Root Cause Analysis (RCA)

Root Cause Analysis for Plant Trip Due to Work on Incorrect Tag

Today in this article we will discuss about the root cause analysis of an incident in which one unit of a plant tripped due to work on an incorrect tag.

The incident we are going to discuss can occur in any plant if a technician or working personnel does not pay proper attention to the job.

Plant Trip Due to Work on Incorrect Tag

Root Cause Analysis for Plant Trip Due to Work on Incorrect Tag

One of the units in the crude plant of a refinery had an issue with a pressure transmitter. The pressure transmitter was single-line equipment and was having issues with fluctuations.

So, maintenance activity for the pressure transmitter was planned. On the low-low pressure alarm of the pressure transmitter, a pump was having an interlock.

The pump will trip on the low-low pressure alarm. A total of three pumps were installed in the same area for the same purpose.

All the transmitters of these 3 pumps were installed in a single skid together. During the activity on the pressure transmitter of pump A, pump B tripped.  

So, what can be the reason for the tripping of pump B?

The technician verified the pressure transmitter on which the job was to be done. The tag number of the pressure transmitter (PT-A) matched with the tag number mentioned on the permit (PT-A).

As soon as the technician isolated the pressure transmitter from the manifold, the pressure of pump B went to 0.5 kg/cm2 on the graphics.

At the same time, pump B tripped. Hence, work on the incorrect tag was clear.

But when the Engineers went to see the pressure transmitter, the tag on which the technician was working was correct.

So further checking was planned. The impulse tube of the pressure transmitter was traced. On tracing the impulse tube, it was observed that the pressure transmitter was connected to pump B.

Also, the pressure transmitter of pump A was traced. It was observed that the pressure transmitter connected to pump A was different. The tag number of the pressure transmitter connected to pump A was PT-B.

Definitely, the tripping of pump B was due to incorrect tagging.

The tag painting was incorrect due to which the tripping of pump B occurred.

So how can we avoid such problems?

  1. Usually, the cables of every transmitter have an aluminum tagging. In this case, the aluminum tag plate was missing.
  2. Also, the display of some transmitters can be configured to show the tag number also. In this case, the tag number on display was left blank.
  3. One more thing to avoid such problems is that when we go for doing the job on any transmitter, always confirm the value with the panel engineer. The value in the field should match with the value on the graphics. This step will eliminate the work on the incorrect tag.
  4. Here for all 3 pumps, a common skid for mounting transmitters was given. So, during the commissioning phase, try to separate a group of transmitters for dedicated equipment.

If you liked this article, then please subscribe to our YouTube Channel for Electrical, Electronics, Instrumentation, PLC, and SCADA video tutorials.

You can also follow us on Facebook and Twitter to receive daily updates.

Read Next:

You've successfully subscribed !

View Comments

  • Good Day,
    i am following the issued technical topics which have very good issues i am now little bit busy but in coming future i will try to write some good
    thinks a lot for your great effort

Share

Recent Articles

  • PLC Tutorials

Batch Mixing with PLC Ladder Logic Program

In this example, we will learn batch mixing with PLC ladder logic program using timer…

1 week ago
  • PLC Tutorials

PLC Example on Manufacturing Line Assembly

This PLC example on manufacturing line assembly is an intermediate-level PLC program prepared for the…

2 weeks ago
  • PLC Tutorials

PLC Programming Example with Pushbutton and Motor

In this article, you will learn the PLC programming example with pushbutton and motor control…

3 weeks ago
  • PLC Tutorials

Boolean Logic to PLC Programming

This article teaches how to convert Boolean logic to PLC programming ladder logic with the…

4 weeks ago
  • PLC Tutorials

PLC Programming Example on Timers Function Block

In this article, you will learn the PLC programming example on timers function block using…

3 weeks ago
  • PLC Tutorials

PLC Pump Control: 10 seconds ON & 20 seconds OFF

Design a program for PLC pump control such that the pump must be turned ON…

2 weeks ago