In this article, we will see about the Super Heater, and How the Steam Temperature is controlled in the Super Heater.
A Superheater is a set of vertical tubes connected between the headers to minimize the pressure drop of the Superheated Steam.
One Header is connected to the Steam Drum to receive the Saturated Steam and the Other Header is connected to the outlet of the Main Steam Stop valve (MSSV).
The Process of Controlling the temperature of the Super-heated Steam by spraying water of High Purity through the Spray Nozzles. The Device Used is called De-Superheater or Attemperator.
In a Boiler, the Super Heater is Having 3 Stages,
To Generate the Main Steam of Desired Temperature, we use Two Desuperheating Stations, with Two Temperature Loop Control systems that exist between the stages of the Superheater.
In Boiler the Stem Path is from Steam Drum to the Secondary Superheater,
Initially, the Temperature of the Main Steam to be controlled is sent to Primary Superheater (PSH), then to Intermediate Superheater (ISH), and finally to the Secondary Superheater (SSH) through Temperature Control Valve.
The Steam Temperature at Various Stages of the Superheater is as below,
`The outlet of the Secondary Superheater (SSH) is the Main Steam at a designed boiler Steam Parameter, is Sent to Turbine and to PRDS through Steam header.
In This method, the Attemperation spray water of high purity is introduced into the Superheated Steam line through a Spray Nozzle.
The Water rapidly evaporates and mixes with the Steam to reduce the Temperature.
This system provides a Quick Response and Sensitive means of Temperature control of the main steam.
The Steam Temperature is controlled using two Temperature Loop Control systems maintaining a constant temperature at the outlets of the Superheater.
The Steam Temperature control at each stage is the same but the Temperature Set Point is Different in Both Loops.
The Attemperation water is the Boiler feed water that is taken from the feed pump itself.
The Attemperation water of High Purity is sprayed at a high velocity through Spray nozzles and at an adequate quantity on the Desuperheating Station. To reduce the temperature of superheated steam to the required temperature of 350oC in the First loop and 440oC in the Second loop.
The Temperature element (TE) senses the Outlet Steam Temperature and gives a proportional current signal to the PID controller via the Temperature transmitter (TT).
The PID controller then compares the Process Variable (Measured Value) received from the Temperature transmitter (TT) with a given SetPoint (SP), generates an error signal, and is then given to the valve positioner, which determines the position of the Temperature Control Valve (TCV).
This valve opens accordingly and sprays atomized water through the spray nozzle until the steam temperature reaches the set value, and re-closes to prevent the further spray of water after normal conditions have been restored,
i.e. Process Variable (PV) must be equal to SetPoint (SP).
PV=SP
The Components Used in both Temperature Loop Control Systems are.
The Boiler has the Following Specifications:
Note: The temperature and pressure values will vary depending on the boiler type and plant.
Learn an example PLC program to control a pump based on level sensors using ladder…
In the PLC timer application for security camera recording, when motion is detected then camera…
In this example, we will learn batch mixing with PLC ladder logic program using timer…
This PLC example on manufacturing line assembly is an intermediate-level PLC program prepared for the…
In this article, you will learn the PLC programming example with pushbutton and motor control…
This article teaches how to convert Boolean logic to PLC programming ladder logic with the…