Transmitters 4-20mA Current Failure Alarm Limits

4-20 mA instrumentation and controls usually support a signal range slightly below 4 mA and above 20 mA.

For transmitters, current values below 4 mA and above 20 mA are used to signal a fault such as a thermocouple burnout, Signal cable broken, Cable Low/High Resistance, Transmitter Failure or other sensor failure.

The transmitter can be configured for failure indication low or high.

Unfortunately manufacturers use different signal levels to indicate failure which prevents tight analog signal integration and interpretation in single loop controllers, control systems, and safety systems.

Transmitters 4-20mA Current Failure Alarm Limits

Image Source : eddl.org

Some transmitters may use 3.75 mA while others may use 3.6 mA or less. Some transmitter may use 21.75 mA or more while other use 23 mA.

This inconsistency of signal levels for failure indication makes it difficult to take full advantage of the failure information in control strategies.

The NAMUR NE43 “Standardization of the Signal Level for the Failure Information of Digital Transmitters” recommendation was created to standardize failure indication from transmitters and interpretation in control systems to enable better analog integration.

NE43 defines 3.8 to 20.5 mA as a valid (‘Good’) measurement value where 3.8 to 4 and 20 to 20.5 mA indicates saturation.

A signal of <3.6 mA or >21 mA indicates a transmitter failure (‘Bad’).

Image Source : eddl.org

By using transmitters and systems that both conform to the NE43 recommendation, it is possible to flag faults to the operators and control strategies.

However, note that all device errors, severe and trivial, are flagged the same way so the operator cannot tell the difference and that if any error occurs it is flagged and the measurement value is not provided.

FOUNDATION fieldbus and PROFIBUS-PA transmitters use digital communication with separate status indication for each measurement including measurement validity flagged in realtime as ‘Good’, ‘Bad’, or ‘Uncertain’.

This allows operators and control strategies to severe problems from trivial issues. This allows the control strategy to put the loop in manual in case of failure, with the option to trip. For non-severe issues the value is still displayed with ‘Uncertain’ status.

Smart Valve Positioners

Smart valve positioners are not in the scope of NAMUR NE43.

However, signals <4 mA and >20 mA also have specific meanings. Control systems and single loop controllers with 4-20 mA output use a similar scheme to achieve tight shut-off for control valves. That is, they may set current <<4 mA or >>20 mA.

Some control systems set the output current to 0 mA to achieve tight shutoff. This is impractical in the case of smart valve positioners since they need 3.6 mA to operate and will be completely switched off at 0 mA.

Therefore make sure to configure the control system or single loop controller to provide at least 3.6 or 3.8 mA for tight shutoff to ensure that the smart valve positioner can continue to operate and respond to HART communication.

Source : Eddl.org

If you liked this article, then please subscribe to our YouTube Channel for PLC and SCADA video tutorials.

You can also follow us on Facebook and Twitter to receive daily updates.

SIS, PLC and BPCS

Pressure Transmitter Tips

Selector, Override control

Calculate Process Variable

Instrument Air Manifold

You've successfully subscribed !

View Comments

Share

Recent Articles

  • PLC Tutorials

Shutter Door Control using Motor and Limit Switches

 In this article, we are going to discuss about shutter door control using induction motor…

6 days ago
  • Electrical Basics

Electrical Drives – Modes, Types, Speed Control Applications

Electrical Drives control the motion of electric motors. Motion control is required in industrial and…

6 days ago
  • PLC Tutorials

PLC Ladder Logic Design: Control 3 Motors with Toggle Switch

PLC ladder logic design to control 3 motors with toggle switch and explain the program…

3 weeks ago
  • PLC Tutorials

VFD Simulator Download – Free Yaskawa V1000 Software

VFD simulator download: Master the online tool from the Yaskawa V1000 & programming software for…

6 days ago
  • PLC Tutorials

Conveyor Sorting Machine PLC Program with Calculation Function

The conveyor sorting machine is widely used in the packing industries using the PLC program…

1 week ago
  • PLC Tutorials

Example of Flip-Flop PLC Program for Lamps Application

Learn the example of flip-flop PLC program for lamps application using the ladder logic to…

1 week ago