HT motors Corrosion Problem

Motors ventilating tubes severe corrosion posed problems are:

  1. Fan blown air carried hygroscopic corrosive dust corroded and stuck hard to the carbon steel ventilating air tubes
  2. Consequent reduced winding cooling and in turn high windings temperature especially in the motors with no winding temperature indicator threatened premature winding burnouts
  3. Holes seen on the tubes after 5-years despite anti-corrosive bore painting added to the above threats and demanded immediate solution

Authors Solution

After several deep-thinking days the author proposed the below given solutions:

  1. Re-tube the motors with thinner walled SS-316 SS tubes; his reasons are:
  2. Air velocity and turbulence influence heat transfer most and tube material thermal conductivity least.
  3. SS does not corrode; hence no non-cleanable hard-stuck and poor thermal conductivity dust coated tube bores → better than design heat transfer effective winding cooling → acceptable winding temperatures → vanished winding burnout threats

A lesson learnt

Expanding the tubes without the end-shields in position in the first instance distorted the motor frame; hence the motor body necessary extensive repairs delayed the motor reassembly by a month and absent spare motor threatened long plant shutdowns (SDs).

Having learnt the lesson the hard way, the crew re-tubed with end shields in position, did not expand the tubes but just m-seal sealed the tubes to motor body joints as the author advised. 

RCA solution Benefits:

Implementing RCA solution Benefits are

  1. Thanks to no corrosion, the dust did not stick hard to the tube bores
  2. Hence, during plant cleaning shutdowns long brushes removed most of the dust
  3. Water soaked squeegee brush mop out followed by dry squeegee mop out tubes were metal clean
  4. These steps preserve the designed in winding cooling; hence winding burnout threats vanished forever.

Author: S. Raghava Chari

Do you face any similar issues? Share with us through the below comments section.

If you liked this article, then please subscribe to our YouTube Channel for Instrumentation, Electrical, PLC, and SCADA video tutorials.

You can also follow us on Facebook and Twitter to receive daily updates.

Read Next:

You've successfully subscribed !
Share

Recent Articles

  • PLC Tutorials

Example PLC Program to Control a Pump based on Level Sensors

Learn an example PLC program to control a pump based on level sensors using ladder…

2 weeks ago
  • PLC Tutorials

PLC Timer Application in Security Camera Recording

In the PLC timer application for security camera recording, when motion is detected then camera…

2 weeks ago
  • PLC Tutorials

Batch Mixing with PLC Ladder Logic Program

In this example, we will learn batch mixing with PLC ladder logic program using timer…

2 weeks ago
  • PLC Tutorials

PLC Example on Manufacturing Line Assembly

This PLC example on manufacturing line assembly is an intermediate-level PLC program prepared for the…

2 weeks ago
  • PLC Tutorials

PLC Programming Example with Pushbutton and Motor

In this article, you will learn the PLC programming example with pushbutton and motor control…

3 weeks ago
  • PLC Tutorials

Boolean Logic to PLC Programming

This article teaches how to convert Boolean logic to PLC programming ladder logic with the…

1 month ago