Loop Calibrator to Simulate a 4-20 mA Signal

Suppose a technician wishes to use a loop calibrator to simulate a 4-20 mA signal to a controller, and decides to connect the loop calibrator to the circuit like this:

Loop Calibrator to Simulate a 4-20 mA Signal

Loop Calibrator to Simulate a 4-20 mA Signal

Explain why this is an improper use of the loop calibrator, and what will happen if the technician tries to simulate a 9 mA signal this way. Finally, identify the proper way to use the loop calibrator to simulate a transmitter signal.

Share your answers with us through comments.

Read Next:

Credits: Tony R. Kuphaldt

You've successfully subscribed !

View Comments

  • The calibrator is not even in closed loop and it is connected as a parallel dc source which will add more mili amps to the instrument additional to the controller mamps supply. Thus the operation of the instrument will be not as expected.

  • Once we have simulate the mA values to the DCS with probes directly to the 24v dc cores without the connection in the tx.

Share

Recent Articles

  • PLC Tutorials

Batch Mixing with PLC Ladder Logic Program

In this example, we will learn batch mixing with PLC ladder logic program using timer…

1 week ago
  • PLC Tutorials

PLC Example on Manufacturing Line Assembly

This PLC example on manufacturing line assembly is an intermediate-level PLC program prepared for the…

2 weeks ago
  • PLC Tutorials

PLC Programming Example with Pushbutton and Motor

In this article, you will learn the PLC programming example with pushbutton and motor control…

3 weeks ago
  • PLC Tutorials

Boolean Logic to PLC Programming

This article teaches how to convert Boolean logic to PLC programming ladder logic with the…

4 weeks ago
  • PLC Tutorials

PLC Programming Example on Timers Function Block

In this article, you will learn the PLC programming example on timers function block using…

3 weeks ago
  • PLC Tutorials

PLC Pump Control: 10 seconds ON & 20 seconds OFF

Design a program for PLC pump control such that the pump must be turned ON…

2 weeks ago