In Boiler, the Draft Plays an Important role. If the Draft of the Boiler Furnace is not Control Properly there are the Chances of Back firing and also the heat can be realised from chimney without its proper use gage these will reduce a boiler efficiency.
Consider the DP transmitter LRV and URV as follows.
LRV= +50
URV=-50
Then the Transmitter will Scale itself for 4-20 mA such that if we will receive 4 mA it will show +50 process Value and 20 mA shows -50 process value.
Details Explanation:
Analog Out from DCS, ID Fan Speed: 0 – 980 RPM (4 – 20 mA)
Analog Input to DCS, Speed Feedback of VFD: 0 – 980 RPM (4 – 20 mA)
So let’s start for the implementation of Program in DCS using function block diagram (FBD).
This DCS program is to Maintain Draft of the Boiler Furnace, along with program explanation and run time test cases.
List of Inputs and Outputs
ADDRESS Description Signal Type
00(02-06) ID Fan Start/Stop Command DO
07(02-00) ID Fan RPM Command AO
00(02-00) ID Fan RPM Feedback AI
Fig. No. (a) Input assigning
Fig. (b) Output Assigning
Fig No. 1.0 PID Block with Library
Fig No. 1.1 PID Blocks in DCS Software
Author: Amit Jadhav
In the PLC timer application for security camera recording, when motion is detected then camera…
In this example, we will learn batch mixing with PLC ladder logic program using timer…
This PLC example on manufacturing line assembly is an intermediate-level PLC program prepared for the…
In this article, you will learn the PLC programming example with pushbutton and motor control…
This article teaches how to convert Boolean logic to PLC programming ladder logic with the…
In this article, you will learn the PLC programming example on timers function block using…
View Comments
what is the simulation software used?