Ultrasonic Tank Gauging

Ultrasonic Tank Gauging is a non-contacting level measurement method. The sensors emit acoustic frequency waves in the range of 20 kHz to 200 kHz that is reflected back from the liquid surface and detected by the emitting transducer.

Ultrasonic level sensors can be affected (due to the change of speed of sound) by factors such as moisture, temperature, and pressures. To overcome this, correction factors are applied to the level measurement to improve measurement accuracy.

Ultrasonic Tank Gauging

Ultrasonic Tank Gauging

Figure: Simple diagram to demonstrate an ultrasonic level measurement system

Mounting and positioning of the ultrasonic transducer is key to ensuring the best response to reflected transmissions. Additionally, the tank should be relatively free of obstacles such as brackets or ladders so that false returns are minimized.

A widely recorded shortcoming of ultrasonic tank gauging systems is that they are susceptible to ringing. This occurs when the transmitted signal is reflected back to the transducer from an unintended surface, namely a surface other than that of the liquid in the tank. Ringing can be compensated for and, in a lot of cases, minimized so that it has a negligible impact on measurement accuracy.

An additional shortcoming is that it has been widely accepted throughout the industry that non-contacting ultrasonic devices are erroneous when used in vacuumed nitrogen blanketed storage tanks. Accuracy can be improved by having a fixed reference point within the tank and to instead continuously monitor the changes in level with respect to this fixed point .

This tank level measurement system is relatively cheap when compared to alternative systems that offer comparable accuracy.

This method of level measurement is widely viewed as being inaccurate; this is caused by the effect that gasoline vapor has upon the measurement. Both system manufacturers and system solution designers and installers have stated that this technology should not be used on gasoline or any fuel storage tanks.

References: Lewis WA (1994) Confusion Over Tank Gauging. Control and Instrumentation 1994, volume 26, Issue 9, pp11

Read Next:

You've successfully subscribed !
Share

Recent Articles

  • PLC Tutorials

From Boolean Algebra to PLC Logic

In this article, a simple example will teach you the conversion from Boolean algebra to…

1 month ago
  • PLC Tutorials

PLC Cooking Timer Example for Kitchen Automation

In this article, you will learn the PLC cooking timer example for kitchen automation using…

3 weeks ago
  • PLC Tutorials

Example PLC Program to Control a Pump based on Level Sensors

Learn an example PLC program to control a pump based on level sensors using ladder…

3 weeks ago
  • PLC Tutorials

PLC Timer Application in Security Camera Recording

In the PLC timer application for security camera recording, when motion is detected then camera…

2 weeks ago
  • PLC Tutorials

Batch Mixing with PLC Ladder Logic Program

In this example, we will learn batch mixing with PLC ladder logic program using timer…

2 weeks ago
  • PLC Tutorials

PLC Example on Manufacturing Line Assembly

This PLC example on manufacturing line assembly is an intermediate-level PLC program prepared for the…

3 weeks ago