Temperature Controller Problem

Suppose a chemical reactor is heated by steam. A temperature controller varies the amount of steam admitted to a “jacket” surrounding the reactor:

Temperature Controller Problem

Temperature Controller Problem

Ever since this process was placed into service, operators have complained about poor temperature control. Several technicians have tried to tune the PID controller, but no combination of tuning constants seems to solve the problem of random reactor temperature fluctuations.

Then one day you notice that the “random” fluctuations of temperature are not really random at all: they directly follow fluctuations in steam supply pressure over time.

Explain the nature of the control problem (why do variations in steam supply pressure affect the reactor temperature?), and propose a solution for it.

Answer:

As the steam supply pressure rises and falls, a greater or lesser steam flow will result through the temperature valve (TV) for any given stem position.

The simplest and most direct solution to this problem is to stabilize the steam supply pressure: determine what is causing the pressure to fluctuate, and fix it!

Question for you:

Like so many real-life problems, there are usually multiple solutions. Try brainstorming more than one practical solution to this control problem! (assume possible cases).

Join the Discussion! Share your answers with us through below comments section.

Read Next:

You've successfully subscribed !

View Comments

  • If you weren't able to stabilize the steam pressure supply, perhaps you could instead create logic that reacts to a steam pressure transmitter that correspondingly adjusts the TV to adjust for it.

    Thanks for posting these thought experiments by the way! I'm a new intern working in process control and just found this website. Really nice resource.

  • salut. je tient a vous remerci pour ses infos ,car tous ce que je reherche je le trouve sur ce site avec des resumer bien expliquer. merci encors une et bon continuation.

    Translated from french:

    Hi. I want to thank you for this info because all that I am looking for, I find on this site with summaries, explained well. thanks again and good luck

  • Add a flow meter and use cascade control requires capital
    If you have header pressure try to add a feedforward signal to the TC

Share

Recent Articles

  • PLC Tutorials

CX-Programmer Products Sorting & Counting – Omron PLC

Omron PLC logic for sorting the number of products and counting the number of products…

5 days ago
  • PLC Tutorials

Water Fountain Control Logic – PLC Exercises and Solutions

Learn the water fountain control logic using the PLC timers programming to control the high…

4 weeks ago
  • Control Systems

What is Open Telemetry? – Principles and Benefits

Open Telemetry is a framework for collecting data in cloud-native applications including tracing, metrics, and…

7 days ago
  • Common

Control of Pneumatic Cylinder and Motor

This article is about controlling the Pneumatic cylinder and Pneumatic motor in the assembly line…

1 week ago
  • PLC Tutorials

Network Switch Requirement in SCADA and DCS Architecture

In this post, we will learn the basic requirements for a network switch to be…

7 days ago
  • PLC Tutorials

PLC Panel and MCC Panel Interface Signals

The PLC panel and MCC panel interface signals are start, stop, run feedback, trip, local…

1 week ago