Level Measurement

DP Transmitter Dry Leg & Wet Leg Calculations

In any process industry, level measurement is very important for safety and process purpose.

The level can be measured by two methods.

  1. Direct method
  2. Indirect method

Here we discuss the indirect method and which is using DP transmitter for level measurement.

A Differential pressure transmitter is a common and well-understood technology for liquid level measurement. If the tank is closed or pressurized, a DP measurement must be made to compensate for the vessel pressure.

DP Transmitter Level Measurement for Closed Tank

In closed tank DP level measurement,  LP leg is connected to the top of tank.

There are two methods in closed tank DP Level Measurement.

Dry leg method:

Dry leg method is used in normal close tank where vapor is not condensate and temperature of process is equal to atmospheric.

Wet leg method:

Wet leg method is used where vapor has a tendency to make the condensate and temperature of process is high or low from the atmospheric .

For DP Transmitter Configuration, we have to find out Zero Level & Span Level. Accordingly we have to configure Lower Range Value (LRV) and Upper Range Value (URV) using HART communicator.

DP Transmitter Level Measurement for Closed Tank – Dry Leg Method

Simply when LP side of the DP transmitter is filled with any gas/air then we call it as Dry Leg & we apply Dry Leg Method for calculations.

DP Transmitter Level Measurement for Closed Tank Dry leg Method

At zero level (LRV) = pressure acting on HP leg – Pressure acting on LP leg

=H2 x specific gravity – 0

= 200 x 0.9 – 0

= 180 mmwc

At 100 % level (URV) = pressure acting on HP leg – Pressure acting on LP leg

= (H2+H1) x specific gravity – 0

= (200 + 500) x 0.9 – 0

= 630 mmwc

Range = URV – LRV = 630 – 180 mmwc = 450 mmwc

So, we have to set Lower Range Value (LRV) = 180 mmwc and Upper Range Value (URV) = 630 mmwc in the DP Transmitter using HART communicator.

DP Transmitter Level Measurement for Closed Tank – Wet Leg Method

Simply when LP side of the DP transmitter is filled with liquid then we call it as Wet Leg & we apply Wet Leg Method for calculations.

Y = H1 +H2 = 500 + 200 = 700 mm
At zero level (LRV) = pressure acting on HP leg – Pressure acting on LP leg

= H2 x SG1 – Y x SG2

= 200 x 0.9 – 700 x 1.0

= 180 – 700

= – 520 mmwc

At 100 % level (URV) = pressure acting on HP leg – Pressure acting on LP leg

= (H2+H1) x SG1 – Y x SG2

= (200 + 500) x 0.9 – 700 x 1.0

 = 630 – 700

= -70 mmwc

Range = URV – LRV = -70 – (-520) = 450 mmwc

So, we have to set Lower Range Value (LRV) = -520 mmwc and Upper Range Value (URV) = -70 mmwc in the DP Transmitter using HART communicator.

Author: Ashish Agrawal

Articles You May Like:

You've successfully subscribed !

View Comments

  • Dear Sir
    I have question, why you neglect the LP side When you do a calculation on a dry leg mode? could you explaine that to me please?

    Best regards
    Ahmed

    • when we consider a dry leg, it means that LP side is subject to only Vapor / gas pressure, in the other hand the vapor/gas pressure is applied to both sides (LP and HP). so we don't consider it (ie. the vapor/gas pressure) altogether.

  • Dear sir,
    how to calculate single liquid LP & HP both side same spesifc graviti (0.838)

    H1=90inch
    h2=10inch
    sg.f=0.838
    sg.p=0.838

    i have calculate and my answer had came LRV=-67.04 and URV=0 but once i hace feed same value but transmiter showing 167% like.
    my transmiter is Husser+Endrees .

    Pls let me know ASAP

  • In the diagram SG2 is 1.0 and while solving,u have taken the value SG2 as 1.2 ,
    Kindly explain

  • HELLO,

    ACCORDING TO MY KNOWLEDGE:
    RANGE IS NOTHING BUT URV-LRV
    SO,HERE IN THE ABOVE CASE i.e for DP Transmitter Level Measurement for Closed Tank – Wet Leg Method
    To Cross Verify the Range: H1*SG1 = 500mm*0.9= 450mm;
    Here in the above case at during verification Range:Range = URV – LRV = -210 – (-840) = 630 mmwc the LRV value instead of -660mmwc it is mentioned -840mmwc.I hope that is wrong and we cannot get the range that is to be attained.

  • there are two mistakes in this problem.
    1. In diagram you specified a SG2 as 1.0 but in calculation you used as 1.2
    2.range valve is URV-LRV= -210-(-660)= -210+660 =450mmwc.

    so please verify before posting.. thnak you

  • In closed tank, wet leg, Y does not equal H1 + H2. Y is visibly longer. Either the diagram was not drawn well enough, and you intended the wet leg to be same as the 100% measurement, or your calcs are wrong, and the dimension for Y would be Y=H1+H2+(some other small height)

Share

Recent Articles

  • Instrumentation Design

Immersion Heaters in Lube Oil Consoles

Rotating equipment packages such as pumps, compressors, turbines need the lube oil consoles for their…

3 mins ago
  • PLC Tutorials

How to Blink Lights in Ladder Logic?

This article explains how to blink lights in ladder logic with a detailed explanation video…

3 weeks ago
  • PLC Tutorials

From Boolean Algebra to PLC Logic

In this article, a simple example will teach you the conversion from Boolean algebra to…

1 month ago
  • PLC Tutorials

PLC Cooking Timer Example for Kitchen Automation

In this article, you will learn the PLC cooking timer example for kitchen automation using…

3 weeks ago
  • PLC Tutorials

Example PLC Program to Control a Pump based on Level Sensors

Learn an example PLC program to control a pump based on level sensors using ladder…

3 weeks ago
  • PLC Tutorials

PLC Timer Application in Security Camera Recording

In the PLC timer application for security camera recording, when motion is detected then camera…

3 weeks ago