Fire & Gas System

Design Basis for Fire Detection and Alarm System

The intent of this document is to define the general requirement of a Fire Detection and Alarm System (FDAS). This article provides general information, process and engineering data, and guidance on the selection of detectors, devices, and systems.

Codes and Standards

The basic design will conform to the requirements of the latest editions of the following codes, guides and specifications wherever applicable.

NFPA 72: 2019National Fire Alarm Code
IS 2189:2008 Code of Practice for selection, installation, and maintenance of Automatic Fire Detection and Alarm System
IS 2175:1988Heat-sensitive fire detectors for use in automatic fire alarm systems.
IS 1881:1998Indoor installation of sounding system
BS EN 50288 7:2005Multi-element metallic cables used in analog and digital communication and control, Part 7- Sectional specification for instrumentation and control cables

Selection Criteria of FDAS Components

Design Basis for Fire Detection and Alarm System

Criteria for selecting fire detectors and devices considering the various areas of the plant should be as follows:

Type of detector/ deviceArea/ Environmental conditions
Fire alarm control panelMCC Room
Repeater PanelControl room
GUI with PCControl room
Multisensor detectorsAll non-plant area
Heat DetectorPump house, Kitchen area, Non-plant buildings (Area above false ceiling & below false flooring)
Beam-type smoke detectorsRaw material goes down, Storage area
Hydrogen gas detectorsBattery Room
Manual call pointAll exits of Plant area & Non-Plant area
Ex-Proof Manual call pointAll exits of Plant area (Hazardous area)
Linear Heat Sensing cableFor HT Cable trays, cable cellar room
Control Module / Monitor ModuleRequired for hardwire Integration with third-party services
Hooter with strobeAll plant exits & noisy areas of the plant (non-hazardous) & Non-Plant Buildings

Fire Alarm Control Panel (FACP)

  • Loop supervision
  • Alarm generation from detector/ devices
  • Functional alarms such as a low battery, AC power failure, fault
  • Connection to detectors/ devices through loop cable
  • Minimum 6 Nos. of loop cards shall be considered by the vendor unless specified.
  • FACP will have an alphanumeric, keyboard, and LCD display for giving the status of the area-wise fire alarms. It will also have Acknowledge, Reset and Test pushbuttons for alarm annunciation It will have indications for Main AC power failure and battery failure.

Fire Alarm Repeater Panel

  • Passive type
  • Alpha-numeric display
  • Controls like alarm silence, alarm reset & alarm acknowledge.
  • Repeat alarm signals from the FACP that are connected to the network.

Graphical User Interface (GUI) with Workstation

  • PC-based GUI shall be provided with customized software.
  • Seamless integrated graphical mimic with full alarm management and panel control capability.
  • Installation plans, device type, locations, zoom areas, and zoom magnifications shall be able to import from AutoCAD as loaded in GUI.
  • Software shall be able to generate audio-visual indications in case of emergency/ input signals from detectors/ devices/ panels.
  • In the event of change of any logic, detector/ zone sequence alteration, the operator can initiate this by alpha-numeric keys on the Fire Alarm Panel or through the GUI.
  • The programming through GUI shall be possible for the FACP provided in the plant.

Multi Sensor Detector

  • Multi Sensor Detector is a combination of smoke & heat sensing technology in which FACP will receive the signal in case of detection of smoke as well as detection of an increase in temperature.
  • The detectors should be intelligent addressable & loop powered.
  • Each detector shall use state-of-the-art microprocessor circuitry with error, detector self-diagnostics, and supervision programs.
  • Each detector should have a multicolor & multi-status indicator LED to indicate the status of the detector.

Manual Call Point (MCP)

  • Manual Call points (MCP) should be addressable & loop powered.
  • It should be surface wall or pole mounted indoor and outdoor type for a safe area.
  • If conventional MCPs provided, the same shall be made addressable using the monitor module.
  • Ex-proof MCPs must be provided in hazardous areas.

Hooter with Strobe

  • Hooter with Strobe should be addressable & loop powered.
  • Hooter should sound automatic when any of the detectors in that zone detects a fire condition.
  • Hooter should be installed considering sound pressure level, and acoustic area coverage.
  • If a conventional Hooter/ strobe is provided, the same should be made addressable using the control module.
  • Ex-proof hooter with strobe should be provided in the hazardous areas.

Monitor Module

  • Monitor Module shall supervise the open potential free dry contact input of the device & give an alarm when the alarm is generated by the connected device.
  • The monitor module shall be the interface between FACP & DCS, FACP & conventional devices to make them addressable one

Control Module

  • Control Module shall provide the dry contact output for activating a variety of auxiliary devices such as PAS, Firefighting equipment, AHUs, and conventional devices as required. These are typically used where control or shutting of external equipment is required.
  • Control relay modules shall be provided to integrate FDAS with third-party systems.

Hydrogen Gas Detectors

  • Hydrogen Gas Detectors shall be provided in Battery rooms for detecting Hydrogen gas leakage from the batteries.
  • Hydrogen Gas Detector shall measure the gas concentration in a % level of 0-100% range.

Beam Type Smoke Detectors

  • A beam-type smoke detector should be installed in areas having a ceiling/ roof height of more than 10 meters or in large areas like warehouses or godowns.
  • The projected beam length will range from 10 meters to 100 meters.
  • Line of sight vision between the transmitter & receiver/reflector should be clear to avoid false alarms.
  • Adjustable sensitivity levels should be set as per site conditions.

Heat Detector

  • The heat detector will detect heat and generate a signal either due to a sudden increase in the temperature or due to an increase in the ambient temperature exceeding the pre-set alarm temperature of the detector.
  • The detectors shall be loop powered.
  • Each detector will have a multicolor & multi-status indicator LED to indicate the status of the detector.
  • Above false ceiling detector with response indicator shall be provided if false ceiling void area is greater than equal to 800mm.

Fault Isolator Module

  • Fault Isolator Module should supervise the open loop or fault in the loop of the devices & give the alarm. It shall isolate them.
  • Fault Isolator Module should be provided in every loop for every 20 devices/detectors.

Linear Heat Sensing (LHS) Cable & Distance Locator Module

  • Linear Heat Sensing (LHS) system must be the analog or digital type with a distance locator module (if required) to indicate the exact location of the occurrence of the fire.
  • A change in temperature shall produce a relative and inverse change in resistance between the two sensor cables.
  • Normally it is used in HT power cable trays. LHS cable shall be detecting heat generated from current carrying cables over its entire length. Also, it is used in coal conveyors, cable trenches, etc.
  • Analog cable is reusable after the detection of the increase in heat where alarm temperature can be set.
  • The Digital cable needs to replace after the detection of the heat. It is available in different temperature ranges.
  • LHS cable shall get connected to the signal line circuit with the help of the monitor module

If you liked this article, then please subscribe to our YouTube Channel for Instrumentation, Electrical, PLC, and SCADA video tutorials.

You can also follow us on Facebook and Twitter to receive daily updates.

Read Next:

You've successfully subscribed !
Share

Recent Articles

  • Instrumentation Design

Immersion Heaters in Lube Oil Consoles

Rotating equipment packages such as pumps, compressors, turbines need the lube oil consoles for their…

21 hours ago
  • PLC Tutorials

How to Blink Lights in Ladder Logic?

This article explains how to blink lights in ladder logic with a detailed explanation video…

3 weeks ago
  • PLC Tutorials

From Boolean Algebra to PLC Logic

In this article, a simple example will teach you the conversion from Boolean algebra to…

1 month ago
  • PLC Tutorials

PLC Cooking Timer Example for Kitchen Automation

In this article, you will learn the PLC cooking timer example for kitchen automation using…

3 weeks ago
  • PLC Tutorials

Example PLC Program to Control a Pump based on Level Sensors

Learn an example PLC program to control a pump based on level sensors using ladder…

3 weeks ago
  • PLC Tutorials

PLC Timer Application in Security Camera Recording

In the PLC timer application for security camera recording, when motion is detected then camera…

3 weeks ago