PLC Tutorials

PLC Conveyor Motor Ladder Logic

PLC Programming Tutorials for PLC Conveyor Motor Ladder Logic or Conveyor Belt Control using a programmable logic controller (PLC).

PLC Conveyor Motor Ladder Logic

Objective: The sequential tasks as follows

  1. When START button pressed
  2. Motor will be started
  3. RUN (Green Lamp) indication lamp will be activated
  4. Motor Running, so Box will start Move
  5. Proximity Sensor will detect when the box arrives at other end
  6. Motor will be stopped
  7. RUN (Green Lamp) indication lamp will be de-activated
  8. STOP (Red Lamp) indication lamp will be activated
  9. An Emergency Stop push button will be used to stop the motor at any time.

Relay Schematic

Conveyor Relay Logic
  • R : STOP Indication lamp,
  • G : RUN Indication lamp,
  • M : Motor,
  • OL : Overload Relay (Motor Protection Relay),
  • LS1 : Proximity Switch,
  • PB1 : Start push button,
  • PB2 : Emergency Stop Pushbutton,
  • CR : Contractor Relay

Operational Sequence

  • Start button is actuated.
  • CR1-1 closes to seal in CR1 or to latch the start command
  • CR1-2 opens, switching the red stop pilot light off
  • CR1-3 closes, switching the green run pilot light on
  • CR1-4 closes to energize the motor starter and motor
  • The box/package moves, and proximity switch (LS1) detects the box when it reached and de-energize coil CR1
  • CR1-1 opens to open the seal-in contact ( unlatched start command)
  • CR1-2 closes, switching the red pilot light on
  • CR1-3 opens, switching the green pilot light off
  • CR1-4 opens to de-energize the starter coil, stop the motor, and end the sequence

PLC Ladder Logic

If you liked this article, then please subscribe to our YouTube Channel for PLC and SCADA video tutorials.

You can also follow us on Facebook and Twitter to receive daily updates.

Read Next:

You've successfully subscribed !

View Comments

  • Start-stop motor control relay logic circuit.
    By pressing start button coil relay for magnetic contactor (CR1) and green lamp energized (G). By pressing stop, it will de-energized the coil relay for magnetic contactor (CR1) and the red lamp will ON (R).
    Please convert Relay Logic Circuit into PLC Logic Circuit through complete connection and details below by using the given inputs/outputs based on the given relay logic diagram.
    (INPUT) Stop – I:0.0 , Start – I:0.1
    (OUTPUT) CR1 – O:0.0 , G – O:-0.1 , R – O:0.2

  • Good Morning editorial team please kindly permit me the use of the PLC conveyor Motor ladder logic and Relay schematic in a Journal Article am working on with my HE student and Co-lecturer .

    Hope to hear from you

    Kind Regards

Share

Recent Articles

  • PLC Tutorials

Example PLC Program to Control a Pump based on Level Sensors

Learn an example PLC program to control a pump based on level sensors using ladder…

2 weeks ago
  • PLC Tutorials

PLC Timer Application in Security Camera Recording

In the PLC timer application for security camera recording, when motion is detected then camera…

2 weeks ago
  • PLC Tutorials

Batch Mixing with PLC Ladder Logic Program

In this example, we will learn batch mixing with PLC ladder logic program using timer…

2 weeks ago
  • PLC Tutorials

PLC Example on Manufacturing Line Assembly

This PLC example on manufacturing line assembly is an intermediate-level PLC program prepared for the…

2 weeks ago
  • PLC Tutorials

PLC Programming Example with Pushbutton and Motor

In this article, you will learn the PLC programming example with pushbutton and motor control…

3 weeks ago
  • PLC Tutorials

Boolean Logic to PLC Programming

This article teaches how to convert Boolean logic to PLC programming ladder logic with the…

1 month ago