Inst ToolsInst ToolsInst Tools
  • Ask
  • Courses
  • Videos
  • Q & A
    • Interview
      • Instrumentation
      • Electronics
      • Electrical
      • Practical Questions
    • MCQ
      • Instrumentation MCQ
      • Electrical MCQ
      • Electronics MCQ
      • Control Systems MCQ
      • Analog Electronics MCQ
      • Digital Electronics MCQ
      • Power Electronics MCQ
      • Microprocessor MCQ
      • Multiple Choice Questions
  • EE
    • Electronics
      • Electronics Q & A
      • Electronic Basics
      • Electronic Devices & Circuits
      • Electronics Animation
      • Digital Electronics
    • Electrical
      • Electrical Basics
      • Electrical Q & A
      • Power Electronics
      • Electrical Machines
      • Electrical Animation
      • Power Systems
      • Switchgear & Protection
      • Transmission & Distribution
  • Measure
    • Control Valves
    • Calibration
    • Temperature
    • Pressure
    • Flow
    • Level
    • Analyzers
    • Switches
    • Vibration
    • Solenoid Valve
  • Control
    • PLC Tutorials
    • Control Systems
    • Safety Instrumented System (SIS)
    • Communication
    • Fire & Gas System
  • More
    • Design
    • Tools
    • Animation
    • Basics
    • Formulas
    • Standards
    • TextBooks
    • Common
    • Software
    • Excel Tools
    • Erection & Commissioning
    • Process Fundamentals
    • Videos
    • Books
Search
All rights reserved. Reproduction in whole or in part without written permission is prohibited.
Reading: Solenoid-controlled Valve Problem
Share
Notification Show More
Font ResizerAa
Inst ToolsInst Tools
Font ResizerAa
  • Courses
  • PLC Tutorials
  • Control Systems
Search
  • Ask
  • Courses
  • Videos
  • Q & A
    • Interview
    • MCQ
  • EE
    • Electronics
    • Electrical
  • Measure
    • Control Valves
    • Calibration
    • Temperature
    • Pressure
    • Flow
    • Level
    • Analyzers
    • Switches
    • Vibration
    • Solenoid Valve
  • Control
    • PLC Tutorials
    • Control Systems
    • Safety Instrumented System (SIS)
    • Communication
    • Fire & Gas System
  • More
    • Design
    • Tools
    • Animation
    • Basics
    • Formulas
    • Standards
    • TextBooks
    • Common
    • Software
    • Excel Tools
    • Erection & Commissioning
    • Process Fundamentals
    • Videos
    • Books
Follow US
All rights reserved. Reproduction in whole or in part without written permission is prohibited.
Inst Tools > Blog > Practical Questions > Solenoid-controlled Valve Problem

Solenoid-controlled Valve Problem

Solenoid-controlled valve refuses to move when the operator pushes the switch. The control valve remains in fully-closed position.

Last updated: February 6, 2022 6:17 pm
Editorial Staff
Practical Questions
1 Comment
Share
4 Min Read
SHARE

Suppose this solenoid-controlled valve refuses to move when the operator pushes the switch. Whether the switch is pressed or unpressed, the control valve remains in the fully-closed (down) position:

Contents
Solenoid-controlled Valve ProblemSolenoid-controlled Valve Solution

Solenoid-controlled Valve Problem

Solenoid-controlled Valve Problem

Another technician has already measured voltage between terminals H1 and H4 on the transformer, and 0 volts between terminals D and X1, in both pushbutton switch positions. At that point, he gave up and left the system for you to troubleshoot.

Identify the below-mentioned faults are possible to happen or not.

  • Fuse F3 blown (failed open)
  • Solenoid stuck in “energized” position
  • Solenoid stuck in “de-energized” position
  • Solenoid coil failed open
  • Solenoid coil failed shorted
  • Silencer plugged
  • Vent cap plugged
  • Wire open between terminals A and E
  • Wire open between terminals C and H
  • Wire open between terminals K and B
  • Valve V1 shut
  • Valve V2 shut

Identify the likelihood of each specified fault for this system. Consider each fault one at a time (i.e. no coincidental faults), determining whether or not each fault could independently account for all measurements and symptoms in this system.

Finally, identify the next diagnostic test or measurement you would make on this system.

Explain how the result(s) of this next test or measurement help further identify the location and/or nature of the fault.

Solenoid-controlled Valve Solution

A plugged vent on the valve actuator, while in theory capable of limiting the control valve’s upward motion, would not prevent any motion at all from occurring when full pressure is applied to the bottom of the diaphragm. This is why “Vent cap plugged” is checked as impossible rather than possible for this scenario.

A good “next test” would be to crack the fitting at port “C” of the solenoid valve. If there is pressure, it means the problem must lie past the solenoid (e.g. valve V1 shut, or a problem in the process control valve).

If there is no pressure at that point, either the solenoid valve is stuck in the “energized” position or there is a lack of supply pressure to the solenoid.

FaultsPossibleImpossible
Fuse F3 blown (failed open) ✓
Solenoid stuck in “energized” position✓ 
Solenoid stuck in “de-energized” position ✓
Solenoid coil failed open ✓
Solenoid coil failed shorted ✓
Silencer plugged ✓
Vent cap plugged ✓
Wire open between terminals A and E ✓
Wire open between terminals C and H ✓
Wire open between terminals K and B ✓
Valve V1 shut✓ 
Valve V2 shut✓ 

Share your answers with us through the below comments section.

Read Next:

  • Spool Valve Symbols
  • PLC Switch Actuation Status
  • Identify Solenoid Valves Status
  • Calculate the Transmitter Values
  • Pressure Actuated Lifts Questions
  • Flow Reversed through Control Valve

Credits: Tony R. Kuphaldt

Don't Miss Our Updates
Be the first to get exclusive content straight to your email.
We promise not to spam you. You can unsubscribe at any time.
Invalid email address
You've successfully subscribed !
Motion-Balance and Force-Balance Instruments
Differential Pressure Measurement across Baghouse
How Manometer Measures Differential Pressure for Different Fluids?
Distillation Tower Displacer Level Instrument Check
Identify the Pressure Gauge Error
Share This Article
Facebook Whatsapp Whatsapp LinkedIn Copy Link
Share
1 Comment
  • Todd says:
    April 15, 2022 at 10:13 am

    Coil shorted open

    Reply

Leave a Reply Cancel reply

Your email address will not be published. Required fields are marked *

Stay Connected

128.3kFollowersLike
69.1kFollowersFollow
208kSubscribersSubscribe
38kFollowersFollow

Categories

Recent Comments

  • Kamli on Top Free PLC Software
  • Guifty Shimica on Top Non-PLC Certification Courses for Automation Professionals
  • Guifty Shimica on Top Non-PLC Certification Courses for Automation Professionals
  • MIHARITSOA Aina Sitraka on Top Non-PLC Certification Courses for Automation Professionals

Related Articles

Determine the Problems with the Level Transmitter and Gauge

Determine the Problems with Level Transmitter and Gauge

Liquid Level Measurement using Pressure Transmitter

Liquid Level Measurement using Pressure Transmitter Questions

Remote Seal Pressure Transmitter

How much Pressure will Remote Seal Pressure Transmitter Indicate?

Dual-junction thermocouple circuit

Find Thermocouple Ouput Voltage

Siemens PLC Block Diagram

Programmable Logic Controller (PLC) Questions and Answers – 14

Calculate DPT Calibrated Range

Calculate the Transmitter Values

Heat Exchanger Differential Pressure Transmitter

Heat Exchanger Differential Pressure Transmitter

simulate a thermocouple

Calculate the appropriate millivoltage values of a Thermocouple

More Articles

Electrodynamometer Movement Principle

Electro-Dynamo Meter Movement

Servo Operated Float Level Measurement

Servo Operated Float Level Measurement

radial-vane damper

Dampers and Louvres

Turbine and Compressor Control System

Turbine and Compressor Control System

Analyzers Questions and Answers

Sodium Analyzer Questions & Answers

To check the characteristic of vibration probe

Bently Nevada Vibration Probes Functional Testing

Analytical Instrumentation Engineering Projects

Top 100 Analytical Instrumentation Engineering Projects

High-pressure Service Level Transmitters Misunderstood Zero Drifts

High-pressure Service Level Transmitters Misunderstood Zero Drifts

Follow US
All rights reserved. Reproduction in whole or in part without written permission is prohibited.
Welcome Back!

Sign in to your account

Username or Email Address
Password

Lost your password?