Reading: Thermocouple Calibration
Share
Notification Show More
Font ResizerAa
Inst ToolsInst Tools
Font ResizerAa
  • Courses
  • Design
  • PLC
  • Interview
  • Control System
Search
  • Courses
  • Automation
    • PLC
    • Control System
    • Safety System
    • Communication
    • Fire & Gas System
  • Instrumentation
    • Design
    • Pressure
    • Temperature
    • Flow
    • Level
    • Vibration
    • Analyzer
    • Control Valve
    • Switch
    • Calibration
    • Erection & Commissioning
  • Interview
    • Instrumentation
    • Electrical
    • Electronics
    • Practical
  • Q&A
    • Instrumentation
    • Control System
    • Electrical
    • Electronics
    • Analog Electronics
    • Digital Electronics
    • Power Electronics
    • Microprocessor
Follow US
All rights reserved. Reproduction in whole or in part without written permission is prohibited.
Inst Tools > Blog > Calibration > Thermocouple Calibration

Thermocouple Calibration

Last updated: September 27, 2023 3:20 pm
Editorial Staff
Calibration Temperature Measurement
No Comments
Share
5 Min Read
SHARE

Thermocouples

Thermocouples measure temperature and are used quite often in process controls.

How They Work

When wires of two different thermoelectrically homogeneous materials are joined at one end and placed in a temperature gradient, a thermoelectric voltage (EMF) is observed at the other end. The connection is called the measuring junction.

On all thermocouples, the red lead is negative. The color of the other wire indicates the thermocouple type.

For example, on a J-type thermocouple, the positive wire is white. Tables for each type of thermocouple list the voltages produced at various temperatures.

Thermocouples should be checked whenever there are indications that the output is not accurate.

It may also be necessary to check a thermocouple that will be used for a measurement standard.

Input and Output Measurement Standards

A temperature bath provides controlled temperatures for testing a sensor. A well in the temperature bath is used to hold the sensor during the accuracy check.

Another well is used to hold a measurement standard thermometer, it is used to confirm the actual bath temperature.

A second measurement standard thermometer is used to read the ambient temperature at the reference junction.

The sensor output signal and ranges determine the thermocouple output measurement standard.

Since the output is measured in millivolts, a millivolt meter is used to read the output.

Connections

Set up the temperature bath as a temperature input standard to the thermocouple.

Select the output standard with the appropriate range for reading millivolts.

Connect the red lead to the negative millivolt meter input and the white lead to the positive millivolt meter input.

Three Point Checks

Because no adjustments are possible, we can only check the calibration of a thermocouple sensor.

This check is generally done at three test point input values: ambient temperature, mid-range temperature, and upper value of the application range.

Recall that in a thermocouple, it is the difference in the temperature between the reference and the measuring junction that produces a millvoltage output.

Before inserting the thermocouple into the bath, determine the ambient temperature, which represents the temperature at the measuring junction of the thermocouple.

When using look-up tables that are referenced to 0 Deg., you must compensate for ambient temperature.

The millivolt value in the tables for the ambient temperature is added to the value from the sensor.

This compensated millivolt value is used to determine from the tables the correct temperature.

Also Read : Thermocouple Tables for millivolt to Temperature conversion

Thermocouple Transmitters

Calibration of temperature transmitters should be checked on a periodic basis.

Input and Output Measurement Standards

The temperature transmitter discussed here receives an input signal from a thermocouple.

A millivolt input signal will be needed for calibration, so a millivolt source can be used for the input standard.

A milliammeter can be used to measure the transmitter output. Use a standard thermometer to calculate the input signal compensation for the ambient temperature.

Finally, a power supply for the transmitter is necessary.

To calibrate a temperature transmitter with a millivolt meter as an input standard, you must compensate for any reference temperature other than 0 Deg. C ( 32 Deg. F.).

Connections

To make the input connections, the location of the reference junction must first be determined.

When thermocouple wires are used to connect the millivolt source to the transmitter, the reference junction is at the transmitter connection.

So, ambient temperature is measured in the transmitter housing. If copper wires are used, the reference junction is at the connection to the millvolt source, so measure ambient temperature at the millivolt source.

Always observe the polarity of the leads. Connect the negative output from the millivolt source to the positive transmitter terminal.

Connect the milliammeter in series with the transmitter and the power supply.

Setting the Equipment

Adjust the millivolt source and the milliammeter to the proper values as required, turn on equipment and begin calibration.

Five Point Check

Perform a five point check to determine if the transmitter is accurate according to specifications.

Accuracy of the Instrument

Adjust the zero shift first. It should be set with an input value of 10%.

With the zero properly set, a 10% input results in a 10% output. Adjust the span using a 90% input.

The zero and span may interact, check and readjust as required.

Also Read : Thermocouple Interview Questions

Don't Miss Our Updates
Be the first to get exclusive content straight to your email.
We promise not to spam you. You can unsubscribe at any time.
Invalid email address
You've successfully subscribed !

Continue Reading

Resistance Temperature Detectors Working Principle
Thermocouple Temperature Measurement Errors
Selection of Master Instrument for Calibration
What are the Thermocouple Applications?
Difference between Accuracy, Tolerance, Uncertainty, and Error
Basics of Calibration
Share This Article
Facebook Whatsapp Whatsapp LinkedIn Copy Link
Share
Leave a Comment

Leave a Reply Cancel reply

Your email address will not be published. Required fields are marked *

Stay Connected

128.3kFollowersLike
69.1kFollowersFollow
210kSubscribersSubscribe
38kFollowersFollow

Categories

Explore More

Smart Transmitter Calibration Tutorial Part 1
Calibration of Temperature Sensor with Indicator
Instruments Calibration Procedures
How to Commission WirelessHART Transmitter With Gateway
How to Calibrate Load Cells in Weighing Applications?
Non-contact Pyrometers Characteristics
Effect of Lead Wire Resistance on RTD
Transmitter Calibration Procedure

Keep Learning

Capacitance-Level-Transmitter

Capacitance Level Switch Calibration

Use of Temperature Transmitters instead of Direct Wiring

Optical Pyrometer

Optical Pyrometer Working Principle

Resistance Temperature Detectors Errors

Resistance Temperature Detectors (RTD) Sources of Error

H & B Gas Analyzer Principle and Calibration Procedure

Differential Pressure Transmitter Manifold

Field Instrument Calibration Errors

Magnetostrictive Level Transmitter Calibration

Magnetostrictive Level Transmitter Calibration Procedure

Temperature Calibration Bath

Temperature Calibration Bath Principle

Learn More

IP Address Change in Simatic

PLC Configuration of Profinet I/O System

Time Response Analysis

Performance Indices

Digital Control Systems

The Z-Transform

harmonics-effect-on-transformer

Harmonics effect on Transformer

What is Shielded Twisted Pair Cable

What is Shielded Twisted Pair Cable? – Advantages, Disadvantages

Shift Bit Register in PLC

Shift Bit Register in PLC

Digital Transducers Objective Questions

Digital Transducers Objective Questions

Radiation Level Measurement Principle

Radiation Level Measurement

Menu

  • About
  • Privacy Policy
  • Copyright

Quick Links

  • Learn PLC
  • Helping Hand
  • Part Time Job

YouTube Subscribe

Follow US
All rights reserved. Reproduction in whole or in part without written permission is prohibited.
Welcome Back!

Sign in to your account

Username or Email Address
Password

Lost your password?