Inst ToolsInst ToolsInst Tools
  • Courses
  • Automation
    • PLC
    • Control System
    • Safety System
    • Communication
    • Fire & Gas System
  • Instrumentation
    • Design
    • Pressure
    • Temperature
    • Flow
    • Level
    • Vibration
    • Analyzer
    • Control Valve
    • Switch
    • Calibration
    • Erection & Commissioning
  • Interview
    • Instrumentation
    • Electrical
    • Electronics
    • Practical
  • Q&A
    • Instrumentation
    • Control System
    • Electrical
    • Electronics
    • Analog Electronics
    • Digital Electronics
    • Power Electronics
    • Microprocessor
  • Request
Search
  • Books
  • Software
  • Projects
  • Process
  • Tools
  • Basics
  • Formula
  • Power Plant
  • Root Cause Analysis
  • Electrical Basics
  • Animation
  • Standards
  • 4-20 mA Course
  • Siemens PLC Course
Reading: Poorly Built Switchgears – Why Breaker Parts Tear apart or don’t work?
Share
Font ResizerAa
Inst ToolsInst Tools
Font ResizerAa
  • Courses
  • Design
  • PLC
  • Interview
  • Control System
Search
  • Courses
  • Automation
    • PLC
    • Control System
    • Safety System
    • Communication
    • Fire & Gas System
  • Instrumentation
    • Design
    • Pressure
    • Temperature
    • Flow
    • Level
    • Vibration
    • Analyzer
    • Control Valve
    • Switch
    • Calibration
    • Erection & Commissioning
  • Interview
    • Instrumentation
    • Electrical
    • Electronics
    • Practical
  • Q&A
    • Instrumentation
    • Control System
    • Electrical
    • Electronics
    • Analog Electronics
    • Digital Electronics
    • Power Electronics
    • Microprocessor
  • Request
Follow US
All rights reserved. Reproduction in whole or in part without written permission is prohibited.
Inst Tools > Blog > Root Cause Analysis (RCA) > Poorly Built Switchgears – Why Breaker Parts Tear apart or don’t work?

Poorly Built Switchgears – Why Breaker Parts Tear apart or don’t work?

Electrical engineering root cause analysis (RCA) related to poorly built Switchgears and Why do breaker parts tear apart or don’t work?

Last updated: September 28, 2022 3:08 pm
S Raghava Chari
Root Cause Analysis (RCA)
No Comments
Share
5 Min Read
SHARE

Electrical engineering root cause analysis (RCA) related to poorly built Switchgears and Why do breaker parts tear apart or don’t work?

Contents
Poorly Built Switchgears ProblemAuthor Root Cause AnalysisWhy Breaker Parts Tear apart or don’t work?Author SolutionResults
Article Type:Root Cause Analysis (RCA)
Category:Electrical
Equipment Type:Bus ducts, Switchgear, Transformers,
Author:S. Raghava Chari

Note: This root cause analysis (RCA) is from real-time scenarios that happened in industries during the tenure of two or three decades ago. These articles will help you to improve your troubleshooting skills and knowledge.

Poorly Built Switchgears Problem

The switchgear – 11 KV, 3.3 KV, and 0.4 KV – based on basic know-how from a reputable collaborator lacking manufacture quality control failed in 10-12 operations.

The breaker vendor ignored the problems and outside repair shops showed no interest. The author took over the problem.

Poorly Built Switchgears
Example Image

Author Root Cause Analysis

Why do breakers fail so often? impacts of operation loosened and tore apart parts and subassemblies in 10-12 operations, resulting in their not making/tripping on protective relay / manual Push Button commands.

Hence, the next level breaker trips 0.4 secs later – the time delay setting. Besides more area electrical outages, the too-long fault current flows damage the failed breaker more.

Why Breaker Parts Tear apart or don’t work?

The moving or slide parts fit up is not the good engineering practice H7d7 running clearance fit-up and the permanently attached parts’ S7/s6 permanent fit.

Hence, the moving / rotating parts wobbled, seized, and the permanently fitted broke loose. Screwdriver slot commercial screws inadequately secured subassemblies worked loose or tore apart.

The breakers did not function as they should because of such several manufacturing defects cumulative effects; hence, the protected motor and transformer, etc. suffered damages. 

Author Solution

The author has taken below given few examples of steps that rendered the breakers near 100% reliable and saved the connected equipment e.g. motor, transformer, etc.

Shop made crank electrical switchgear
  1. Shop made crank (fig 1) machined out of a steel block replaced the spring charging mechanism built up crank – the  often breaking part
  2. Tight fitted S7/s6 bronze bushes (fig 3) to steel parts and the mating parts slid / rotated with just enough play seizure free
  3. Inserted ZZ antifriction bearing (fig 3) at the spring changing mechanism belt driven Al pulley hub for seizure free run and reliable spring charging
  4. Replaced inadequate fasteners with high tensile hex / Allen head fasteners; instead screwing these on to the casing thin walls, secured these with thick nuts. Tack welded the nuts to the casing wall. This way the bolts engaging in several threads resists braker impact shocks and remains ever tight
  5. Substituted 25 mm thick conveyor belt disc absorbs 400 V breaker solenoid plunger hits, unlike the original flimsy shock absorbers, which tore apart in few hits
  6. Silicone Compound coated electrical conductors retained IR values near infinity forever and suffered no short circuit flashovers
  7. And many more similar improvements

The author rebuilt breakers were intact even after 100 shop test on / offs, unlike the originals, which tore apart in 10 or even fewer on / offs.

Results

The mechanical strengthening ensured reliable on/off operations and Silicone Compound (SC) coating freedom from short circuits. i.e. the breakers would trip/make on commands 100% and save their connected equipment. Their field performance too was as good as the shop performance.

Thanks to both,  plant on stream hours and hence production increased. So did the and electricians’ confidence and morale.

Author: S. Raghava Chari

Do you face any similar issues? Share with us through the below comments section.

If you liked this article, then please subscribe to our YouTube Channel for Instrumentation, Electrical, PLC, and SCADA video tutorials.

You can also follow us on Facebook and Twitter to receive daily updates.

Read Next:

  • Insulation Resistance Problems
  • Failing Weigh Feeders and Drives
  • Transformers Coolers Problems
  • Frequent Lightning Arrester Burst
  • 110 KV Connection to Feeder A
Don't Miss Our Updates
Be the first to get exclusive content straight to your email.
We promise not to spam you. You can unsubscribe at any time.
Invalid email address
You've successfully subscribed !

Continue Reading

11 kV, 3.3 kV, and 400 V systems insulation resistance (IR) Problems
Control Valve Passing Problem after Overhauling Job
Seawater Pipeline Spools from day-1 leaks threaten Plant Shutdown
[RCA] Pump Low throughput Eliminated
Heat Exchanger Root Cause Analysis (RCA)
RCA Related to Trip Throttle Valve (TTV)
Share This Article
Facebook Whatsapp Whatsapp LinkedIn Copy Link
Share
Leave a Comment

Leave a Reply Cancel reply

Your email address will not be published. Required fields are marked *

Stay Connected

128.3kFollowersLike
69.1kFollowersFollow
210kSubscribersSubscribe
38kFollowersFollow

Categories

Explore More

CO2 Absorber Corroded Wall Thickness & Weld Building
Many Bucket Elevator Wrecks rob crew morale
Pressure Switch Frozen Screwed Cover Extends the Plant Shutdown
Unreliable Ammonia Flow Transmitter Reading and Problems
HT Motor Problem appears after Disassembly and Reassembly
Industrial Light Fittings and Street Light Poles Corrosion Problems
Ammonia Flash Vessel All Level Instruments Stopped Working
Failed Letdown Valve Shuts down a Urea Plant Several Hours

Keep Learning

Finned Heater Leaks Sealed

Finned Tube Steam Leaks – Root Cause Analysis

Fasteners and General Corrosion of Electrical Motors

Fasteners and General Corrosion of Electrical Motors

Wrongly terminated Thermocouple (TC) wires

Too Low-Temperature Readings after a Failed Thermocouple Change

Ball Valve root cause

Ammonia Feed Ball Valve to Ship Tank Closed

Butterfly Valve Failure caused Fire

Butterfly Valve Failure Caused Serious vicinity Heavy Fire

Surface Condenser Condensate Evacuation Pumps

Condensate Pump Frequent Wrecks Threatens Long Plant Outages

Centrifugal Compressor outage reduced

Centrifugal Compressor Outage Reduced – Root Cause Analysis

Thermocouple Extension Lead Problem

Thermocouple Extension Lead Problem

Learn More

Electrical Ground Loop

How to Solve Electrical Ground Loop Problems?

PLC Program to control level of parallel tanks

Parallel Tanks Level Control using PLC Ladder Diagram Tutorial

Identify Process Variables in P&ID

Identify Process Variables in P&ID

Differential Pressure Sensor for Filtration Monitoring

Differential Pressure Sensor for Filtration Monitoring

Phosphate Dozing System

Phosphate Dozing System Problems

High-Speed and Fast Counters in PLC

What are High-Speed Counters and Fast Counters in PLC?

IPSec

What is IPSec? – Internet Protocol Security

Zone vs Class - Division

Zone vs Class / Division

Menu

  • About
  • Privacy Policy
  • Copyright

Quick Links

  • Learn PLC
  • Helping Hand
  • Part Time Job

YouTube Subscribe

Follow US
All rights reserved. Reproduction in whole or in part without written permission is prohibited.
Welcome Back!

Sign in to your account

Username or Email Address
Password

Lost your password?