Heat Exchanger Temperature Control

Since the outlet temperature of a heat exchanger can only change if there is an imbalance of inlet and outlet heat rates (assuming constant liquid inlet temperature and constant liquid composition), would this system be practical to achieve steady liquid outlet temperature control? Explain why or why not.

Heat Exchanger Temperature Control

Heat Exchanger Outlet Temperature Control

Note: the philosophy behind this control system is a principle known as energy balance, and it is a very valid principle. Explain what the principle of “energy balance” is, and how it is implied in the design of this control system.

Answer:

In theory, this feedforward system would work to hold the liquid outlet temperature absolutely constant, because it will try to maintain heat flow out equal to heat flow in (energy out balances energy in).

However, there are some practical reasons why it would not work (even if the liquid inlet temperature and composition were held constant).

Questions For You:

1. Explain why the control system as shown is impractical for real-life use, despite the fact that it does represent a very effective and important control strategy frequently used in industry.

2. Determine whether the controller needs to be direct acting or reverse acting.

3. A problem-solving technique useful for analyzing control systems is to mark the PV and SP inputs of all controllers with “+” and “−” symbols, rather than merely label each controller as “direct” or “reverse” action. Apply this technique to the control strategy shown here, identifying which controller input(s) should be labeled “+” and which controller input(s) should be labeled “−”.

4. Modify this control strategy to incorporate “feedback trim” in addition to the feedforward action it currently possesses.

5. Are there any loads unaccounted for in this feedforward control strategy? If so, see if you can modify this control strategy to account for them as well.

Join the Discussion! Share your answers with us through below comments section.

Read Next:

You've successfully subscribed !

View Comments

  • 1. Yes, I am agreed that the control system is impractical for real-life use because TI must include the loop to measure the output disturbance of change of temperature.
    2. The output needed is Hot liquid so that FC will control FV where steam flow to be directing acting and reverse acting on the FV for the cold liquid in.

Share

Recent Articles

  • Instrumentation Design

Immersion Heaters in Lube Oil Consoles

Rotating equipment packages such as pumps, compressors, turbines need the lube oil consoles for their…

20 hours ago
  • PLC Tutorials

How to Blink Lights in Ladder Logic?

This article explains how to blink lights in ladder logic with a detailed explanation video…

3 weeks ago
  • PLC Tutorials

From Boolean Algebra to PLC Logic

In this article, a simple example will teach you the conversion from Boolean algebra to…

1 month ago
  • PLC Tutorials

PLC Cooking Timer Example for Kitchen Automation

In this article, you will learn the PLC cooking timer example for kitchen automation using…

3 weeks ago
  • PLC Tutorials

Example PLC Program to Control a Pump based on Level Sensors

Learn an example PLC program to control a pump based on level sensors using ladder…

3 weeks ago
  • PLC Tutorials

PLC Timer Application in Security Camera Recording

In the PLC timer application for security camera recording, when motion is detected then camera…

3 weeks ago