Inst ToolsInst ToolsInst Tools
  • Courses
  • Videos
  • Q & A
    • Interview
      • Instrumentation
      • Electronics
      • Electrical
      • Practical Questions
    • MCQ
      • Instrumentation MCQ
      • Electrical MCQ
      • Electronics MCQ
      • Control Systems MCQ
      • Analog Electronics MCQ
      • Digital Electronics MCQ
      • Power Electronics MCQ
      • Microprocessor MCQ
      • Multiple Choice Questions
  • EE
    • Electronics
      • Electronics Q & A
      • Electronic Basics
      • Electronic Devices & Circuits
      • Electronics Animation
      • Digital Electronics
    • Electrical
      • Electrical Basics
      • Electrical Q & A
      • Power Electronics
      • Electrical Machines
      • Electrical Animation
      • Power Systems
      • Switchgear & Protection
      • Transmission & Distribution
  • Measure
    • Control Valves
    • Calibration
    • Temperature
    • Pressure
    • Flow
    • Level
    • Analyzers
    • Switches
    • Vibration
    • Solenoid Valve
  • Control
    • PLC Tutorials
    • Control Systems
    • Safety Instrumented System (SIS)
    • Communication
    • Fire & Gas System
  • More
    • Design
    • Tools
    • Animation
    • Basics
    • Formulas
    • Standards
    • TextBooks
    • Common
    • Software
    • Excel Tools
    • Erection & Commissioning
    • Process Fundamentals
    • Videos
    • Books
Search
All rights reserved. Reproduction in whole or in part without written permission is prohibited.
Reading: Field Instrumentation Tips
Share
Notification Show More
Font ResizerAa
Inst ToolsInst Tools
Font ResizerAa
  • Courses
  • PLC Tutorials
  • Control Systems
Search
  • Courses
  • Videos
  • Q & A
    • Interview
    • MCQ
  • EE
    • Electronics
    • Electrical
  • Measure
    • Control Valves
    • Calibration
    • Temperature
    • Pressure
    • Flow
    • Level
    • Analyzers
    • Switches
    • Vibration
    • Solenoid Valve
  • Control
    • PLC Tutorials
    • Control Systems
    • Safety Instrumented System (SIS)
    • Communication
    • Fire & Gas System
  • More
    • Design
    • Tools
    • Animation
    • Basics
    • Formulas
    • Standards
    • TextBooks
    • Common
    • Software
    • Excel Tools
    • Erection & Commissioning
    • Process Fundamentals
    • Videos
    • Books
Follow US
All rights reserved. Reproduction in whole or in part without written permission is prohibited.
Inst Tools > Blog > Common > Field Instrumentation Tips

Field Instrumentation Tips

Last updated: April 29, 2019 7:57 am
Editorial Staff
Common
2 Comments
Share
6 Min Read
SHARE

1. For RTD Pt 100 measurement,measure the resistance across the white and common terminal, then the temperature can be calculated simply by

Temp = (resistance measured across terminal minus 100)/0.385

or

Temp = (resistance measured across terminal minus 100)multiplied by 2.6

For example :

if the RTD resistance across white and red terminal is 126 ohm, then

the temperature measured is 26/0.385=67.53 degree centigrade or

26 multiplied by 2.6

26*2.6=67.53

This follow the same eqn, R=Rₒ(1+αT) remember that this is only applicable for PT 100 not other types

2.For calibration of -100 mmH2O to -10 mmH20 range capillary type using pressure pump not vacuum pump

The values for 25%, 50%, 75%, 100% are as follows:

0% is -100 mm h2o

25% is  -77.5 mm h2o

50% is -55 mm h2o

75% is -32.5 mm h2o

100% is -10 mm h2o

First find the Span=URV-LRV=-10+100=90

Then divide this by 4 as we are calibrating for 4 values namely 25%, 50%, 75%, 100%

i.e. 90/4=22.5

then the 4 points can be calculated as follows

0%(4ma)————-> 0 mm h2o i. e LP and HP open to atmosphere

25%(8ma)———–> -0+22.5=22.5 mm h2o (apply 22.5mmh2o to HP side not LP here LP is open to atmosphere.)

50%(12ma)——–> 22.5+22.5=44 mm h2o (apply 44mmh2o to HP side not LP)

75%(16ma)———> 44+22.5=67.5 mm h2o (apply 67.5 mmh2o to HP side not LP)

100%(20 ma)——> 67.5+22.5=90 mm h2o (apply 90 mmh2o to HP side not LP)

3.Calculation of flow m3/hr from differential pressure values mm h20 if both ranges are known:

We know that the flow equation is related as follows

Q=k√∆p

Here Q is the rate of flow: k is the Bernoulli’s constant; and ∆p is the differential pressure

Consider for instance the D.P. transmitter is of range 0 to 120 mm H2O and the DCS range of

0 to 1500 m3/hr

Then the next step is to find the Bernoulli’s constant

i.e. Q=k√∆p

1500=k√120 (here we consider span URV values to find Bernoulli’s constant)

k=1500/√120

k=136.936

Once we get Bernoulli’s constant we can calculate any flow rate if we know the D.P.

For e.g.

If differential pressure is 90 mmH2O

Q=k√∆p becomes

Q=136.936√90

= 136.936*9.486 = 1298.9 m3/hr

Thus we can calculate any flow rate if we know the transmitter and DCS range.

Or simply

Flow in DCS(present value) =(DCS range)√(Present DP value/DP range)

For example DCS range is 1000m3/hr,

DP range is 100 mmh20,

And present DP value in transmitter is showing 25 mmh2o,then

DCS flow will be

Flow in DCS(present value) =(DCS range)√(Present DP value/DP range)

=1000√(25/100)

=1000√(1/4)

=1000*1/2

=500 m3/hr

4.For K type thermocouple (Chromel alumel) if the mV measured across yellow(positive) and red (negative) is x,then the temperature can be calculated as follows

Temperature = x/0.0397(millivolt measured divided by 0.0397) or x *25.2 (millivolt multiplied by 25.2)

for example if we measure the mV value across yellow and red terminal using a multimeter and found to be 0.397 then temperature can be calulated by

temperature=(0.397/0.0397)=10 degree centigrade or (0.397*25.2)=10 degree centigrade

5.calibration checking of capillary type LT if you dont have any instruments for checking

Suppose that a capillary type LT is mounted on a tank having range of -1200mmh2o as LRV and URV -60 mmh2o and you need to check whether the transmitter is Ok

We know that the transmitter is mounted with HP side to high pressure side and LP tapping to low pressure side,Firstly isolate the process line,vent and drain the process inorder to release any trapped pressure inside the flange.the transmitter will show 0% reading ie(-1200mmh2o),

Now measure the tap to tap length and mark the corresponding 25%,50%,75% and 100% level .Remove the LP flange of the transmitter(with HP flange of capillary intact) and keep it near(parallel) to HP tapping, the transmitter will show 100%.Now lift the LP capillary flange to 25% above from the HP tapping (where we marked before as 25%),now the transmitter will show 75% (not 25%)

Next keep the transmitter LP capillary flange at 50% marking the transmitter will show 50% reading.Similarly when we place at 75% the transmitter will be showing 25%

Finally if we place at 100% marking the transmitter should show 0% that is -60mmh2o

6.For most of the thermocouples the red terminal is considered as negative terminal(ANSI standard) and if red is not available then white terminal is considered as negative terminal(japan and IEC standards)

7.For pH analysers calibration can be done by supplying mV

58mV corresponds to 1 pH

so if we are calibrating for water whose pH is 7, the supplied voltage should be 58*7 mV=406mV.

Thus if 406mV is applied to pH transmitter it will show a reading of 7pH

Credits : kishore karuppa swamy

Don't Miss Our Updates
Be the first to get exclusive content straight to your email.
We promise not to spam you. You can unsubscribe at any time.
Invalid email address
You've successfully subscribed !

Recommended Articles

7 Marketing Strategies for Engineering Companies
Wet Dust Suppression System
Car Lifts – Choosing the Right One for Your Mechanic Shop
Cold Email Deliverability – Latest Comprehensive Guide
Meters used in Troubleshooting Electrical Equipment
Why is CO2 the Most Promising Refrigerant in Cooling Industry?
Share This Article
Facebook Whatsapp Whatsapp LinkedIn Copy Link
Share
2 Comments
  • Hardik Mungra says:
    August 22, 2018 at 1:46 pm

    Nice and very useful information

    Reply
  • Mack Kelly says:
    July 25, 2019 at 10:25 am

    was owesome to me

    Reply

Leave a Reply Cancel reply

Your email address will not be published. Required fields are marked *

Stay Connected

128.3kFollowersLike
69.1kFollowersFollow
208kSubscribersSubscribe
38kFollowersFollow

Categories

Recent Comments

  • William Snyder on Top Non-PLC Certification Courses for Automation Professionals
  • Kamli on Top Free PLC Software
  • Guifty Shimica on Top Non-PLC Certification Courses for Automation Professionals
  • Guifty Shimica on Top Non-PLC Certification Courses for Automation Professionals

Related Articles

Bracelet Scanner

How to Use Bracelet Scanner? – Ultrasonic Thickness Gauge

types of maintenance programs

Maintenance – Preventive, Predictive, Proactive, Corrective

Solar Pump

What is a Solar Pump VFD? – Advantages, Principle

Common Materials used in Instrumentation Cables

Common Materials used in Instrumentation Cables

custom metal fabrication

Custom Metal Fabrication Techniques for Quality Machined Parts

List of 100 Sensors and Transducers Questions

List of 100 Sensors and Transducers Questions

Sugar Plant - Automatic Control of Massecuite Feed

Sugar Plant – Automatic Control of Massecuite Feed

Classification of Weighing Balance

Classification of Weighing Balance and Weight

More Articles

Hydraulic Motor Forward and Reverse Control with Simulation

Hydraulic Motor Forward and Reverse Control with Simulation

Flow Measurement Questions

MCQ on Flow Measurement

smart-transmitters-advanced-diagnostics

Smart Transmitters Advanced Diagnostics

SMART Transmitter

What is a SMART Transmitter?

Top 10 Facts about HART Technology

What is HART, Foundation Fieldbus & Profibus ?

Example of Automated Guided Vehicle with PLC

Example of Automated Guided Vehicle with PLC

Ladder Diagram PLC program

PLC Counter Instructions

Strain Gauge Bridge Circuit

Something is Wrong with Strain Gauge Bridge Circuit

Follow US
All rights reserved. Reproduction in whole or in part without written permission is prohibited.
Welcome Back!

Sign in to your account

Username or Email Address
Password

Lost your password?