An FRP line was continuously getting damaged (cracks were observed). This was occurring very frequently (once per 15 to 20 days).
An FRP line was installed in one plant for supplying water to a mixing tank. The line size was 10 inches. An On-Off valve, an isolation valve, a pressure transmitter, and a flow transmitter were installed in the same line. Almost after every 15 to 20 days, the FRP line got damaged near the On-Off valve.
So, what can be the probable reason for frequent damage to the FRP line?
Probable Problem 1: FRP line not having proper supports
FRP line was installed as per standard and sufficient support was also provided.
Probable Problem 2: FRP line might be thin as compared to the standard / required thickness
FRP thickness verified with standard documents. FRP line thickness was perfect.
Probable Problem 3: High vibrations in FRP line
No vibrations were observed in the FRP line while the water was passing through the line.
Probable Problem 4: High pressure of water flowing through the FRP line.
The pressure of the water is confirmed through the pressure transmitter. The pressure was below maximum operating pressure.
The standard operating pressure was 6 kg/cm2 while the maximum pressure observed during the feed inlet to the tank was 2.8 kg/cm2 due to the unavailability of one out of three feed pumps.
Probable Problem 5: Design issue in the line size and On-Off valve sizing
Design side all parameters reverified with the vendor. All sizing found ok.
Observations after frequent visits to the FRP line during different timings:
During normal operations, the FRP line was very steady like all other lines in the plant. But, whenever the On-Off valve was given close command, the valve got operated by creating a heavy sound.
So, on continuous observation of the valve, it was found that the valve is the main root cause of the FRP pipe getting damaged.
What went wrong?
On further checking by the Instrumentation team, the Instrument air pressure to the On-Off valve was found 6.5 kg/cm2.
(Some basic information: The on-off valve is having a butterfly-type body. The on-Off valve size is 8 inches.
Also, the fail action of the valve is fail-open. So, the air is required to close the valve. As per the datasheet, Instrument Air pressure to the actuator should be a maximum of 4.5 kg/cm2)
The instrumentation team checked the operation of the valve with 6.5 kg/cm2 air pressure and found that the valve movement during the closing time was very fast. This also caused very high vibration and jerks during closing.
So, after a detailed study, it was concluded that there are 2 main reasons for this FRP line getting damaged
Immediately, the Instrument Air pressure to the On-Off valve was normalized to 4.5 kg/cm2. Also, this point was included in LLF to check the Instrument Air pressure of all valves.
Learn an example PLC program to control a pump based on level sensors using ladder…
In the PLC timer application for security camera recording, when motion is detected then camera…
In this example, we will learn batch mixing with PLC ladder logic program using timer…
This PLC example on manufacturing line assembly is an intermediate-level PLC program prepared for the…
In this article, you will learn the PLC programming example with pushbutton and motor control…
This article teaches how to convert Boolean logic to PLC programming ladder logic with the…
View Comments
very good and useful infomation