Problem on PLC, HMI, VFD, and Motor Circuit

In this system a variable-frequency drive (VFD) sends AC electrical power to an induction motor to control the speed of that motor.

The VFD receives its “command” signal in the form of a 4-20 mA DC current sent from a programmable logic controller (PLC) with an analog output card, 4 mA representing a “zero-speed” signal (no power sent to the motor) and 20 mA representing a “full speed” signal (60 Hz power sent to the motor):

Problem on PLC HMI VFD

Unfortunately, though, there is something wrong with this system. The pump does not run, regardless of what the operator commands using the touch-screen panel. When you examine the VFD faceplate, you see a few LED indicators lit, but nothing either confirming or denying that power is reaching the motor.

Supposing the only test equipment available to you is a digital multimeter (DMM), what diagnostic tests could you perform to identify the location and nature of the system fault?

Share Your ideas on solving the problem with us through comments.

Scroll down to read the ideas shared by the users.

If you liked this article, then please subscribe to our YouTube Channel for PLC and SCADA video tutorials.

You can also follow us on Facebook and Twitter to receive daily updates.

Credits: Tony R. Kuphaldt

You've successfully subscribed !

View Comments

  • Hi, may I suggest that the whole power is to be shut down including its main switch, wait for 30seconds then restart by switching the main switch to on to enable the system restart

  • here is the steps to find out the cause

    1. Need to Measure 3 phase supply is coming to VFD or not.

    2. If 3 phase supply is available to VFD, need to turn on the motor through HMI , check 3 phase output is reaching to motor or not

    3. If 3 phase output is reaching to motor then VFD is fine and something wrong with motor

    4.If 3 phase output not reaching to motor then something wrong with VFD or power cables between VFD output terminal & motor input terminals

    5. After tun the motor ON from HMI Check whether VFD output is giving output or not

    6. If the VFD output is not giving output then something wrong wth VFD parameters settings

    7. If VFD output is giving output & power not reaching it to motor then need to check power cables between VFD & motor.

    • Please am facing some challenge i have done all my checks and the output of the vfd is giving me power the parameter setting are all right but still the motor is not running on the vfd display settings can u help me with that

  • First I would use DMM to check if the VFD is getting it's start signal from HMI, probably 120v from PLC digital output card.

    If that is good I would then use the DMM to check VFD input for 4 to 20 ma. Need to make sure the 4 to 20 ma analog output card on PLC is good. Then I would use the DMM to check the fail to start relay to see if it is tripped.

    If that is good I would use the DMM to check for 120 V at the motor starter relay. If the motor starter relay has voltage I would use DMM to check to see if 480 V is being applied to motor.

    • I would not use just a DMM as they do not draw enough current to test for a reliable source of supply. Use a "low impedance" setting on your DMM, or load the circuit with a resitor in parallel with the Voltmeter, say 5 000 Ohms. Loading the circuit will show up any poor connections.

  • Inspect for any error on VFD or HMI. If no alarm present.

    Do following step.

    1. Check incoming AC voltage using DMM at VFD panel.

    2. Verify control loop for start and stop signal and speed input to VFD. If it is normal and all signal are recieving at VFD termination point then only thing to check is VFD settings and parameters.

  • 1- 1st of all we must know if the enable signal reach the VFD or not either by DO from the PLC or by enable key in the VFD (according to your wiring).

    2- For the 4-20ma you can check the VFD LCD you must find the equivalent HZ to this analog signal.

    3- you must check VFD configurations such as the enable signal, run soure fixed speed or 4-20ma.

    4- By the DMM you can check the 3 phase input voltage to the VFD if you found it and not found any voltage in the output of the VFD to the motor. So the problem in the VFD, and you must check by following the A/M points.

  • The output voltage and input voltages can be measured using the multimeter.we can know the faults with the power supply of there is any else there might be a problem with the output of the PLC it can be measured using the multimeter in DC voltage mode.
    If any of these fails there might be a problem with PLC or the VFD itself.

  • Make sure polarity of 4-20 is correct. simple stuff first. then you can start trouble shooting the higher voltage.

  • First check analog o/p dcs coming 25% check mA, Note amps and check on command ofter all are ok main supply off wait some time after-on test all, check all interlocks healthy and control supply check.

  • as per my knowledge, its no longer helpful feeding a pump application motor by VFD, only DOL is more than enough though run by PLC & HMI

  • With using a digital multimeter, I start checking the signals input in VFD coming from plc, if it greater than 4 mA I must check the vdf output to the motor, if there is no output voltage then I must check the setting of vfd

Share

Recent Articles

  • PLC Tutorials

Water Fountain Control Logic – PLC Exercises and Solutions

Learn the water fountain control logic using the PLC timers programming to control the high…

4 weeks ago
  • Control Systems

What is Open Telemetry? – Principles and Benefits

Open Telemetry is a framework for collecting data in cloud-native applications including tracing, metrics, and…

6 days ago
  • Common

Control of Pneumatic Cylinder and Motor

This article is about controlling the Pneumatic cylinder and Pneumatic motor in the assembly line…

1 week ago
  • PLC Tutorials

Network Switch Requirement in SCADA and DCS Architecture

In this post, we will learn the basic requirements for a network switch to be…

6 days ago
  • PLC Tutorials

PLC Panel and MCC Panel Interface Signals

The PLC panel and MCC panel interface signals are start, stop, run feedback, trip, local…

1 week ago
  • PLC Tutorials

Shutter Door Control using Motor and Limit Switches

 In this article, we are going to discuss about shutter door control using induction motor…

1 week ago