In this article, we are going to discuss one root cause analysis in which a Solenoid solenoid-operated valve (SOV) did not open while start-up of the plant. This article is an interesting one.
After the shutdown of the Nitrogen plant in one unit of a refinery, a start-up was planned.
In the start-up procedure, if the product nitrogen’s purity comes within spec, then the product is diverted to the main nitrogen header by opening a final product on-off valve.
Till then, the product is being vented because it is not in proper specs.
During start-up, the specs of the nitrogen were within the limit. So, the panel engineer gave the open command to the final product on-off valve to divert the product nitrogen to the main header. But the valve did not open and a command vs feedback error was generated.
The panel engineer gave the close command and then again gave the open command to the valve. But the valve did not open. So, he informed instrumentation engineers to check the valve.
The on-off valve was a single-acting valve with a fail condition close. The instrumentation team checked and solved the issue within an hour. Then after stroke checking, the on-off valve was taken inline.
During the start-up procedure, when the purity of the nitrogen reached the acceptable limit, the panel engineer gave the open command to the final product on-off valve which diverts the nitrogen to the main header. But the valve did not open.
The panel engineer tried one more time but still, the valve did not open. So, the Instrumentation team was informed about this and they visited the field.
The following activity was done by the Instrumentation team in the field
The instrumentation team replaced the SOV’s coil and the issue was resolved.
Also, on checking the records, it was found that the preventive maintenance (PM) of this valve was done 5 days before the incident. In PM no observation came and the valve operation was ok.
A fault tree analysis was made for this incident which is shown below:
As mentioned in the above fault tree analysis, the valve did not open due to the SOV coil having an issue.
Various reasons mentioned below were considered and a conclusion was made. The reasons are:
Here, SOV’s coil was not in healthy condition and hence the valve was not opening.
2 recommendations came after this incident. These recommendations should be implemented in every plant.
Recommendation 1: In PM activity of a valve, always check the resistance of the SOV coil. In this case, the resistance might have increased gradually over time. This could have been identified in the PM activity if coil resistance checking was done.
Recommendation 2: In LLF activity, check the SOV’s temperature. Abnormally high temperature of SOV indicates that the coil is heating and action needs to be taken.
If you liked this article, then please subscribe to our YouTube Channel for PLC and SCADA video tutorials.
You can also follow us on Facebook and Twitter to receive daily updates.
Read Next:
In this post, we will learn the basic requirements for a network switch to be…
The PLC panel and MCC panel interface signals are start, stop, run feedback, trip, local…
In this article, we are going to discuss about shutter door control using induction motor…
Electrical Drives control the motion of electric motors. Motion control is required in industrial and…
PLC ladder logic design to control 3 motors with toggle switch and explain the program…
VFD simulator download: Master the online tool from the Yaskawa V1000 & programming software for…