A Thermocouple is a sensor used to measure temperature. Thermocouples consist of two wire legs made from different metals. The wires legs are welded together at one end, creating a junction.
This junction is where the temperature is measured. When the junction experiences a change in temperature, a voltage is created. The voltage can then be interpreted using thermocouple reference tables (linked) to calculate the temperature.
There are many types of thermocouples, each with its own unique characteristics in terms of temperature range, durability, vibration resistance, chemical resistance, and application compatibility.
Type J, K, T, & E are “Base Metal” thermocouples, the most common types of thermocouples. Type R, S, and B thermocouples are “Noble Metal” thermocouples, which are used in high temperature applications (see thermocouple temperature ranges.
Thermocouples are used in many industrial, scientific, and OEM applications. They can be found in nearly all industrial markets: Power Generation, Oil/Gas, Pharmaceutical, BioTech, Cement, Paper & Pulp, etc. Thermocouples are also used in everyday appliances like stoves, furnaces, and toasters.
Thermocouples are typically selected because of their low cost, high temperature limits, wide temperature ranges, and durable nature.
Cold, or reference junction, is the end of a thermocouple that provides a reference point.
Thermocouples measure the difference in temperature between two junctions. They do NOT measure actual temperature. The sensing junction is where the thermocouple wires are welded (or otherwise connected) together, and located at a point where the temperature is desired.
The other junction is typically located where it is connected to instrumentation (measuring device or transmitter). This is known as the cold or reference junction.
Thermocouple millivolt tables and mathematical formulas are based on a cold junction temperature of 0°C. To determine actual temperature, the instrumentation must “adjust” for the difference between ambient temperature and 0°C. This adjustment is known as cold junction compensation.
Also Read : Thermocouples Green Rot Effect
A thermocouple is called “grounded” when the sensing junction is connected (physically and electrically) to the metal case.
There are advantages and disadvantages but generally ungrounded thermocouples are preferable, providing a slower response time is acceptable.
First, consider the difference in temperature ranges. Noble Metal Thermocouples can reach 3,100 F, while standard RTDs have a limit of 600 F and extended range RTDs have a limit of 1,100 F.
A plain stem thermocouple is 2 to 3 times less expensive than a plain stem RTD.
A thermocouple head assembly is roughly 50% less expensive than an equivalent RTD head assembly.
As a general rule, RTDs are more accurate than thermocouples. This is especially true at lower temperature ranges.
RTDs are also more stable and have better linearity than thermocouples. If accuracy, linearity, and stability are your primary concerns and your application is within an RTD’s temperature limits, go with the RTD.
In the sensors industry, RTDs are widely regarded as a less durable sensor when compared to thermocouples.
RTDs cannot be grounded. For this reason, they have a slower response time than grounded thermocouples.
Also, thermocouples can be placed inside a smaller diameter sheath than RTDs.
A smaller sheath diameter will increase response time. For example, a grounded thermocouple inside a 1/16” dia.
sheath will have a faster response time than a RTD inside a ¼” dia. sheath
This is the most common junction style. A thermocouple is grounded when both thermocouple wires and the sheath are all welded together to form one junction at the probe tip.
Grounded thermocouples have a very good response time because the thermocouple is making direct contact with the sheath, allowing heat to transfer easily.
A drawback of the grounded thermocouple is that the thermocouple is more susceptible to electrical interference. This is because the sheath often comes into contact with the surrounding area, providing a path for interference.
A thermocouple is ungrounded when the thermocouple wires are welded together but they are insulated from the sheath.
The wires are often separated by mineral insulation.
A thermocouple is exposed when the thermocouple wires are welded together and directly inserted into the process.
The response time is very quick, but exposed thermocouple wires are more prone to corrosion and degradation. Unless your application requires exposed junctions, this style is not recommended.
An ungrounded uncommon thermocouple consists of a dual thermocouple that is insulated from the sheath and each of the elements are insulated from one other.
M.I. (Mineral Insulated) cable is used to insulate thermocouple wires from one another and from the metal sheath that surrounds them.
MI Cable has two (or four when duplex) thermocouple wires running down the middle of the tube.
The tube is then filled with magnesium oxide powder and compacted to ensure the wires are properly insulated and separated.
MI cable helps to protect the thermocouple wire from corrosion and electrical interference.
Also Read : Thermocouple Calibration
A thermocouple can be identified by the color of its wire insulation.
For example, in the United States a type J thermocouple grade wire has one red wire and one white wire, typically with a brown over jacket.
A type J extension grade wire also has one red wire and one white wire, but it has a black over jacket.
As a general rule the red wire of a thermocouple or extension wire is negative and the positive wire is color coded according to the type of thermocouple.
Different countries use different color codes.
Thermocouple grade wire is used to manufacture thermocouple probes.
Thermocouple grade wire is normally used for the junction and inside the stem sheath. This is because the thermocouple grade wire has a better accuracy specification than extension grade wire.
Extension grade wire is a less expensive, lower grade wire. It is used to extend the signal from the thermocouple probe to the control system or digital display.
Extension grade wire is more economical due to a lesser grade metal being used.
Extension grade wire should not be used in the process itself and should not see the temperature extremes & temperature cycling as standard grade wire.
When two wires of different metals or metal alloys (thermo wires) are joined together in one end (hot junction), a thermocouple is formed.
If there is a temperature difference between the hot junction and the open ends, a thermal electromotive force (a thermal voltage) is created in the thermocouple. This is also called the Seebeck effect.
A thermocouple measurement always needs information from joined wire end (hot junction) and open wire end (cold junction). The cold junction is also called reference point.
Variations of reference point temperature are compensated with CJC measuring (Cold Junction Compensation).
Temperature transmitters CJC measuring can be an internal function or a measuring resistor integrated in connectors.
If the reference point is far away from the transmitter, a separate temperature measuring of that point has to be implemented and wired to transmitter as compensation signal.
Compensating cable is a thermocouple measuring circuit cable, which is identified by the letter C (e.g. for type K cable KC).
Wires of the compensating cable have the same electrical features, but not the same materials, as the thermo wires of the TC sensor.
Compensating cable is a more cost effective solution than extension cable, but the maximum ambient temperature allowed is lower, approximately 100…200 °C depending on the insulation material.
Extension cable is a thermocouple cable which is identified by the letter X (e.g. for type K cable KX). Wires of the extension cable are of exactly the same materials as the thermo wires of the TC sensor.
These cables can achieve even the same ambient temperatures as the thermocouple can.
Trace heating is a term usually used for keeping pipelines and attached devices unfrozen.
The important function of trace heating is maintaining stable temperature and flow rate of the materials flowing through the pipeline.
The most common implementation of trace heating is electrical, which offers good adjustability.
However, for accurate process control and adjustment also precise temperature data is needed.
For these applications we have designed our high quality trace heating sensors, which already have been available for years, also for Ex applications.
Based on the design of your system you need to know:
Once those are established then you’re ready to consult ASME standard PTC 19.3 TW-2010 Thermowell section, which goes through the calculation for the design of the well.
Here are some basic rules you can follow*:
A Pyrometer is a non-contacting device that intercepts and measures thermal radiations.
Without making any contact with the radiating body and the process is known as pyrometry. This device is useful for determining the temperature of an object’s surface.
Pyrometer strictly works on the principle of black body radiation. Here emissivity of the target plays an important role, as it governs how bright the target appears to the pyrometer.
Due to its high accuracy, speed, economy and specific advantages, it is widely being used as a standard procedure in many industrial applications.
Working:
An exposed (measuring) junction is recommended for the measurement of flowing or static non-corrosive gas temperature when the greatest sensitivity and quickest response is required.
An insulated junction is more suitable for corrosive media although the thermal response is slower.
In some applications where more than one thermocouple connects to the associated instrumentation, insulation may be essential to avoid spurious signals occurring in the measuring circuits. If not specified, this is the standard.
An earthed (grounded) junction is also suitable for corrosive media and for high pressure applications.
It provides faster response than the insulated junction and protection not offered by the exposed junction.
Also Read : Thermocouples Connector & Tip styles
Thermowells provide protection for temperature probes against unfavorable operating conditions such as corrosive media, physical impact (e.g. clinker in furnaces) and high pressure gas or liquid.
Their use also permits quick and easy probe interchanging without the need to “open-up” the process.
The main application areas are:
One-piece Thermowells are suited to the highest process loads, depending on their design. Thus in the petrochemical industry, one-piece thermocouples are now used almost exclusively.
There are two types of thermocouple construction used most commonly.
These are Mineral Insulated (M.I.) Thermocouples & Non M.I. Thermocouples.
Magnesium Oxide insulated thermocouples, are used in many process and laboratory applications.
They are rugged in nature and bendable, and their fairly high temperature ratings make MgO thermocouples a popular choice for a multitude of temperature measuring applications.
MgO sensors are constructed by placing an element or elements into a sheath of a suitable material and size, insulating the elements from themselves and the sheath with loose filled or crushable Magnesium Oxide powder or insulators, and then swaging or drawing the filled sheath down to its final reduced size.
The swaging process produces an element with highly compacted MgO insulation and provides high dielectric strength insulation between the elements themselves and their sheath.
Mineral insulated Thermocouples consist of thermocouple wire embedded in a densely packed refractory oxide powder insulate all enclosed in a seamless, drawn metal sheath (usually stainless steel).
At one end cores and sheath are welded from a “hot” junction. At the other end, the thermocouple is connected to a “transition” of extension wires, connecting head or connector.
In Non-M.I. thermocouples, thermocouple wires are either insulated with ceramic beads or after insulation of ceramic, covered by a metal sheath (usually stainless steel) and some form of termination (extension lead, connecting head or connector for example) is provided.
In this type of construction thermocouple wires are protected from the measuring environment when a sheath protection is provided.
The sheath material is dependent on the measuring environment usually stainless steel is used. According to the corrosive environment sheath selection is changed.
This construction does not provide flexibility & not found in small sizes. Not too good mechanical strength.
In Non M.I. construction sheath may be of ceramic or metal as per suitability.
Exposed, Grounded and Ungrounded all types of junctions are formed in both the M.I, & Non M.I. construction.
Tolerance denotes the maximum allowable value obtained by subtracting the temperature reading or the temperature at the hot junction from the standard temperature converted from the applicable temperature EMF table.
Operating temperature limit means the upper temperature where thermocouple can be used continuously in air.
Maximum limit means the upper temperature where thermocouple can be used temporarily for short period of time owing to unavoidable circumstances.
Principal factors that affect the life of a thermocouple are:
The response time for a thermocouple is usually defined as the time taken for the thermal voltage (output) to reach 63% of maximum for the step change temperature.
It is dependent on several parameters including the thermocouple dimension, construction, tip configuration and the nature of the medium in which the sensor is located.
Thermocouple assemblies are” tip” sensing devices which lend them to both surface and immersion applications depending on their construction.
However immersion type must be used carefully to avoid error due to stema conduction from the process which can result in a high or low reading respectively.
A general rule is to immerse into the medium to a minimum of 4 times the outside diameter of them sheath; no quantitative data applies but care must be exercised in order to obtain meaningful results.
Although thermocouple assemblies are primarily tip sensing devices, the use of protection tubes renders surface sensing impractical.
Physically, the probe does not lend itself to surface presentation and steam conduction would cause reading errors.
If thermocouple is to be used reliably for surface sensing, it must be either exposed, welded junction from with very small thermal mass or be housed in a construction, which permits true surface contact when attaching to the surface.
The following are the different thermowell tip profiles :
The outside diameter decreases gradually along the immersion length. Used for high velocity applications.
It one end has flat surface. Used in low pressure applications or where flow characteristics around the thermowell are not important.
Because a thermocouple measures in wide temperature ranges and can be relatively rugged, thermocouples are very often used in industry.
The following criteria are used in selecting a thermocouple:
A time constant has been defined as the time required by a sensor to reach 63.2% of a step change in temperature under a specified set of conditions.
Five time constants are required for the sensor to approach 100% of the step change value. An exposed junction thermocouple offers the fastest response.
Also, the smaller the probe sheath diameter, the faster the response, but the maximum temperature may be lower.
Be aware, however, that sometimes the probe sheath cannot withstand the full temperature range of the thermocouple type.
Download : Thermocouple Calculator
You have to consider the characteristics and costs of the various sensors as well as the available instrumentation.
In addition, Thermocouples generally can measure temperatures over wide temperature ranges, inexpensively, and are very rugged, but they are not as accurate or stable as RTD’s and thermistors.
RTD’s are stable and have a fairly wide temperature range, but are not as rugged and inexpensive as thermocouples.
Since they require the use of electric current to make measurements, RTD’s are subject to inaccuracies from self-heating.
Thermistors tend to be more accurate than RTD’s or thermocouples, but they have a much more limited temperature range. They are also subject to selfheating.
Infrared Sensors can be used to measure temperatures higher than any of the other devices and do so without direct contact with the surfaces being measured.
However, they are generally not as accurate and are sensitive to surface radiation efficiency (or more precisely, surface emissivity).
Using fiber optic cables, they can measure surfaces that are not within a direct line of sight.
Thermocouples are available in different combinations of metals or calibrations. The most common are the “Base Metal” thermocouples known as Types J, K, T, E and N.
There are also high temperature calibrations – als known as Noble Metal thermocouples – Types R, S, C and GB.
K Type Thermocouples are known as general purpose thermocouple due to its low cost and temperature range.
This high temperature wire/thermocouple is produced using a wide range of materials, and is available with PVC, FEP, TFE, PFA, Fiberglass, and Ceramaflex insulation.
However, if you see it referenced by “type” on a spec sheet, the description is referring to the kind of metal alloy used for the wire’s conductor:
When an “X” follows the letter indicating which alloy was used in the cable, the cable is extension grade.
In these cases, the types of cable are listed as Type EX, Type JX, Type KX, Type NX, or Type TX.
Common Thermocouple Temperature Ranges | |||
Calibration | Temperature Range | Standard Limits of Error | Special Limits of Error |
---|---|---|---|
J | 0° to 750°C (32° to 1382°F) | Greater of 2.2°C or 0.75% | Greater of 1.1°C or 0.4% |
K | -200° to 1250°C (-328° to 2282°F) | Greater of 2.2°C or 0.75% | Greater of 1.1°C or 0.4% |
E | -200° to 900°C (-328° to 1652°F) | Greater of 1.7°C or 0.5% | Greater of 1.0°C or 0.4% |
T | -250° to 350°C (-328° to 662°F) | Greater of 1.0°C or 0.75% | Greater of 0.5°C or 0.4% |
This wire that is used to make the sensing point of the instrument, where extension grade wire is only used to extend a thermocouple signal from a probe back to the instrument reading the signal.
The various sheath materials are dependent upon the application.
The following list will help you make the best selection:
Learn an example PLC program to control a pump based on level sensors using ladder…
In the PLC timer application for security camera recording, when motion is detected then camera…
In this example, we will learn batch mixing with PLC ladder logic program using timer…
This PLC example on manufacturing line assembly is an intermediate-level PLC program prepared for the…
In this article, you will learn the PLC programming example with pushbutton and motor control…
This article teaches how to convert Boolean logic to PLC programming ladder logic with the…