Inst ToolsInst ToolsInst Tools
  • Courses
  • Automation
    • PLC
    • Control System
    • Safety System
    • Communication
    • Fire & Gas System
  • Instrumentation
    • Design
    • Pressure
    • Temperature
    • Flow
    • Level
    • Vibration
    • Analyzer
    • Control Valve
    • Switch
    • Calibration
    • Erection & Commissioning
  • Interview
    • Instrumentation
    • Electrical
    • Electronics
    • Practical
  • Q&A
    • Instrumentation
    • Control System
    • Electrical
    • Electronics
    • Analog Electronics
    • Digital Electronics
    • Power Electronics
    • Microprocessor
  • Request
Search
  • Books
  • Software
  • Projects
  • Process
  • Tools
  • Basics
  • Formula
  • Power Plant
  • Root Cause Analysis
  • Electrical Basics
  • Animation
  • Standards
  • 4-20 mA Course
  • Siemens PLC Course
Reading: Input-Output Relationships of Transmitters
Share
Font ResizerAa
Inst ToolsInst Tools
Font ResizerAa
  • Courses
  • Design
  • PLC
  • Interview
  • Control System
Search
  • Courses
  • Automation
    • PLC
    • Control System
    • Safety System
    • Communication
    • Fire & Gas System
  • Instrumentation
    • Design
    • Pressure
    • Temperature
    • Flow
    • Level
    • Vibration
    • Analyzer
    • Control Valve
    • Switch
    • Calibration
    • Erection & Commissioning
  • Interview
    • Instrumentation
    • Electrical
    • Electronics
    • Practical
  • Q&A
    • Instrumentation
    • Control System
    • Electrical
    • Electronics
    • Analog Electronics
    • Digital Electronics
    • Power Electronics
    • Microprocessor
  • Request
Follow US
All rights reserved. Reproduction in whole or in part without written permission is prohibited.
Inst Tools > Blog > Formulas > Input-Output Relationships of Transmitters

Input-Output Relationships of Transmitters

Last updated: April 19, 2019 1:19 pm
Editorial Staff
Formulas
6 Comments
Share
6 Min Read
SHARE

Have you ever had that actually forget something simple? And generally forgotten it was in the form like a formula. For example, the formula to convert temperature unit of degrees Celsius to degrees Fahrenheit. Generally we use the formula:

{(9/5) * x + 32 ° F}

Where “x”  is the temperature in Deg C

So as to know how to calculate ° F of the temperature of 50 ° C, if using the above formula to

{(9/5) * x + 32 ° F} = {(9/5) * 50 ° F} + 32 = 122 ° F

Easy enough right? Yes, if we memorized formula. The problem is if we completely forgot the formula.

The calculation of input-output relationships of transmitter

input-output-relationships-of-transmitters

Something similar may happen when we’re doing calibration, like a pressure transmitter. For example, with an input pressure of 0-300 PSI and 4-20mA output.

If we use the method of 5-point calibration (0%, 25%, 50%, 75% and 100%), it may be quite easy for us, it should be how we put pressure on the transmitter at the time of testing at 50% (12mA). But it is different if we verify the pressure transmitter is already on-line with different process value.

For example, we find the pressure on the input side of the transmitter is 235 PSI, then what is the pressure transmitter output signal?

Back to the issue of conversion of temperature. If we forget the formula, we can actually do the conversion without having memorized the formula, the condition we know the upper limit and lower limit for the second unit. Then, using the equation of general comparison, we can create their own respective formula.

We know that the units Celsius has a measuring range (measuring scale for the calculation) between 0-100 ° C and Fahrenheit 32-212 ° F. So if asked, 50 ° C was how ° F, then:

Temperature Transmitter Formula

See calculation above, it may be longer than we memorize the formula, here we do not try to memorize formulas, but understand the concept, because the first formula above were true simplification of calculations a second.

The concept of how it mean? This calculation is a calculation of comparison, to compare two different scales.

Let’s agree that:

x ° C = value ° C

C min   = minimum scale ° C = 0 ° C

C max  = maximum scale ° C = 100 ° C

x ° F = value ° F

F min  = minimum scale ° F = 32 ° F

F max maximum scale ° F = 212 ° F

thus:

Temperature Transmitter Conversion Formula

Using the above equation:

Temperature Transmitter Conversion Example

This applies to calculate the output of a transmitter at the time of a particular input. For example, as the above example, we have a pressure transmitter with 0-300 PSI pressure input range and output 4-20mA.

Let’s agree:

x in   = value transmitter input (235PSI)

In min   = scale of minimum input transmitter = 0PSI

In max   = maximum scale transmitter input = 300PSI

x out = transmitter output value (mA)

Out min   = minimum scale transmitter output = 4mA

Out max = maximum scale = 20mA transmitter output

With reference to the equation of comparison, the value of 235PSI input transmitter can be calculated:

Temperature Transmitter Calculation

By understanding the concept of the above, we can make a generic equation for the relation between the input and output of a transmitter as follows:

Temperature Transmitter Formulae

Where:

x dit   = value in question (want to know)

dit min   = minimum scale range in question

dit max   = maximum scale range in question = 300PSI

x dik = value unknown

dik min   = minimum scale of a range of known

dik max = maximum scale of the known range

Example:

A temperature transmitter with an input range +50 to 200 ° F and output range is 4-20mA. what is the output if input temperature is 61 ° F:

dit min   = 4

dit max   = 20

x dik = 61

dik min   = 50

dik max  = 200

Then:

Temperature Transmitter Convert

Thus, the input temperature of 61 ° F, the transmitter output is 5.1737 mA

Thus, a generic formula for calculating the relationship of input and output transmitter or vice versa, can use:

Temperature Transmitter Formulae

A temperature transmitter with input range -25 to 100 ° C and output 4-20mA range, Transmitter output is 17.5 mA, and find out temperature reading ?

Try to calculate the answer using above method:

Share your comments

Articles You May Like :

Level Control Loop Tuning

Percentage to Process Variable

Transmitter Process Variable

Control Valve Cv calculation

Radar Level Transmitter

Don't Miss Our Updates
Be the first to get exclusive content straight to your email.
We promise not to spam you. You can unsubscribe at any time.
Invalid email address
You've successfully subscribed !

Continue Reading

Turbine Flow Meter Coefficient and Scaling Factor
Displacer Level Measurement Calculations
DP Level Transmitter Elevation and Suppression Corrections
4-20mA Transmitters Calculations
Transmitter Turndown Ratio, Set Span and Zero Span
Formula to Calculate 4-20ma from Percentage
Share This Article
Facebook Whatsapp Whatsapp LinkedIn Copy Link
Share
6 Comments
  • Venkat says:
    November 21, 2016 at 8:23 am

    Was very useful. Can’t believe how we think of simple things as complicated ones. Thanks.

    Reply
  • kingsley says:
    November 21, 2016 at 1:35 pm

    Thanks sir , you are great !!! your informations are powerfull.

    Please explain how to calibrate FF temperature and pressure transmitter using field communicator

    Reply
  • Nagaraju says:
    November 25, 2016 at 3:12 pm

    Thank u sir.

    Reply
  • kudo says:
    December 17, 2018 at 7:10 am

    may I know what is the answer sir?

    Reply
  • kudo says:
    December 17, 2018 at 7:31 am

    I get 80.47 deg C, is it true?

    Reply
    • S Bharadwaj Reddy says:
      December 17, 2018 at 8:01 am

      Yes, Correct. You can try online Inst Cal for cross checking. Click Here.

      Reply

Leave a Reply Cancel reply

Your email address will not be published. Required fields are marked *

Stay Connected

128.3kFollowersLike
69.1kFollowersFollow
210kSubscribersSubscribe
38kFollowersFollow

Categories

Explore More

Siemens Pressure Transmitter with Remote Seals Calculations
4-20mA Formulas and Examples
Raw Counts to Engineering Units : Conversion Formula
How to do 4-20mA Conversions Easily
PLC Analog Input Scaling
Calculate Control Valve Stem Position
Instrument Percent of Span Error
Calculate Flow Coefficient Kv of Solenoid Valve

Keep Learning

4-20mA to Process Variable conversion

Formula to Calculate Process Variable from 4-20mA

Current-to-Percentage-Conversion

Formula for Current 4-20ma to Percentage Conversion

plc-analog-input-card-conversion-formula

PLC Analog Input Conversion Formula

Gas flow rate Formulas

Gas Flow Formulas

Control Valve Cv Formula

Control Valve Cv calculation

Formulas to calculate ma from PV

Formulas to calculate mA from PV, LRV and URV

Relationship between Temperature Scales

Relationship between Temperature Scales

Process variable to 4-20mA Conversion

Formula to Calculate 4-20 mA from Process Variable

Learn More

Digital Electronics Multiple Choice Questions

Master-Slave Flip-Flops Objective Questions

redundant transmitters

SIS Sensors

Siemens S7 300 CPU Status and LED Errors Explanation

Siemens S7 300 CPU Status and LED Errors Explanation

Analog Input Card Resolution Effects on Accuracy

PLC Analog Input Card Resolution Effects on Accuracy

valve actuator yoke

Advantages and Disadvantages of Valve Actuators

Electrical Machines Questions and Answers

DC Machines Torque Quiz

Alternating Current

Difference between AC and DC

PLC Pump Control

PLC Pump Control: 10 seconds ON & 20 seconds OFF

Menu

  • About
  • Privacy Policy
  • Copyright

Quick Links

  • Learn PLC
  • Helping Hand
  • Part Time Job

YouTube Subscribe

Follow US
All rights reserved. Reproduction in whole or in part without written permission is prohibited.
Welcome Back!

Sign in to your account

Username or Email Address
Password

Lost your password?