Practical Questions

Solenoid-controlled Valve Problem

Suppose this solenoid-controlled valve refuses to move when the operator pushes the switch. Whether the switch is pressed or unpressed, the control valve remains in the fully-closed (down) position:

Solenoid-controlled Valve Problem

Solenoid-controlled Valve Problem

Another technician has already measured voltage between terminals H1 and H4 on the transformer, and 0 volts between terminals D and X1, in both pushbutton switch positions. At that point, he gave up and left the system for you to troubleshoot.

Identify the below-mentioned faults are possible to happen or not.

  • Fuse F3 blown (failed open)
  • Solenoid stuck in “energized” position
  • Solenoid stuck in “de-energized” position
  • Solenoid coil failed open
  • Solenoid coil failed shorted
  • Silencer plugged
  • Vent cap plugged
  • Wire open between terminals A and E
  • Wire open between terminals C and H
  • Wire open between terminals K and B
  • Valve V1 shut
  • Valve V2 shut

Identify the likelihood of each specified fault for this system. Consider each fault one at a time (i.e. no coincidental faults), determining whether or not each fault could independently account for all measurements and symptoms in this system.

Finally, identify the next diagnostic test or measurement you would make on this system.

Explain how the result(s) of this next test or measurement help further identify the location and/or nature of the fault.

Solenoid-controlled Valve Solution

A plugged vent on the valve actuator, while in theory capable of limiting the control valve’s upward motion, would not prevent any motion at all from occurring when full pressure is applied to the bottom of the diaphragm. This is why “Vent cap plugged” is checked as impossible rather than possible for this scenario.

A good “next test” would be to crack the fitting at port “C” of the solenoid valve. If there is pressure, it means the problem must lie past the solenoid (e.g. valve V1 shut, or a problem in the process control valve).

If there is no pressure at that point, either the solenoid valve is stuck in the “energized” position or there is a lack of supply pressure to the solenoid.

FaultsPossibleImpossible
Fuse F3 blown (failed open)
Solenoid stuck in “energized” position
Solenoid stuck in “de-energized” position
Solenoid coil failed open
Solenoid coil failed shorted
Silencer plugged
Vent cap plugged
Wire open between terminals A and E
Wire open between terminals C and H
Wire open between terminals K and B
Valve V1 shut
Valve V2 shut

Share your answers with us through the below comments section.

Read Next:

Credits: Tony R. Kuphaldt

You've successfully subscribed !

View Comments

Share

Recent Articles

  • PLC Tutorials

From Boolean Algebra to PLC Logic

In this article, a simple example will teach you the conversion from Boolean algebra to…

1 month ago
  • PLC Tutorials

PLC Cooking Timer Example for Kitchen Automation

In this article, you will learn the PLC cooking timer example for kitchen automation using…

3 weeks ago
  • PLC Tutorials

Example PLC Program to Control a Pump based on Level Sensors

Learn an example PLC program to control a pump based on level sensors using ladder…

3 weeks ago
  • PLC Tutorials

PLC Timer Application in Security Camera Recording

In the PLC timer application for security camera recording, when motion is detected then camera…

3 weeks ago
  • PLC Tutorials

Batch Mixing with PLC Ladder Logic Program

In this example, we will learn batch mixing with PLC ladder logic program using timer…

2 weeks ago
  • PLC Tutorials

PLC Example on Manufacturing Line Assembly

This PLC example on manufacturing line assembly is an intermediate-level PLC program prepared for the…

3 weeks ago