Reading: Ammonia Gas Detector Working Principle and Calibration
Share
Notification Show More
Font ResizerAa
Inst ToolsInst Tools
Font ResizerAa
  • Courses
  • Design
  • PLC
  • Interview
  • Control System
Search
  • Courses
  • Automation
    • PLC
    • Control System
    • Safety System
    • Communication
    • Fire & Gas System
  • Instrumentation
    • Design
    • Pressure
    • Temperature
    • Flow
    • Level
    • Vibration
    • Analyzer
    • Control Valve
    • Switch
    • Calibration
    • Erection & Commissioning
  • Interview
    • Instrumentation
    • Electrical
    • Electronics
    • Practical
  • Q&A
    • Instrumentation
    • Control System
    • Electrical
    • Electronics
    • Analog Electronics
    • Digital Electronics
    • Power Electronics
    • Microprocessor
Follow US
All rights reserved. Reproduction in whole or in part without written permission is prohibited.
Inst Tools > Blog > Analyzers > Ammonia Gas Detector Working Principle and Calibration

Ammonia Gas Detector Working Principle and Calibration

Last updated: July 20, 2019 11:26 am
Editorial Staff
Analyzers Calibration
No Comments
Share
5 Min Read
SHARE

Ammonia gas detector working principle and calibration. (Make: Dragger Model : Polytron 5100)

Gas detector is a very important safety device for any chemical plant. Its can give information in any small leak from any pipelines and with early action we can save any incident in plant.

In any chemical plant generally we use four types detector:

  1. Hydrocarbon Detector
  2. CO detector
  3. NH3 detector
  4. Chlorine detector

Here we discussed about Ammonia detector.

Principle :

Ammonia detector works on electrochemical principle. Electrochemical sensors are electrochemical measuring transducers for measuring the partial pressure of gases under atmospheric conditions. The ambient air being monitored diffuses through a membrane into the liquid electrolyte in the sensor. The electrolyte contains a measuring electrode, a counter-electrode and a reference electrode. An electronic potentiostatic circuit ensures a constant electrical voltage between the measuring electrode and reference electrode.

Voltage, electrolyte and electrode material are selected to suit the gas being monitored so that it is transformed electrochemically on the measuring electrode and a current flows through the sensor. This current is proportional to the gas concentration. At the same time, oxygen from the ambient air reacts at the counter-electrode electrochemically. The current flowing through the sensor is amplified electronically, digitized and corrected for several parameters (e.g. the ambient temperature). The resulting measured value is given as an analog, 4-20 mA signal.

Gas Detector Internal Circuit

Gas Detector Parts :

  1. Meter
  2. Potentiostat
  3. Direct current supply
  4. Measured gas
  5. Membrane
  6. Measuring electrode
  7. Electrolyte
  8. Reference electrode
  9. Counter electrode
  10. Temperature sensor

Configuration of Gas Detector:

Gas detector can be used as a two wire or as three wire device.

Connect the gas detector wiring as per your requirement & Power ON the detector. Display shows a start up timer.

Wait for the timer to complete and then press down navigation and go to FSD for Span range.

Ammonia Gas Detector Calibration

Calibration of Gas Detector:

For calibration we use N2 gas for zero calibration and 90 PPM ammonia cylinder for span gas .

Typical Calibration Setup : 

Gas Detector Calibration Setup

Parts :

  1. Regulator
  2. Calibration gas cylinders ( Zero Gas Cylinder & Span Gas Cylinder  )
  3. Calibration adapter

For zero calibration

  1. Connect the regulator with N2 cylinder adapter to detector then adjust the flow to 0.5 l/min
  2. Press down navigation key for 5 sec its showing -0- Adj.
  3. Tap [OK].
  4. The display will show the current value blinking.
  5. Wait for the value to stabilize.
  6. Use [UP] / [DOWN] navigation to adjust the value to 0.
  7. Enter [OK] then detector return to main menu.
  8. Turn off gas flow and remove the calibration adapter from the sensor or disconnect tubing.

Note : Ambient air can be used to zero the sensor instead of nitrogen or Zero Air if the area is known to be free of the target gas or any gas to which the sensor may be cross-sensitive. In this case, no cylinder or calibration adapter is needed for the zero calibration.

For span calibration

  1. Connect the regulator with 90 PPM ammonia cylinder adapter to detector then adjust the flow to 0.5 l/min
  2. Press down navigation key for 5 sec its showing -0- Adj. press down its showing SPn Adj
  3. Tap [OK].
  4. The display will show the current value blinking.
  5. Wait for the value to stabilize.
  6. Use [UP] / [DOWN] navigation to adjust the value (As mention on cylinder certificate, means span cylinder gas concentration).
  7. Enter [OK] then detector return to main menu.
  8. Turn off gas flow and remove the calibration adapter from the sensor or disconnect tubing.

General Preventive Maintenance : In every 6 months once, carry out the calibration of gas detector.

Reference : Drager Manual

Article by :
Ashish Agrawal
Don't Miss Our Updates
Be the first to get exclusive content straight to your email.
We promise not to spam you. You can unsubscribe at any time.
Invalid email address
You've successfully subscribed !

Continue Reading

Field Instrument Calibration Errors
Instruments Calibration Procedures
Capacitance Level Sensor Principle, Limitations, Installation & Calibration
Gas chromatograph Working Animation
Luft detector Principle
Oxidation-Reduction Potential (ORP) Sensor Calibration Procedure
Share This Article
Facebook Whatsapp Whatsapp LinkedIn Copy Link
Share
Leave a Comment

Leave a Reply Cancel reply

Your email address will not be published. Required fields are marked *

Stay Connected

128.3kFollowersLike
69.1kFollowersFollow
208kSubscribersSubscribe
38kFollowersFollow

Categories

Explore More

Humidity Measurement Principle
Total Organic Carbon Analyzers Questions and Answers
Hair Hydrometer Principle
Magnetostrictive Level Transmitter Calibration Procedure
Ionization chamber Principle
Single-beam Non-dispersive Analyzer
Smart Transmitter Calibration Tutorial Part 1
pH Monitoring System Triggers an Alarm

Keep Learning

In-Situ Zirconia Oxygen Analyzer

Oxygen (O2) Measurement in Flue Gas

Instrument Linearity Error

Instrument Errors – Zero, Span, Linearity

Pulsed Fluorescence SO2-H2S-CS Analyzer Working Principle

Pulsed Fluorescence SO2, H2S, CS Analyzer Working Principle

Instrument Calibration Lab Exercise

Instrument Calibration Lab Exercise

HART Transmitter Calibration

How are HART instruments Calibrated?

Instrument Zero and Span Calibration

Instrument Zero and Span Calibration

H & B Gas Analyzer Principle and Calibration Procedure

Calibration and Troubleshooting of Oxygen Analyzer

Calibration and Troubleshooting of Oxygen Analyzer

Learn More

Rotary Drier Shell to Split Gear drive

Rotary Drier Shell to Split Gear drive eliminates too frequent drive failures

Steady-state process gain

Steady-State Process Gain

Magnetically coupled float indicates liquid level

What are Mechanical Level Indicators? – Classification & Principle

Structured Text PLC Program for Measuring Event Duration

Structured Text PLC Program for Measuring Event Duration

Difference of Energy Gap

Difference between Intrinsic and Extrinsic Semiconductors

Online time of the PLC

System and Local Time in PLC

Power Supply Voltage Regulator Problem

Troubleshooting a Power Supply Circuit

Electrical Machines Questions and Answers

Armature Quiz

Follow US
All rights reserved. Reproduction in whole or in part without written permission is prohibited.
Welcome Back!

Sign in to your account

Username or Email Address
Password

Lost your password?