Inst ToolsInst ToolsInst Tools
  • Courses
  • Automation
    • PLC
    • Control System
    • Safety System
    • Communication
    • Fire & Gas System
  • Instrumentation
    • Design
    • Pressure
    • Temperature
    • Flow
    • Level
    • Vibration
    • Analyzer
    • Control Valve
    • Switch
    • Calibration
    • Erection & Commissioning
  • Interview
    • Instrumentation
    • Electrical
    • Electronics
    • Practical
  • Q&A
    • Instrumentation
    • Control System
    • Electrical
    • Electronics
    • Analog Electronics
    • Digital Electronics
    • Power Electronics
    • Microprocessor
  • Request
Search
  • Books
  • Software
  • Projects
  • Process
  • Tools
  • Basics
  • Formula
  • Power Plant
  • Root Cause Analysis
  • Electrical Basics
  • Animation
  • Standards
  • 4-20 mA Course
  • Siemens PLC Course
Reading: 4-20 mA Loop Splitter
Share
Notification Show More
Font ResizerAa
Inst ToolsInst Tools
Font ResizerAa
  • Courses
  • Design
  • PLC
  • Interview
  • Control System
Search
  • Courses
  • Automation
    • PLC
    • Control System
    • Safety System
    • Communication
    • Fire & Gas System
  • Instrumentation
    • Design
    • Pressure
    • Temperature
    • Flow
    • Level
    • Vibration
    • Analyzer
    • Control Valve
    • Switch
    • Calibration
    • Erection & Commissioning
  • Interview
    • Instrumentation
    • Electrical
    • Electronics
    • Practical
  • Q&A
    • Instrumentation
    • Control System
    • Electrical
    • Electronics
    • Analog Electronics
    • Digital Electronics
    • Power Electronics
    • Microprocessor
  • Request
Follow US
All rights reserved. Reproduction in whole or in part without written permission is prohibited.
Inst Tools > Blog > Control Systems > 4-20 mA Loop Splitter

4-20 mA Loop Splitter

Last updated: June 29, 2019 3:12 pm
Editorial Staff
Control Systems Instrumentation Design
4 Comments
Share
6 Min Read
SHARE

4-20 mA Loop Splitter

Problems with Current Loop Loads in Series

Problems with Current Loop Loads in Series

Contents
4-20 mA Loop SplitterLoop Splitter / Retransmitter SolutionTheory of OperationApplication

Not so good:  A single 4-20 mA loop from a sensor is connector to a panel meter, a external control valve, a recorder, a local controller, a local switch, a third party data logger and a PLC in series. If the loop opens, all devices in the loop fail.

  1. All devices in the loop cannot share a common ground, but must be electrically floating. This is often not possible.
  2. When any device in a loop is removed, fails, or if a wiring fault occurs, all other devices in the loop loose their 4-20 mA signal.
  3. The transmitter(signal conditioner) voltage compliance limit may be exceeded, since the voltage drops across loads in series are additive.
  4. The 4-20 mA signal to each load device cannot be individually adjusted for calibration purposes.
  5. There are not diagnostics for the current to each load.

Loop Splitter / Retransmitter Solution

Why a Loop Splitter is Needed ?

In many industrial systems, the same 4-20 mA signal from a transmitter is sent to multiple devices in series, such as panel meters, chart recorders and PLCs, as shown below. When any device in the loop is removed, fails, or suffers a wiring fault, all other devices will then also lose their 4-20 mA signal.

Loop Splitter with output load

Much better:  Four independent 4-20 mA loops with ±10V common mode isolation. If any of the output loops opens, only a single device is affected. The output loops can share a common ground.

  1. Sources up to four (4) independently adjustable 4-20 mA outputs from a single input, which can be 4-20 mA, 1-5V, 0-5V or 0-10V, as selected by jumpers. ( Note : Number of outputs depends on loop splitter model )
  2. If any device in an output loop is removed from a loop or fails, or if a wiring fault occurs in any loop, the other loops continue to operate properly.
  3. Signal input and outputs can share a common signal ground.
  4. Common mode volage of output loops is ±10V by means of active circuity so that remote grounds can vary by up to ±10V.
  5. Each loop only drives a single load, thus avoiding voltage compliance problems.
  6. ±10% of zero and span adjustment are provided for each output loop to allow for independent loop calibration.
  7. Diagnostics for each output loop are provided by a yellow LED lamp to indicate loop continuity and by a test point across a 10Ω series resistor, where 200 mV corresponds to 20 mA. The test point allows a multimeter to measure the loop current without breaking the loop.
  8. Power for the loop splitter can be 85-264 Vac or low voltage 10-48 Vdc or 12-32 Vac (Vary from model to model). An excitation output is provided on the signal input side to drive a 2- or 3-wire transmitter at 24 Vdc up to 30 mA.

Theory of Operation

4-20 mA Loop Splitter

The loop splitters convert a 4-20mA process current input into two/four identical isolated 4-20mA output signals. Power is obtained from the output loop (sinks current).

Each channel operates independently to prevent interaction between channels. Galvanic isolation eliminates ground loops, reduces noise, and blocks transient signals. Splitters are available in 2-wire loop-powered and 4-wire AC/DC-powered models.

The loop powered model runs on 12-50 VDC power from the output loop, has a built-in isolated excitation supply with short circuit protection, and can drive up to two/four field 2-wire process loops.

Galvanic & Active Isolation:

A single input current loop is split into four independent output loops I1, I2, I3 and I4 by four current generators. The input and output signals are galvanically isolated from power and earth grounds by up to 264 Vac.

Active circuitry allows a common mode voltage up to ±10V between Local Signal Ground (on pins 1) and the Remote Grounds.

Each common mode volt­ages, labeled CMV1 to CMV4 in the dia­gram, reflects the actual voltage difference between Local Signal Ground and the Remote Ground. Such differ­ences can be caused by current flows in the factory.

Floating loads:

Any output load R that is floating (not connected to Earth Ground or a Local Ground) can be connected between current output (Pin 1) and current return (Pin 2). Current return is internally tied to Signal Ground, which can be floating or be connected to Earth Ground.

Grounded loads:

Any output load R can be connected to a Local Ground instead of current return. The Remote Grounds can each be different, but can only differ from Signal Ground by a safe common mode voltage CMV. Signal Ground should be tied to Earth Ground to minimize noise pickup.

Application

  • Isolation and conversion of standard DC signals.
  • Galvanic separation of analog current and voltage signals. Elimination of ground loops and measurement of floating signals.
  • A competitive choice in terms of both price and technology for galvanic isolation of current and voltage signals to SCADA systems or PLC equipment.
  • Installation in ATEX Ex zone 2 / IECEx zone 2 / FM division 2. Suitable for environments with high vibration stress

Source : laurels

Don't Miss Our Updates
Be the first to get exclusive content straight to your email.
We promise not to spam you. You can unsubscribe at any time.
Invalid email address
You've successfully subscribed !

Continue Reading

Hardwired I/O and Serial I/O – Differences Explained
Motor Control Circuit Wiring
How-to Create Instrument Loop Diagram (ILD)?
Compare Modbus, Fieldbus, and Profibus
Explaining Various Types of Analog Instruments
NACE Standards – MR0103 Vs MR0175
Share This Article
Facebook Whatsapp Whatsapp LinkedIn Copy Link
Share
4 Comments
  • Muhammad zarif says:
    March 2, 2017 at 11:25 am

    U r awesome dear .pls keep it up. Really hardworking . best of wishes.

    Reply
  • sethh says:
    May 15, 2017 at 5:46 pm

    very good can u mail me the documents

    Reply
  • Benjamin Kaul says:
    January 8, 2019 at 4:09 am

    I came across this few weeks ago. The notes really explain it well

    Reply
  • Selig says:
    September 29, 2023 at 4:20 pm

    Hi, may i have 1 signal of 4 to 20mA input to more than 4 isolated 4 to 20mA output? For example: 14 outputs.

    Reply

Leave a Reply Cancel reply

Your email address will not be published. Required fields are marked *

Stay Connected

128.3kFollowersLike
69.1kFollowersFollow
210kSubscribersSubscribe
38kFollowersFollow

Categories

Explore More

What is the thermal effect on Sensors?
Self-regulating Processes – Liquid Flow Control
Why Orifice Flow Meter Flange is Not Recommended 150# Rating?
Technical Evaluation for DCS and ESD – Distributed Control System
Difference between DCS, PLC, and RTU ?
Foundation Fieldbus Split Range Valves
Analysis of HART communicator and Smart HART Transmitter
Boiler Three Element Controller Philosophy

Keep Learning

Pressure Gauge Design

How to Select a Pressure Gauge

Selector Control Function in DCS

Selector Control Functions

SCADA RTU TELEMETRY

SCADA & Telemetry Systems

Alarm Management Practices

Control Room Alarm Management Practices

Thermowell Immersion Length

Thermowell Insertion and Immersion Length

CAN Protocol with the OSI Model

Basics for CAN Bus Protocol – Controller Area Network

Open Platform Communication (OPC)

Open Platform Communication (OPC)

Interlock Philosophy

Types of Interlocks

Learn More

Control Systems Questions & Answers

Control Systems Objective Questions & Answers – Set 5

Temperature Transmitter Foundation Fieldbus Configuration

Foundation Fieldbus Temperature Transmitter Configuration

harmonics-disadvantages-in-power-system

Harmonics Disadvantages in Power System

Power Electronics objective questions and answers

Top 50 Power Electronics Quiz

PLC Program for Temperature Control using Thermostat

PLC Program for Temperature Control using Thermostat

reverse-biased varactor diode

Varactor Diode Operation

Best Instrumentation Engineering Books to Purchase

Best Instrumentation Engineering Books to Purchase

Configuration of Siemens VFD Using TIA Portal

Configuration of Siemens VFD Using TIA Portal Start drive

Menu

  • About
  • Privacy Policy
  • Copyright

Quick Links

  • Learn PLC
  • Helping Hand
  • Part Time Job

YouTube Subscribe

Follow US
All rights reserved. Reproduction in whole or in part without written permission is prohibited.
Welcome Back!

Sign in to your account

Username or Email Address
Password

Lost your password?