Instrumentation Basics – Range Conversion Formula and Examples

We encounter many transmitters in daily activities like preventive maintenance, breakdown, or commissioning activities.

We may need to convert any given transmitter range to other range like from (0oC – 100oC) to (4 mA – 20 mA) or (0 kg/cm2 – 10 kg/cm2) to (3 psi – 15 psi) or (0 mmH2O – 2000 mmH2O) to (0% – 100%), etc.

Instrumentation Basics

Instrumentation Basics - Range Conversion Formula and Examples

All the above conversions are easy to implement. But now think of a case in which you are supposed to convert from (-250oC to 150oC) to (4 mA to 20 mA) or any such instrument range which has uneven starting and endpoints.

Don’t worry friends, in this article we will learn two methods to convert the value from one range to another range.

Instrument Range Conversion – Method 1

This method might be known to many engineers who are reading this article. But still, we don’t use it frequently because we often forget the formula.

Every transmitter range has two parameters which are LRV and URV. Here LRV means lower range value and URV means upper range value.

Let us recall the method. Suppose the first range is having LRV and URV as LRV_1 and URV_1 and another range has LRV_2 and URV_2.

Desired values are Value_1 and Value_2 in both ranges.

So, we use the below formula:

Let us see an example.

Suppose range one is 0 kg/cm2 – 100 kg/cm2

Range two is 4 mA to 20 mA

What will be value corresponding to 25 kg/cm2? (in milli amps)

Here Value_1 = 25

LRV_1 = 0

URV_1 = 100

Value_2 = to be calculated

LRV_2 = 4

URV_2 = 20

Put these values into the formula

(25-0) / (100-0) = ((Value_2) – 4) / (20-4)

25/100 = (Value_2 – 4) / 16

0.25 = (Value_2 – 4) / 16

Value_2 – 4 = 0.25 x 16

Value_2 = 4 + 4

Solving this equation, we get

Value_2 = 8

Hence for 25 kg/cm2, we get 8 mA as a proportional value.

This was quite an easy calculation that can even be done without using this formula.

Now have a look at the below example.

Range one: -70 o C to 190 o C

Range two: 4 mA to 20 mA

What will be the value corresponding to 50 o C? (in milli amps)

Put all values in our standard equation.

(50-(-70)) / (190-(-70)) = ((Value_2)-4) / (20-4)

120/260 = (Value_2 – 4)/16

0.4615 = (Value_2 – 4)/16

Value_2 – 4 = (0.4615 x 16)

Value_2 = 7.384 + 4

Solving this equation, we get

Value_2 = 11.384 mA

This is the first method.

Now let us see the second method which is for those who do not want to remember the formula.

Instrument Range Conversion – Method 2

Let us see this method by taking an instrument example. Let us take the above example only

Range one: -70oC to 190oC

Range two: 4 mA to 20 mA

We need to calculate the equivalent milli amperes for the value of 50oC

First, calculate how much % is 50oC in the range of -70oC to 190oC.

The range is 260oC

For this we will use a simple formula :

50-(-70)  —->  260

     ?      <—-  100

We have to take 50-(-70) because we want absolute value from LRV.

We get,

(100*120)/260 = 46.1538 %

Now we need a 46.1538% value for the 4 mA to 20 mA range

Divide the above value by 100. (46/100 = 0.461538)

Here 16 is the difference between URV and LRV.

So, multiply 0.461538 by 16. We get 7.3846.

Now add this value to our LRV. (7.3846 + 4)

We get 11.3846 mA which is our required value.

This is how we can convert values from one range to another.

If you liked this article, then please subscribe to our YouTube Channel for Instrumentation, Electrical, PLC, and SCADA video tutorials.

You can also follow us on Facebook and Twitter to receive daily updates.

Read Next:

You've successfully subscribed !

View Comments

Share

Recent Articles

  • PLC Tutorials

Conveyor Sorting Machine PLC Program with Calculation Function

The conveyor sorting machine is widely used in the packing industries using the PLC program…

5 days ago
  • PLC Tutorials

Example of Flip-Flop PLC Program for Lamps Application

Learn the example of flip-flop PLC program for lamps application using the ladder logic to…

5 days ago
  • PLC Tutorials

STAR DELTA Programming using PLC Controller

In this article, you will learn the STAR DELTA programming using PLC controller to start…

5 days ago
  • Instrumentation Design

Single and Three Phase Immersion Electrical Heaters Wiring Circuits

Lube oil consoles of rotary equipment packages in industrial process plants are usually equipped with…

2 days ago
  • Instrumentation Design

Immersion Heaters in Lube Oil Consoles

Rotating equipment packages such as pumps, compressors, turbines need the lube oil consoles for their…

5 days ago
  • PLC Tutorials

How to Blink Lights in Ladder Logic?

This article explains how to blink lights in ladder logic with a detailed explanation video…

4 weeks ago