Practical Questions

Calculate Incident Power in Radar Level Measurement

Calculate the percentage of incident power reflected back to the transmitter, and the percentage of incident power transmitted (forward) through the liquid in this radar level measurement application:

Radar Level

Calculate Incident Power in Radar Level Measurement

Also, calculate the ullage for this vessel in both units of meters and units of feet/inches, given a reflected pulse (“echo”) time of 11.176 nanoseconds.

Note: the propagation velocity of radio waves in air is approximately 3 × 108 meters per second, the same as the speed of light in a vacuum.

Partial Answer:

Preflected = 63.45%

Ullage = 1.676 meters

More Questions

1. An effective problem-solving technique to apply to the calculation of ullage is to simplify the problem and solve that simplified problem.

In this case, an easy way to “simplify the problem” is to change the numerical values for echo time and speed of light until the solution for ullage becomes obvious even without using a calculator.

Then the formula we must use to calculate any time/speed/ullage echo problem will be apparent. Apply the “simplify the problem” technique to this ullage calculation.

2. Would you say this is an example of good signal reflection, or poor signal reflection? In general terms, what condition(s) make for strong reflected signals for a radar-based level instrument?

Share your answers and explanation with us through the below comments section.

Read Next:

Credits: Tony R. Kuphaldt

You've successfully subscribed !
Share

Recent Articles

  • PLC Tutorials

Conveyor Sorting Machine PLC Program with Calculation Function

The conveyor sorting machine is widely used in the packing industries using the PLC program…

5 days ago
  • PLC Tutorials

Example of Flip-Flop PLC Program for Lamps Application

Learn the example of flip-flop PLC program for lamps application using the ladder logic to…

5 days ago
  • PLC Tutorials

STAR DELTA Programming using PLC Controller

In this article, you will learn the STAR DELTA programming using PLC controller to start…

5 days ago
  • Instrumentation Design

Single and Three Phase Immersion Electrical Heaters Wiring Circuits

Lube oil consoles of rotary equipment packages in industrial process plants are usually equipped with…

3 days ago
  • Instrumentation Design

Immersion Heaters in Lube Oil Consoles

Rotating equipment packages such as pumps, compressors, turbines need the lube oil consoles for their…

5 days ago
  • PLC Tutorials

How to Blink Lights in Ladder Logic?

This article explains how to blink lights in ladder logic with a detailed explanation video…

4 weeks ago