Flow Measurement

Orifice Flowmeter Rangeability

Orifice, combined with differential pressure transmitter, is the most used flow measurement device in oil & gas plants because of its low cost and its ease of installation and maintenance.

Flowmeter Rangeability

However, the orifice only allows 3:1 rangeability to maintain accuracy. This means, if one wants to measure a maximum flow of 10 MMscfd, then the minimum flow measurement that could be measured is only 3.3 MMscfd.

According to the Bernoulli principle, the relationship between the flow and pressure drop of fluid passing through an orifice is given by the following formulae:

Orifice Formulae

Q = Volumetric flowrate
dP = Measured pressure drop ρ = Density
Ao = Cross-sectional orifice area
Cf = Constant

Hence, flow value could be obtained by measuring pressure drop and the relationship between them is a square root.

Let’s say the orifice is intended for flow measurement of 0-10 MMscfd which is represented by 0-100 inH2O pressure drop (as shown below the curve)

At a maximum flow of 10 MMscfd, a change of 1% of full flow (0.1 MMscfd) to 9.9 MMscfd will be represented by a change of 2% of DP (from 100 inH2O to 98.01 in H2O).

The following table summarizes the value of flow, its corresponding pressure drop, and its dP change in percentage of full scale for a 1% change of full flow at the specified flow.

The less flow to be measured, the more sensitivity suffers.

If you liked this article, then please subscribe to our YouTube Channel for Instrumentation, Electrical, PLC, and SCADA video tutorials.

You can also follow us on Facebook and Twitter to receive daily updates.

Read Next:

You've successfully subscribed !

View Comments

  • The statement "orifice only allows 3:1 rangeability to maintain accuracy" is not clear. You haven't explained why you are considering 3:1 rangeability for orifice plate. Also you haven't explained what is the accuracy for Orifice plate measurement you have considered here.

    You may be knowing that using a multivariable transmitter, the rangeability of orifice plate can be increased to 10:1. Without multivariable orifice by changing the transmitter or by changing the orifice plate itself the rangeability of orifice can be increased substantially. In industry we are doing it frequently.

Share

Recent Articles

  • PLC Tutorials

Conveyor Sorting Machine PLC Program with Calculation Function

The conveyor sorting machine is widely used in the packing industries using the PLC program…

4 days ago
  • PLC Tutorials

Example of Flip-Flop PLC Program for Lamps Application

Learn the example of flip-flop PLC program for lamps application using the ladder logic to…

4 days ago
  • PLC Tutorials

STAR DELTA Programming using PLC Controller

In this article, you will learn the STAR DELTA programming using PLC controller to start…

5 days ago
  • Instrumentation Design

Single and Three Phase Immersion Electrical Heaters Wiring Circuits

Lube oil consoles of rotary equipment packages in industrial process plants are usually equipped with…

2 days ago
  • Instrumentation Design

Immersion Heaters in Lube Oil Consoles

Rotating equipment packages such as pumps, compressors, turbines need the lube oil consoles for their…

4 days ago
  • PLC Tutorials

How to Blink Lights in Ladder Logic?

This article explains how to blink lights in ladder logic with a detailed explanation video…

4 weeks ago