Inst ToolsInst ToolsInst Tools
  • Courses
  • Videos
  • Q & A
    • Interview
      • Instrumentation
      • Electronics
      • Electrical
      • Practical Questions
    • MCQ
      • Instrumentation MCQ
      • Electrical MCQ
      • Electronics MCQ
      • Control Systems MCQ
      • Analog Electronics MCQ
      • Digital Electronics MCQ
      • Power Electronics MCQ
      • Microprocessor MCQ
      • Multiple Choice Questions
  • EE
    • Electronics
      • Electronics Q & A
      • Electronic Basics
      • Electronic Devices & Circuits
      • Electronics Animation
      • Digital Electronics
    • Electrical
      • Electrical Basics
      • Electrical Q & A
      • Power Electronics
      • Electrical Machines
      • Electrical Animation
      • Power Systems
      • Switchgear & Protection
      • Transmission & Distribution
  • Measure
    • Control Valves
    • Calibration
    • Temperature
    • Pressure
    • Flow
    • Level
    • Analyzers
    • Switches
    • Vibration
    • Solenoid Valve
  • Control
    • PLC Tutorials
    • Control Systems
    • Safety Instrumented System (SIS)
    • Communication
    • Fire & Gas System
  • More
    • Design
    • Tools
    • Animation
    • Basics
    • Formulas
    • Standards
    • TextBooks
    • Common
    • Software
    • Excel Tools
    • Erection & Commissioning
    • Process Fundamentals
    • Videos
    • Books
Search
All rights reserved. Reproduction in whole or in part without written permission is prohibited.
Reading: Calibration of Temperature Sensor with Indicator
Share
Notification Show More
Font ResizerAa
Inst ToolsInst Tools
Font ResizerAa
  • Courses
  • PLC Tutorials
  • Control Systems
Search
  • Courses
  • Videos
  • Q & A
    • Interview
    • MCQ
  • EE
    • Electronics
    • Electrical
  • Measure
    • Control Valves
    • Calibration
    • Temperature
    • Pressure
    • Flow
    • Level
    • Analyzers
    • Switches
    • Vibration
    • Solenoid Valve
  • Control
    • PLC Tutorials
    • Control Systems
    • Safety Instrumented System (SIS)
    • Communication
    • Fire & Gas System
  • More
    • Design
    • Tools
    • Animation
    • Basics
    • Formulas
    • Standards
    • TextBooks
    • Common
    • Software
    • Excel Tools
    • Erection & Commissioning
    • Process Fundamentals
    • Videos
    • Books
Follow US
All rights reserved. Reproduction in whole or in part without written permission is prohibited.
Inst Tools > Blog > Calibration > Calibration of Temperature Sensor with Indicator

Calibration of Temperature Sensor with Indicator

Learn the calibration of the temperature sensor with an Indicator with a temperature bath, master sensor, and multi-function calibrator.

Last updated: September 28, 2022 3:24 pm
Saurabh Vaidya
Calibration Temperature Measurement
No Comments
Share
5 Min Read
SHARE

Learn the calibration of the temperature sensor with an Indicator with a temperature bath, master sensor, and multi-function calibrator.

Temperature Sensor is broadly classified as RTD Sensor and Thermocouple Sensor.

RTD Sensor is further classified as 2wire, 3wire and 4 wire RTD Sensor

Thermocouple Sensor is further classified as Type – B, E, J, K, N, R, S, and T.

Temperature Sensor is connected to Temperature Indicator to display Temperature directly in Units of Temperature i.e. Degree Celsius, Kelvin, Fahrenheit.

This calibration procedure can be used for either RTD or thermocouple calibration and validation.

Calibration of Temperature Sensor

Calibration of Temperature Sensor with Indicator

The below 10 steps will help you to calibrate your temperature sensor using a temperature bath and a master sensor.

Step 1:

Select the suitable Temperature Bath (Source) for Calibration of Temperature Sensor with Indicator. The temperature sensor to be calibrated is called Unit Under Calibration (UUC).

Let’s choose a temperature bath for our calibration.

Even if Temperature Bath has its own Temperature Indicator/display, it cannot be used as a master for Calibration. It is used as the only source, i.e. only to generate and read the temperature in the bath.

Another calibrated RTD Sensor or Thermocouple is used for Calibration and this is called a Master sensor.

Temperature Bath is selected according to the range of Temperature Sensor.

Step 2:

Insert the Temperature Sensor which is to be calibrated into the temperature bath.

In this article, we considered the temperature sensor to be calibrated to have an inbuilt temperature indicator or display. We use this indicator to note down the temperature readings during the calibration. If the temperature sensor does not have an inbuilt indicator then we have to connect a multi-function calibrator to read the temperature readings.

Insert the master RTD Sensor/Thermocouple into another slot of the same Temperature Bath.

Connect a calibrated multi-function calibrator to this master sensor to read the sensor output in temperature units like deg C. (as we don’t have an inbuilt indicator in our master sensor we need to connect a device to read the temperature readings)

Make sure to insert the above two sensors at equal depth to have the ideal effects of the generated temperature.

If you don’t have a multi-function calibrator then you can use calibrated multimeters. Note down the output and do the conversion to temperature using RTD or thermocouple standard temperature tables.

Step 3:

Decide the calibration points of the Temperature Sensor before starting the actual calibration.

For example, I want to do calibration at these points 50 deg c, 75 deg C, 100 deg C, 125 deg C, and 150 deg C.

Step 4:

Set the required setpoint in the temperature bath.

Allow the temperature bath to reach its temperature to the desired setpoint.

Let the bath stabilized at the required temperature.

Step 5:

Note down Master Sensor reading & Temperature Sensor (unit under calibration) with Indicator reading.

As per our example set 50 deg c in the temperature bath, wait 30 seconds, note down master sensor and UUC readings.

Step 6:

Take 5 Readings of each setpoint at the interval of 30 Seconds.

For example, set 50 deg c in the temperature bath, wait 30 seconds, note down master sensor and UUC readings.

Step 7:

If both readings are changing (Master and UUC). Take the average of 5 readings for a single setpoint.

Step 8:

Repeat the above step 4 to step 7 for every setpoint or calibration point.

That means, do the same calibration steps for 75 deg C, 100 deg C, 125 deg C, and 150 deg C setpoints.

Step 9:

After Calibration is completed, set the temperature bath temperature to room temperature.

Step 10:

Switch off the temperature bath after reaching room temperature.

 If the Temperature bath is switched off directly at a setpoint other than room temperature, it loses accuracy, stability, and uniformity.

If you liked this article, then please subscribe to our YouTube Channel for Instrumentation, Electrical, PLC, and SCADA video tutorials.

You can also follow us on Facebook and Twitter to receive daily updates.

Read Next:

  • History of Measurement
  • Calibration Procedure of Voltmeter
  • Different Types of Calibration
  • Magnehelic Gauge Calibration
  • Compare Accuracy and Precision
Don't Miss Our Updates
Be the first to get exclusive content straight to your email.
We promise not to spam you. You can unsubscribe at any time.
Invalid email address
You've successfully subscribed !

Continue Reading

Thermocouple Calibration
Installation and Calibration of Level Transmitter
Temperature Switch Principle
Laws of Thermocouples
How to Calibrate the Eddy Current Conductivity Meter?
Basics of Temperature Switch
Share This Article
Facebook Whatsapp Whatsapp LinkedIn Copy Link
Share
Leave a Comment

Leave a Reply Cancel reply

Your email address will not be published. Required fields are marked *

Stay Connected

128.3kFollowersLike
69.1kFollowersFollow
208kSubscribersSubscribe
38kFollowersFollow

Categories

Explore More

Installation Precautions of Thermocouple and RTD
Seebeck Effect Theory
Impulse Line Pressure Testing Procedure
What is a Three-wire RTD ?
Hybrid Level Measurement Principle, Selection, Installation, Limitations and Calibration
Flow Meter Calibration
Temperature Standards
Why it is important to note As-Found and As-Left data during Calibration?

Keep Learning

Thermocouple Types

Types of Thermocouples

Thermowell Design Guidelines

Stability and Uniformity of Temperature Bath

Stability and Uniformity of Temperature Bath

Infrared Hydrocarbon Gas Detector Calibration Procedure

Infrared Hydrocarbon Gas Detector Calibration Procedure

Smart Transmitter Calibration Tutorial Part 2

Smart Transmitter Calibration Tutorial Part 2

pH sensor calibration procedure

Thermocouple Questions and Answers

Thermocouple Questions and Answers

Instrument Turndown Ratio

Instrument Turndown Ratio

Learn More

What is Switchgear and Electrical Substation?

What is Switchgear and Electrical Substation?

Applications of CNC Machining

Important Applications of Rapid Prototype CNC Machining Services

4-20 mA Conversion Formulas

Standard 4 to 20 mA Conversion Formula

repairs of welding cast refractory lined box over the hot spots

Too often done riskily repaired Roof Hot Spots eliminated forever

What is an Oil Separator in HVAC?

What is an Oil Separator in HVAC?

Dual-beam non-dispersive analyzer

Dual-beam Non-dispersive Analyzer

Codesys function block example

Create a User-Defined Function Block in Codesys

main controller fails

How does a Redundant Controller comes in line when the Main Controller fails?

Follow US
All rights reserved. Reproduction in whole or in part without written permission is prohibited.
Welcome Back!

Sign in to your account

Username or Email Address
Password

Lost your password?