Actuators may be categorized as ‘direct acting’ or ‘reverse acting’ and some configurations are indicated in Below Figure.

In a reverse acting actuator an increase in the pneumatic pressure applied to the diaphragm lifts the valve stem (in a normally seated valve this will open the valve and is called ‘air to open’).

In a direct acting actuator, an increase in the pneumatic pressure applied to the diaphragm extends the valve stem (for a normally seated valve this will close the valve and is called ‘air to close’).

The choice of valve action is dictated by safety considerations. In one case it may be desirable to have the valve fail fully open when the pneumatic supply fails. In another application it may be considered better if the valve fails fully shut.

Direct Acting Control Valves & Reverse Acting Control Valves

Direct Acting Control Valves & Reverse Acting Control Valves

The fail-safe mode of a pneumatic/spring valve is a function of both the actuator’s action and the valve body’s action.

For sliding-stem valves, a direct-acting actuator pushes down on the stem with increasing pressure while a reverse-acting actuator pulls up on the stem with increasing pressure.

Sliding-stem valve bodies are classified as direct-acting if they open up when the stem is lifted, and classified as reverse-acting if they shut off (close) when the stem is lifted.

Thus, a sliding-stem, pneumatically actuated control valve may be made air-to-open or air-to-close simply by matching the appropriate actuator and body types.

The most common combinations mix a direct-acting valve body with either a reverse – or direct acting valve actuator, as shown in this illustration:

Reverse-acting valve bodies may also be used, with opposite results:

The reverse-acting gate valve body shown in the left-hand illustration is open, with fluid flowing around the stem while the wide plug sits well below the seat area.

Reverse-acting valve bodies tend to be more complex in construction than direct-acting valve bodies, and so they are less common in control valve applications.

Articles You May Like :

Selecting a Solenoid Valve

Pneumatic Valve Actuators

Electronic Valve positioners

Self-Actuated Valves

Control Valve Performance

You've successfully subscribed !

View Comments

  • One thing that is confusing me. If the process signal increase (air is provided to the diaphragm) causes an increase in the valve output (more flow of water) then it is said to be direct acting.

    How is an actuator that when you increase the process signal to (increase the air) causes the valve to open referred to as reverse acting? I am not saying it is not true since I have confirmed it with multiple references, but the confusion is driving me crazy. would appreciate it if someone could clarify. is it just convention that when air opening is on the bottom then the actuator is reverse acting regardless of what happens to the output?

Share

Recent Articles

  • PLC Tutorials

Conveyor Sorting Machine PLC Program with Calculation Function

The conveyor sorting machine is widely used in the packing industries using the PLC program…

4 days ago
  • PLC Tutorials

Example of Flip-Flop PLC Program for Lamps Application

Learn the example of flip-flop PLC program for lamps application using the ladder logic to…

4 days ago
  • PLC Tutorials

STAR DELTA Programming using PLC Controller

In this article, you will learn the STAR DELTA programming using PLC controller to start…

5 days ago
  • Instrumentation Design

Single and Three Phase Immersion Electrical Heaters Wiring Circuits

Lube oil consoles of rotary equipment packages in industrial process plants are usually equipped with…

2 days ago
  • Instrumentation Design

Immersion Heaters in Lube Oil Consoles

Rotating equipment packages such as pumps, compressors, turbines need the lube oil consoles for their…

4 days ago
  • PLC Tutorials

How to Blink Lights in Ladder Logic?

This article explains how to blink lights in ladder logic with a detailed explanation video…

4 weeks ago