification

Basic Terms used in SIL Verification

Air Cylinder Consumption Calculation for Control Valves

Air Cylinder Consumption Calculation for Control Valves

More Articles

Difference Between Combinational Circuit and Sequential Circuit

Difference Between Combinational and Sequential Circuit

Career Opportunities in Instrumentation Engineering

Job and Career Opportunities in Instrumentation Engineering

RFID Technology in Industrial Automation

RFID Technology in Industrial Automation

radial-vane damper

Dampers and Louvres

Flame Detectors Working Principle

Flame Detectors Working Principle

Snubber Circuits

Thyristor Protection Circuits (SCR) – Types, Principle, Explanation

Effect of Lead Wire Resistance on RTD

Effect of Lead Wire Resistance on RTD