Instrumentation engineering root cause analysis of seal pressure instruments, gauges, transmitter, switches, and DP transmitters.
Article Type: | Root Cause Analysis (RCA) |
Category: | Instrumentation |
Equipment Type: | Sensors |
Author: | S. Raghava Chari |
Note: This root cause analysis (RCA) is from real-time scenarios that happened in industries during the tenure of two or three decades ago. These articles will help you to improve your troubleshooting skills and knowledge.
The abbreviation SPI covers Seal Pressure Gauges (PG), Pressure Transmitter (PT) and Pressure Switches (PS) and SDPT for Seal Differential Pressure Flow and Level Transmitters.
Body Type Seals (BTS fig 2) common for pipeline flowing ambient temp congealing liquids pressure measuring and flanged seals (FS fig 3) fitted SPI for vessels. Few such liquids examples are coal tar, molten sulfur, urea melt etc.
Such liquids stagnating in the process leads to the instruments attain ambient temperatures and solidify. Hence the instruments don’t read. Hence, the seals.
Seal details follow:
A BTS (fig 2) consists of seal body with a factory welded 0.015 mm thick diaphragm (D). A PG or other PI either directly screws on to seal body (SB) top, or capillary connects to it. BTSs of process compatible materials are available.
The factory evacuates the assembly and fills with silicone or other oils. SB bolts on welded to pipeline weldolet (W).
Suitable gasket e.g. serrated 3 mm thick SS 316 ring makes the installation leak tight.Field crew bolts the BTS to W with factory supplied special high tensile Allen screws. Commercial studs and nuts are unsuitable
Fig 2 shows that the seal body extends into the pipe bore, where hot flowing process liquid always remains liquid and hence exerts pressure on the diaphragm.
The oil fill communicates the line pressure to the top mounted PI/PG/PS for reliable and failure free readings.
On the other hand, had we installed the instrument conventionally, the liquid would stagnate in the lead to the instrument, eventually cool down to ambient temp, freeze the instrument would not read the pressure.
Flanged Seal (FS) (fig 3) essentially works the same way, a diaphragm welded to a 1” RF flange of process suitable rating and material replaces the SB and bolts to the pipeline short nozzle flange (fig 3)
Though the seal instruments do fine in other Urea Processes, unfortunately they did not in a Total Recycle Process Urea Plant. The process engineers to whom I pointed out this did not take it seriously and apply their minds.
Faced problems are:
The author tried different solutions as mentioned below.
The SPIs with ½ mm thick PTFE barriers discs to prevent process fluid wetting the diaphragms calibrated well; however the diaphragms pinholes forming persisted as before; hence the problems too.
A. Diaphragm Sandwiched Between a PTFE Gasket and Seal Body Bottom Screwed Cover (Fig 3):
This too shop calibrated well; however, the well wrench and cheater tightened screwed cover was so loose after calibration that crew hand unscrewed the cover.
Since, no other gasket is suitable the author discarded it.
B. Weld New Diaphragm to the Body
The author guided workshop crew successfully argon arc welded the thin diaphragm to SB’s as under:
Connect the readied seal instrument as in fig 4 using 6-mm metal / nylon tubes. Close needle Valve V‑2 and open V‑1.
Start the pump. The initial rapid bubbling in the oil would reduce to 3‑5 bubbles / mt in about 1-minute.
Otherwise, one or more leaky joints lets air in. Identify and correct. Hold 4-5 bubble rates for about 5 minutes. Evacuation is adequate Close V‑1 and open V-2. Atmospheric pressure oil fills the SPI completely.
Apply 50 mm air pressure via V-2 for double sure fill. Carefully disconnect FP and plug it taking care to avoid spill. Wipe and solvent clean plug area. Apply epoxy or other seal as abundant leak prevention measure.
This method of restoring the failed instruments saved over Rs. 10 million per annum by way of no purchase of numerous of new assemblies.
However, poor diaphragm lives still plagued the plant necessitating the Author inventing No Diaphragm Seal Instruments (NDSI) – the ultimate solution!
Below listed steps convert diaphragm seals into No Diaphragm Seals (NDS)
‘new ideas objectors’ objections, that the oil would color the product urea and build market resistance. They had no answers to the author’s query what happens to the several tens of the feed CO2 compressor liters of lube oil / day that go into the reactor.
The NDSI worked fine and astounded everybody.
However, the author removed the finely working NDSI two months later for evaluation. Condensate fill surprised him.
An operator explained, “Sir, we condensate wash the pipelines before plant start and after plant shutdown (SD). The heavier condensate displaces the lighter oil; hence the condensate fill you see”.
The author complemented him and profusely thanked him. But for his clarification, the seen condensate fill would have bothered the author; it would have even delayed large scale SPI trials. He realized that in this case, urea melt / carbomate dissolves in the condensate till saturation.
The saturated solution does not congeal even at ambient temperature. The fill conveys the hot process liquid exerted pressure to the PI/PT/PS/PS sensing element.
Hence, condensate fill is the best, as it satisfies the objectors and saves oil costs.
SB modified according to fig 6 works fine. to the weldolet elbow facing up. Fill condensate via the elbow till it overflows. Screw in the PI/PT/PS.
Thus all PIs/PTs/PSs, indications, control, alarms and shutdowns lasted failure free forever;
The plant saved around Rs 10 million yearly (1980s figures) instrument import bills, avoided risky plant runs, enhanced plant safety and consequently operator morale, not expressible as money.
Convert flanged seals into No Diaphragm Flanged Seals (NDFS) according to fig 7 to get rid of flanged seals problems. Fill condensate and screw in PI/PT/PS as in other seals.
Fill condensate, bolt the NDFS instrument assembly to vessel nozzle flange as before, and enjoy years of trouble-free services.
(Fig 8): while writing this article the below described PNDS flashed to the author:
Remove the pinholes developed diaphragm from seal body and modify according to fig 8.
Machine SS piston for 0.5 mm clearance with the 0.4µm RMS smooth finished bore and fit PTFE filled rope packing in the piston groove.
Fill viscous oil above piston. Screw in PI/PT/PS/PG to the seal body. Piston seal instrument is ready for use.
Readers can make flanged PNDS also along these lines.
Piston No-Diaphragm Seals (PNDS) foreseen advantages as follows:
Since, the author is no longer in service, he requests seal PI/PT/PS/PG problems overwhelmed readers to try out the piston seal and pass on feedback to him.
The author is sure of its success after identifying and removing ‘bugs’ if any seen.
Author: S. Raghava Chari
Do you face any similar issues? Share with us through the below comments section.
If you liked this article, then please subscribe to our YouTube Channel for Instrumentation, Electrical, PLC, and SCADA video tutorials.
You can also follow us on Facebook and Twitter to receive daily updates.
Read Next:
Learn an example PLC program to control a pump based on level sensors using ladder…
In the PLC timer application for security camera recording, when motion is detected then camera…
In this example, we will learn batch mixing with PLC ladder logic program using timer…
This PLC example on manufacturing line assembly is an intermediate-level PLC program prepared for the…
In this article, you will learn the PLC programming example with pushbutton and motor control…
This article teaches how to convert Boolean logic to PLC programming ladder logic with the…