Blast Furnace Panel Modification to Reduce Down Time by 60 to 70%

With the time demand of increasing the efficiency of production facilities to achieve Target, it is required to made the engineering system robust and fool proof .The below  described is used for various systems and subsystems in the industries and are backed up with practical success .The modification is very helpful in achieving the high end target, increased production capacities ,reduction in human effort and make a WIN WIN situation for the both  employees and employers.

Description of system

The blast furnace operations normally using bell operations for charging & employ the services of pneumatic cylinders for operation. These cylinders are operated by pneumatic solenoid valves which are switched on and off by PLC control system. For continuous operations of the furnace, the complete system needs to be healthy.

Standalone  System panel (Existing System)

The available  solenoid valve system are  generally are of  standalone type system where any malfunction/breakdown of solenoid valve will take a long time of say around 30-40 minutes to remove the valve and place a new valve in line. Thus for a huge system like blast furnace the 40 minutes breakdown cost are very high.

The schematic diagram of the standalone system (Fig 1) is indicated below; in this the solenoid valve S/V 5 is operated as per requirement of furnace. The manual valve 3 is put in open condition. The charging frequency depends on the charging mode of the furnace.

Blast Furnace Panel Modification

Modified panel: (Modified System)

The pneumatic system is little bit modified (Shown below Fig 2) with the putting up of a branch line and the spare solenoid valve as shown in below picture. Here one additional solenoid valve indicated by S/V 6 is placed in system .along with this we have placed simple manual on/off valves indicated by NO 1, 2 and 4.

In normal operation the solenoid S/V 5 remains in working and manual valve 1 is placed in open condition. The manual valves 1, 2 and 4 are in closed position.

Once the things are done ,the breakdown if occurs in the solenoid valve ,the manual valves 3 is  closed .after this manual valves 1,2,& 4 are opened .This facilitates for taking S/V 6  in to system ,simultaneously the coil from the existing solenoid valve S/V 5 is to be placed on the spares solenoid valve ,thus the system is healthy for charging the furnace.

The system can be put back in operation within a span of 10-15 minutes at the most against the normally 30-40 minutes required with a standalone system

Another advantage is that the work is done by only 1 technician in shifts,

Thus the system can help to minimize the downtime of system on account of solenoid valve failure.

Article Written by: 

Sh. Pravin V. Maheshkar

Management & technical consultant/trainer  Freelance

Previously Manager –Inst  & Business excellence

(Hindustan zinc ltd ,Echjay steels ltd,total:23 yrs)

You've successfully subscribed !

View Comments

Share

Recent Articles

  • PLC Tutorials

Conveyor Sorting Machine PLC Program with Calculation Function

The conveyor sorting machine is widely used in the packing industries using the PLC program…

5 days ago
  • PLC Tutorials

Example of Flip-Flop PLC Program for Lamps Application

Learn the example of flip-flop PLC program for lamps application using the ladder logic to…

5 days ago
  • PLC Tutorials

STAR DELTA Programming using PLC Controller

In this article, you will learn the STAR DELTA programming using PLC controller to start…

5 days ago
  • Instrumentation Design

Single and Three Phase Immersion Electrical Heaters Wiring Circuits

Lube oil consoles of rotary equipment packages in industrial process plants are usually equipped with…

2 days ago
  • Instrumentation Design

Immersion Heaters in Lube Oil Consoles

Rotating equipment packages such as pumps, compressors, turbines need the lube oil consoles for their…

5 days ago
  • PLC Tutorials

How to Blink Lights in Ladder Logic?

This article explains how to blink lights in ladder logic with a detailed explanation video…

4 weeks ago