Pneumatic Level Transmitter Calibration Table

A pneumatic level transmitter has a calibrated range of 0 to 5 feet, and its output signal range is 3 to 15 PSI.

Complete the following table of values for this transmitter, assuming perfect calibration (no error). Be sure to show your work!

Calibration Table

Pneumatic Transmitter

Solution:

Pneumatic Level Transmitter Calibration Table

Credits: Tony R. Kuphaldt