Safety Instrumented System (SIS)

Pilot-operated Safety and Relief Valves

While many safety and relief valves actuate by the direct action of the process fluid forcing against the valve plug mechanism, others are more sophisticated in design, relying on a secondary pressure sensing mechanism to trigger and direct fluid pressure to the main valve assembly to actuate it.

This pressure-sensing mechanism is called a pilot, and usually features a widely-adjustable range to give the overall valve assembly a larger variety of applications.

In a pilot-operated over-pressure-protection valve, the “lift” pressure value is established by a spring adjustment in the pilot mechanism rather than by an adjustment made to the main valve mechanism.

Pilot-operated Safety and Relief Valves

A photograph of a pilot-operated pressure relief valve used on a liquid petroleum pipeline appears here:

Pilot-operated Safety and Relief Valves

This photograph courtesy of the National Transportation Safety Board’s report of the 1999 petroleum pipeline rupture in Bellingham, Washington. Improper setting of this relief valve pilot played a role in the pipeline rupture, the result of which was nearly a quarter-million gallons of gasoline spilling into a creek and subsequently igniting.

One of the lessons to take from this event is the importance of proper instrument maintenance and configuration, and how such technical details concerning industrial components may have consequences reaching far beyond the industrial facility where those components are located.

The relief valve mechanism itself is the white-painted flanged valve found in the center-right region of the photograph (RV-1919). This particular relief valve happens to be a Fisher model 760 with 8-inch, ANSI 300# flanges.

The actuating pilot mechanism is the small unit connected to the relief valve body via stainless-steel tubing. When this pilot senses fluid pressure in the pipeline exceeding the lift pressure, it switches fluid pressure to the piston actuating mechanism of the main relief valve, opening it to relieve fluid pressure from the pipeline.

Thus, the lift pressure value for the relief valve is set within the pilot rather than within the main valve mechanism. Altering this lift pressure setting is a matter of adjusting spring tension within the pilot mechanism, and/or replacing components within the pilot mechanism.

Comparison to non piloted pressure relief valves

Advantages

  • Smaller package on the larger pipe sizes.
  • More options for control.
  • Seals more tightly as the system pressure approaches but does not reach set pressure.
  • Control pilot can be mounted remotely.
  • Some designs allow for changes in orifice size within the main valve.
  • Can be used in engines.

Disadvantages

  • More complex, resulting in various fail-open failure modes.
  • More expensive at smaller sizes (starts to even out as pipe size increases).
  • Small parts in pilot valve are sensitive to contaminant particles.

Articles You May Like :

Pneumatic Instrumentation

Pressure Transmitter Manifolds

Insertion flow meters

What is Magnetic Tape Recorder ?

P&ID for Pumps Heat Exchangers

De-energize to Safe Loop philosophy

You've successfully subscribed !
Share

Recent Articles

  • PLC Tutorials

PLC Ladder Logic Design: Control 3 Motors with Toggle Switch

PLC ladder logic design to control 3 motors with toggle switch and explain the program…

3 weeks ago
  • PLC Tutorials

VFD Simulator Download – Free Yaskawa V1000 Software

VFD simulator download: Master the online tool from the Yaskawa V1000 & programming software for…

3 days ago
  • PLC Tutorials

Conveyor Sorting Machine PLC Program with Calculation Function

The conveyor sorting machine is widely used in the packing industries using the PLC program…

6 days ago
  • PLC Tutorials

Example of Flip-Flop PLC Program for Lamps Application

Learn the example of flip-flop PLC program for lamps application using the ladder logic to…

6 days ago
  • PLC Tutorials

STAR DELTA Programming using PLC Controller

In this article, you will learn the STAR DELTA programming using PLC controller to start…

7 days ago
  • Instrumentation Design

Single and Three Phase Immersion Electrical Heaters Wiring Circuits

Lube oil consoles of rotary equipment packages in industrial process plants are usually equipped with…

4 days ago