Suppose you wish to calibrate a pneumatic pressure transmitter to an input range of 0 to 200 inches of water, with an output range of 3 to 15 PSI.
Complete the following calibration table showing the test pressures to use and the allowable low/high output signals for a calibrated tolerance of +/- 0.5% (of span):
If the operator happens to read a process pressure of 153 inches W.C. at the indicator, how far off might the actual process pressure be from this indicated value?
Given the tolerance of ± 0.5% of the 200” span (± 1”), the actual process pressure could be as low as 152 ”W.C. or as high as 154 ”W.C.
Share with us the formula used for the above calculations using the below the comments section.
Examine the diagram for a Foxboro model 139PP pneumatic pressure repeater, then identify multiple faults which could cause this instrument to:
For each of your identified faults, explain why the pneumatic output signal pressure will be incorrect, and also identify how to correct the problem.
Reasons for the output pressure to be too low:
Reasons for the output pressure to be too high:
Credits: Tony R. Kuphaldt